Fire Protection Services Regulations
under the
Fire Protection Services Act
Amended by:
108/17
2/19
23/26
NEWFOUNDLAND
AND
LABRADOR
REGULATION 45/12
Fire Protection Services Regulations
under the
Fire Protection Services Act
(Filed May 8, 2012)
Under the authority of
section 33 of the Fire Protection Services Act,
I make the following regulations.
Dated at St. Johns
, April 30, 2012.
Kevin O'Brien
Minister of Municipal Affairs
REGULATIONS
Analysis
Short title
Definitions
PART I
ADOPTION OF CODES
Codes adopted
Conflict
PART II
SMOKE AND FIRE ALARM DETECTION SYSTEMS
Application
Compliance with codes and standards
Requirements
Testing and maintenance
PART III
FIRE EXTINGUISHERS AND FIRE EXTINGUISHING SYSTEMS
Fire extinguishers
Plans to be approved
Installation or service of unit or system
Persons qualified for servicing
Notice of commissioning
Equipment not to be inoperative
PART IV
FIREWORKS
Explosives Act ( Canada
Permit required for retail sale
Discharge of family fireworks
Purchase and discharge of aerial fireworks
18.1
Discharge of fireworks during forest fire season
Discharge inside a building
PART V
GENERAL
Transitional
Repeal
Commencement
Schedule
Short title
These regulations may be cited as the Fire Protection Services Regulations.
45/12 s1
Back to Top
Definitions
In these regulations
(a)
"aerial fireworks" means high hazard fireworks as described in Class 7, Division 2, Subdivision 2 of the Explosives Regulations
under the Explosives Act
(Canada) ;
(b)
"family fireworks" means low hazard fireworks for recreation commonly referred to as consumer fireworks, and as described in Class 7, Division 2, Subdivision 1 of the Explosives Regulations
under the Explosives Act
(Canada) ;
(c)
"fireworks" means
the type of explosive classified in accordance with paragraph 36(2)(
f) of the Explosives Regulations, 2013
under the Explosives Act
(Canada);
(d)
"fire extinguishing systems" means manual or automatic extinguishing systems designed to extinguish or limit the growth of a fire and include
(
i) sprinkler systems and other water based
systems,
(ii)
foam based
systems,
(iii)
carbon dioxide systems,
(iv)
halon systems,
(
v) dry chemical systems,
(vi)
wet chemical systems,
(vii)
wetting agents, and
(viii)
clean agent extinguishing systems;
(d.1)
"forest fire season" means a specific period declared by order of the minister;
(e)
"pyrotechics" means theatrical explosives as described in Class 7, Division 2, Subdivision 5 of the Explosives Regulations
under the Explosives Act
(Canada) ;
(f)
"recognized national testing laboratory" means an organization accredited by the Standards Council of Canada;
(g)
"residential occupancies, group C" means the occupancy or use of a building or part of a building by persons for whom sleeping accommodations are provided but who are not harboured or detained to receive medical care or treatment or are not involuntarily detained; and
(h)
"smoke alarm" means a combined smoke detector and audible alarm device designed to sound an alarm within the room or suite in which it is located upon the detection of smoke within that room or suite.
45/12 s2 ; 23/26 s1
PART I
ADOPTION OF CODES
Back to Top
Codes adopted
(1)The following codes are adopted with the additions, alterations or changes as directed by and described in the schedule:
(
a) for the construction of all buildings
(
i) theNational Building Code of Canada, 2015 edition, except
Part 9 where relative to one and 2 family dwellings within Group C, and
(ii)
the National Fire Code of Canada, 2015 edition; and
(
b) for the use and operation of all buildings, processes, areas and vehicles
(
i) the National Fire Code of Canada, 2015 edition, and
(ii)
the NFPA 101, Life Safety Code, 2018 edition, as published by the National Fire Protection Association.
(1.1) Amendments to the codes adopted under subsection (1), and further editions and amendments to those codes, are adopted 6 months following the date of their publication.
(2) Notwithstanding
(
a) Division A, subsection 1.5.1.3 of the National Building Code of Canada and the National Fire Code of Canada; and
(
b) Division B, Subsection 1.3.1 of the National Building Code of Canada and the National Fire Code of Canada,
the standards referenced in all codes adopted by these regulations shall be the current editions of those standards at the date these regulations come into force.
(3) Where, after the coming into force of these regulations, referenced standards in codes adopted by these regulations change or are updated, those standards are adopted 6 months following the date of their publication.
45/12 s3 ; 108/17 s1 ; 2/19 s1
Back to Top
Conflict
In the event of a conflict between the codes adopted under
section 3, the provisions of the National Building Code of Canada shall prevail with regard to
design and construction, except as may be otherwise provided in the schedule.
45/12 s6
PART II
SMOKE AND
FIRE
ALARM DETECTION SYSTEMS
Back to Top
Application
Smoke alarms which comply with the codes adopted under
section 3 shall be installed in:
(
a) new and existing dwelling units and in each sleeping room not within a dwelling unit;
(
b) existing one and 2 family units, owner occupied or rented, unless governed by a municipal by-law;
(
c) privately owned and occupied seasonal cottages and seasonal homes; and
(
d) other areas which may be determined by the fire commissioner.
45/12 s5
Back to Top
Compliance with codes and standards
The installation, testing and maintenance of smoke alarms shall comply with all codes and standards adopted under
section 3 as described in the schedule.
45/12 s6
Back to Top
Requirements
(1)The requirements for fire alarm and detection systems in new or existing buildings shall be as required by the codes and standards adopted under
section 3 as described in the schedule, and
may be varied by order of the fire commissioner for the safety of occupants.
(2) Fire alarm and detection systems shall be designed only by qualified persons in accordance with the National Building Code of Canada and all components of fire alarm and detection systems shall be tested, listed and labelled by a recognized national testing laboratory or as otherwise approved by the fire commissioner.
(3) The installation and verification of all newly installed fire alarm and detection systems and voice communication systems used in conjunction with fire alarm and detection systems shall comply with the National Fire Code of Canada.
(4) Plans for the installation of fire alarm and detection systems shall be approved by the fire commissioner.
45/12 s7
Back to Top
Testing and maintenance
(1)The testing and maintenance of fire alarm and detection systems in buildings shall be performed in accordance with the National Fire Code of Canada.
(2) Qualified personnel performing the tests and maintenance referred to in subsection (1) shall follow the requirements of the National Fire Code of Canada.
(3) A person shall not perform maintenance, repair, inspection, testing or verification of an installed fire alarm and detection system unless, in the opinion of the fire commissioner, that person
(
a) possess the necessary tools and testing equipment to do the work;
(
b) has passed certification examinations to the satisfaction of the fire commissioner; and
(
c) has received the applicable licences.
(4) A licence to perform testing and maintenance of fire alarm and detection systems shall remain in force unless cancelled, suspended, or surrendered.
(5) Fire alarm and detection systems shall be in working order.
(6) Where services are required to installed fire alarm and detection systems, those systems shall not be inoperative for any longer than reasonably necessary for those services to be performed.
(7) Where a fire alarm and detection system is temporarily inoperative in an occupied building required to have a fire alarm and detection system, the person responsible for completing the work shall:
(
a) immediately notify the fire department and monitoring station of the shut down and where that shut down is anticipated to last more than 24 hours, that notification shall be in writing;
(
b) post notices on all floors by elevators and at entrances, stating the fire alarm and detection system is inoperative and that work is being carried out on it and when that work is expected to be completed;
(
c) patrol the area at least once every hour;
(
d) notify the fire department, monitoring station and the building occupants and owner when the work has been completed and the system is operational; and
(
e) in addition to the requirements of paragraphs (
a) to (d), comply with the other fire and life safety requirements of the fire commissioner with respect to the shut-down, if any, for the protection of persons affected by it.
(8) Inoperative fire alarm and detection systems referred to in subsection (7) shall be given high priority in regard to
repairs or adjustments that may be required to restore them to full operation.
45/12 s8
PART III
FIRE
EXTINGUISHERS AND
FIRE
EXTINGUISHING SYSTEMS
Back to Top
Fire extinguishers
(1)A person shall not sell, use or install a portable fire extinguisher within the province unless and until it has been listed and labelled for use in Canada .
(2) A person shall not sell, use or install an obsolete fire extinguisher, including a fire extinguisher which has been noted as obsolete by NFPA 10, Portable Fire Extinguishers, as published by the National Fire Protection Association.
45/12 s9
Back to Top
Plans to be approved
(1)A plan for the installation of a fire extinguishing system and system components shall be approved by the fire commissioner before that system is installed.
(2) Notwithstanding subsection (1), where a fire extinguishing system required for commercial cooking according to NFPA 96, Standard for Ventilation Control and Fire Protection of Cooking Operations is installed, plan approval by the fire commissioner is not required.
45/12 s10
Back to Top
Installation or service of unit or system
(1)A person shall not install or perform a service on a fire extinguisher or fire extinguishing system until, in the opinion of the fire commissioner, that person
(
a) possesses the necessary tools and testing equipment to do that work;
(
b) has passed certification examinations to the satisfaction of the fire commissioner; and
(
c) has received the applicable licence issued by the fire commissioner.
(2) A licence shall remain in force unless cancelled, suspended or surrendered.
(3) All installation and servicing shall be performed in accordance with codes adopted under
section 3 and as described in the schedule.
(4) The fire commissioner may cancel or suspend a licence for non-compliance with the Act or these regulations.
45/12 s11
Back to Top
Persons qualified for servicing
(1)Only persons or agencies fulfilling the requirements of subsection 11(1) shall perform servicing procedures.
(2) An agency shall, as required by the fire commissioner, report the name and address of each qualified person and the number of and names of all trainees in its employ.
(3) A trainee shall perform servicing procedures only under the direct supervision of a qualified person who shall be responsible for the work performed.
45/12 s12
Back to Top
Notice of commissioning
Upon completion of the installation of a fire extinguishing system and upon commissioning of that system, a copy of the installer's or manufacturer's verification shall be submitted to the fire commissioner.
45/12 s13
Back to Top
Equipment not to be inoperative
(1)Installed fire extinguishing systems shall be in working order.
(2) Where services are required to installed fire extinguishing systems, those systems shall not be inoperative for any longer than reasonably necessary for those services to be performed.
(3) Where a fire extinguishing system is temporarily inoperative in an occupied building required to have a fire extinguishing system, the person responsible for completing the work shall
(
a) immediately notify the fire department and monitoring station of the shut down and where that shut down is anticipated to last more than 24 hours, that notification shall be in writing;
(
b) post notices on all floors by elevators and at entrances, stating the fire extinguishing system is inoperative and that work is being carried out on it and when that work is expected to be completed;
(
c) patrol the area at least once every hour;
(
d) notify the fire department, monitoring station and the building occupants and owner when the work has been completed and the fire extinguishing system is operational; and
(
e) in addition to the requirements of paragraphs (
a) to (d), comply with the other fire and life safety requirements of the fire commissioner with respect to the shut-down, if any, for the protection of persons affected by it.
(4) Inoperative fire extinguishing systems referred to in subsection (3) shall be given high priority in regard to
repairs or adjustments that may be required to restore them to full operation.
45/12 s14
PART IV
FIREWORKS
Back to Top
Explosives Act ( Canada
Only fireworks which have been authorized under the Explosives Act
(Canada) may be stored, sold or used in the province.
45/12 s15
Back to Top
Permit required for retail sale
(1)A person shall not offer family fireworks for retail sale unless that person has obtained a permit from the fire commissioner authorizing the storage and sale of those fireworks in accordance with these regulations and the applicable federal requirements.
(2) A permit issued under subsection (1) shall remain in force until cancelled, suspended or surrendered.
(3) The fire commissioner may cancel or suspend a permit for non-compliance with the Act, these regulations or the applicable federal requirements.
45/12 s16
Back to Top
Discharge of family fireworks
A person shall not discharge or displayfamily fireworks unless that person
(
a) is over 18 years of age;
(
b) discharges fireworks in accordance with instructions printed on each item or package; and
(
c) exercises care and caution in the discharge of those fireworks.
45/12 s17
Back to Top
Purchase and discharge of aerial fireworks
(1)A person shall not discharge aerial fireworks unless a permit from the fire commissioner is obtained authorizing the discharge or display.
(2) A permit issued for outside discharge or display of aerial fireworks is valid only for the date and area for which it is issued.
(3) The discharge or display of aerial fireworks shall be under the direction of a person authorized to do so by the applicable federal regulatory authority.
45/12 s18
Back to Top
Discharge of fireworks during forest fire season
18.1.
A person shall not discharge fireworks outdoors during the forest fire season where the discharge of fireworks is prohibited under subsection 5(2) of the Forest Fire Regulations .
23/26 s2
Back to Top
Discharge inside a building
(1)A person shall not discharge fireworks inside a building.
(2) Notwithstanding subsection (1), the fire commissioner may issue a permit for the discharge of pyrotechnics within a building for special occasions, including theatrical performances, and may stipulate the conditions under which that discharge may be permitted.
45/12 s19
PART V
GENERAL
Back to Top
Transitional
A permit issued under the Fire Protection Act, 1991,
for installation, inspection or maintenance of
(
a) fire alarm and detection systems; or
(
b) fire extinguishers and fire extinguishing systems
shall be valid for a period of 12 months following the coming into force of these regulations only, at which time all permits for those purposes issued under the former Act shall be cancelled.
45/12 s20
Back to Top
Repeal
The following regulations are repealed:
(
a) Fire Prevention Fire Extinguisher and Fixed Fire Extinguishing Systems Regulations , Consolidated Newfoundland
and Labrador
Regulation 958/96;
(
b) Fire Prevention Fireworks Regulations , Consolidated Newfoundland
and Labrador
Regulation 8/96;
(
c) Fire Prevention Flammable and Combustible Liquids Regulations , Consolidated Newfoundland
and Labrador
Regulation 959/96;
(
d) Fire Prevention Regulations,
Consolidated Newfoundland
and Labrador
Regulation 9/96; and
(
e) Fire Prevention Smoke and Fire Alarm Regulations , Consolidated Newfoundland
and Labrador
Regulation 960/96.
45/12 s21
Back to Top
Commencement
These regulations come into force on June 1, 2012.
45/12 s22
Back to Top
Schedule
Fire and Life Safety
Interpretation
(1)In this
Schedule
(a)
"addition" means an increase in building area, aggregate floor area, height, or number of stories of a structure;
(b)
"adopted code" means the applicable code as adopted under
section 3 of the regulations;
(c)
"authority having jurisdiction" means the government body responsible for the enforcement of a part of the referenced code or the official or agency designated by that body to exercise that function;
(d)
"change of occupancy classification" means a change in the occupancy classification of a structure or portion of a structure;
(e)
"change of use" means a change in the purpose or level of activity within a structure that involves a change in application of the requirements of the Act, regulations and adopted codes;
(f)
"existing building or structure" means building or structure approved for occupancy by the AHJ
or a building or structure which is currently occupied;
(g)
"historic building" means a building or facility considered to have historical, architectural, or cultural significance by a local, regional, or national authority;
(h)
"modification" means
(
i) the addition or elimination of load-bearing elements,
(ii)
the reconfiguration of any space,
(iii)
the addition or elimination of any door or window;
(iv)
the reconfiguration or extension of any system, or
(
v) the installation of any additional equipment;
(i)
"new construction" means a building or structure which is
(
i) under construction, or
(ii)
not approved for occupancy by the AHJ;
(j)
"reconstruction" means
(
i) the reconfiguration of a space that affects an exit, or a corridor shared by more than a single tenant, or
(ii)
the reconfiguration of space so that the rehabilitation
work area is not permitted to be occupied because existing means of egress and fire protection systems, or their equivalent, are not in place or continuously maintained;
(k)
"rehabilitation"
means any work on an existing building
classified as:
(
i) repair,
(ii)
renovation,
(iii)
modification,
(iv)
reconstruction,
(
v) change of use of occupancy, or
(vi)
addition;
(l)
"renovation" means
(
i) the replacement in kind or strengthening of load bearing elements, or
(ii)
the refinishing, replacement, bracing, strengthening, or upgrading of existing materials, elements, equipment or fixtures, without involving the reconfiguration of spaces; and
(m)
"repair" means the patching, restoration, or painting of materials, elements, equipment, or fixtures for the purpose of maintaining those materials, elements, equipment or fixtures in good or sound condition.
(2) Words and phrases used in this
schedule that are not included in this
section shall have the meanings which are commonly assigned to them in the context in which they are used, taking into account
the specialized use of terms with the various trades and professions to which the terminology applies.
(3) The following abbreviations are used in this schedule:
(
a) AHJ: authority having jurisdiction;
(
b) LSC: NFPA 101 Life Safety Code;
(
c) NBCC: National
Building
Code of Canada ;
(
d) NFCC: National Fire Code of Canada ; and
(
e) NFPA: National Fire Protection Association.
Back to Top
Application and use
(1)This
schedule directs the application and use of the adopted codes.
(2) This
schedule directs the application and use of the appropriate codes, sections or chapters of codes that shall be used for
(
a) the design, construction, operation of new structures; and
(
b) the use and operation of existing
structures.
(3) This
schedule identifies the procedures that owners or developers shall follow in the repair, renovation, modification, reconstruction, change of use or change of occupancy classification , and addition
to existing structures including historic buildings .
Back to Top
Existing buildings
(1)This
schedule permits repairs , renovations, modifications, reconstructions, additions, and changes of use that maintain or improve the health, safety, and well-being of occupants in existing
buildings, without requiring full compliance with the adopted codes,
except for proportional additional work as specified in this
schedule and the LSC .
(2) Nothing in this
section shall be interpreted as requiring the repair , renovation , modification
or reconstruction
of existing
buildings, but in all circumstances the requirements of the adopted codes shall be met.
(3) All work shall be classified into categories of:
(
a) repair;
(
b) renovation;
(
c) modification;
(
d) reconstruction;
(
e) change of use; or
(
f) addition
with specific requirements established for each category according to the LSC .
Back to Top
Compliance
(1)Existing life safety features which are obvious to the public, if not required by the adopted codes , shall be either maintained or removed.
(2) This
schedule shall not supersede any adopted codes or ordinances that address dangerous or unsafe buildings.
(3) Buildings and structures located in whole or in
part in a floodway or floodway fringe shall conform to the Newfoundland
and Labrador Provincial Land Use Policy Flood Risk Areas .
(4) The minimum design loads for a structure shall be the loads applicable at the time the building was constructed, provided that no structurally deficient condition is created.
(5) Notwithstanding subsection (4), structural elements that are uncovered during the course of
the building rehabilitation
which are found to be unsound or structurally deficient shall comply with the load requirements of the NBCC .
(6) Where a rehabilitation
work area includes a commercial kitchen and the work includes reconfiguration or extension of cooking equipment or the installation of additional cooking equipment, existing grease ducts, exhaust equipment, and kitchen hoods shall be brought into compliance with the requirements of NBCC .
(7) Where
(
a) a rehabilitation
work area is more than 50 percent of the gross floor area; or
(
b) the occupant load is intended to be increased by at least 20 percent as a result of
the rehabilitation
work,
the plumbing system shall be upgraded to the NBCC .
(8) Rehabilitation
work, including an addition,
shall not create or extend any nonconformity to the adopted codes in the existing building
in which the rehabilitation
work or the addition
is constructed.
Back to Top
Preliminary meeting
(1)Where a building permit is required for a rehabilitation
project involving multiple adopted codes
, before the submission of the construction permit application and upon the request of the applicant and the payment of any required fees, the AHJ
or its designee and representatives from all necessary agencies may meet with the applicant to
discuss plans for any proposed work or change of occupancy.
(2) The meeting referred to in subsection (1) shall, to the extent possible, include the officials responsible for permit approval and enforcement with respect to the following, as applicable to the rehabilitation
project:
(
a) National Building Code of Canada;
(
b) National Plumbing Code of Canada;
(
c) NFPA 101, LSC;
(
d) Canadian Electrical Code;
(
e) National Fire Code of Canada;
(
f) Public Safety Act ;
(g)
(
h) Historic Resources Act ;
(3) Decisions made at the meeting shall be documented and circulated to those in attendance.
(4) For a rehabilitation
project or portion of it that is in the repair , renovation, or modification
category of work, a preliminary meeting may be permitted to be granted at the discretion of the AHJ
when a request for a preliminary meeting is made by the prospective applicant prior to the submission of the construction permit application.
(5) The rehabilitation
work area shall be clearly identified on all construction permit applications, construction documents, and permits required by the AHJ .
Back to Top
Design, coustruction, use & occupancy - new construction
(1)Building plans submitted for approval shall meet the requirements of the regulations, adopted codes and this schedule.
(2) All new construction
, including construction and development shall meet the requirements in the table:
New Construction
OCCUPANCY TYPE
DESIGN, CONSTRUCTION, USE & OCCUPANCY
GENERAL NOTES
NBCC Occupancy Classification
LSC Occupancy
Classification
Group A - Division 1,2,3,4 Assembly
ASSEMBLY
NBCC, NFCC AND
CHAPTER 12 LSC
Group A - Division 2 Assembly
EDUCATION
NBCC, NFCC AND
CHAPTER 14 LSC
Group A - Division 2 Assembly
DAY
- CARE
NBCC, NFCC AND
CHAPTER 16 LSC AND
DAY
- CARE
REGS.
Group B - Division 1 Detention
DETENTION & CORRECTIONAL
NBCC, NFCC AND
CHAPTER 22 LSC
Group B - Division 2 Treatment
HEALTH CARE
NBCC, NFCC AND
CHAPTER 18 LSC
Group B- Division 3
Care
RESIDENTIAL BOARD AND CARE
NBCC, NFCC,
Chapter 32 LSC and NL Personal Care Home Policy Manual
Group C Residential
ONE
& TWO FAMILY
DWELLINGS
NO REQUIREMENTS
Group C Residential
LODGING & ROOMING HOUSES
NBCC, NFCC AND
CHAPTER 26 LSC
Group C Residential
HOTELS & DORMITORIES
NBCC, NFCC AND
CHAPTER 28 LSC
Group C Residential
APARTMENT BUILDINGS
NBCC, NFCC AND
CHAPTER 30 LSC
Group D Business and personal services
AMBULATORY HEALTH CARE
NBCC, NFCC AND
CHAPTER 20 LSC
Group D Business and personal services
BUSINESS
NBCC, NFCC AND
CHAPTER 38 LSC
Group E Mercantile
MERCANTILE
NBCC, NFCC AND
CHAPTER 36 LSC
Group F - Division 1,2,3 Industrial
INDUSTRIAL
NBCC, NFCC AND
CHAPTER 40 LSC
Group F - Division 2,3 Industrial
STORAGE
NBCC, NFCC AND
CHAPTER 42 LSC
(3) N ew construction
shall follow the NBCC
for design and construction with the only exception of the means of egress.
(4) Means of egress for new construction
shall comply with
Chapter 7 of the LSC
unless otherwise provided for or modified by the individual occupancy chapters, which shall prevail.
(5) The requirements for the use and occupancy of the building shall follow the NFCC
and the applicable occupancy
chapter for new construction
requirements in the NFPA 101, LSC .
(6) The use and occupancy requirements shall be incorporated into the design and construction of the building.
(7) There shall be no use and occupancy requirement for design and construction that exceeds
(
a) the requirements of the NBCC; or
(
b) section 2, Means of Egress, of the applicable occupancy
chapter of the NFPA 101, LSC.
Back to Top
Use and occupancy - existing
buildings
(1)E xisting buildings
shall meet the requirements of the regulations, adopted codes, this
schedule and the requirements in the table:
Existing Buildings
OCCUPANCY TYPE
USE & OCCUPANCY
GENERAL NOTES
EXISTING
ASSEMBLY
NFCC AND
CHAPTER 13 LSC
EDUCATION
NFCC AND
CHAPTER 15 LSC
DAY
- CARE
NFCC AND
CHAPTER 17 LSC AND
DAY
- CARE
REGULATIONS
HEALTH CARE
NFCC AND
CHAPTER 19 LSC
AMBULATORY HEALTH CARE
NFCC AND
CHAPTER 21 LSC
DETENTION & CORRECTIONAL
NFCC AND
CHAPTER 23 LSC
ONE
& TWO FAMILY
DWELLINGS
NO REQUIREMENTS
LODGING & ROOMING HOUSES
NFCC AND
CHAPTER 27 LSC
HOTELS & DORMITORIES
NFCC AND
CHAPTER 29 LSC
APARTMENT BUILDINGS
NFCC AND
CHAPTER 31 LSC
RESIDENTIAL BOARD & CARE
NFCC AND
CHAPTER 33 LSC AND
PERSONAL CARE
HOME POLICY MANUAL
MERCENTILE
NFCC AND
CHAPTER 37 LSC
BUSINESS
NFCC AND
CHAPTER 39 LSC
INDUSTRIAL
NFCC AND
CHAPTER 41 LSC
STORAGE
NFCC AND
CHAPTER 43 LSC
(2) E xisting buildings
shall meet the requirements of NFCC ; and the applicable
chapter for existing buildings in the NFPA 101, LSC .
(3) Means of egress for existing buildings shall comply with
Chapter 7 of the LSC
unless otherwise provided for or modified by the individual occupancy chapters.
(4) There shall be no use and occupancy requirement for existing buildings
that exceeds
(
a) the requirements of the NBCC; or
(
b) the applicable existing occupancy
chapter of the NFPA 101, LSC
(5) Where an existing building
requires upgrading to meet the requirements of subsection (2), the owner may be subject to a fire commissioner's order to correct any deficiencies and that order shall be implemented in accordance with sections 8 and 9.
(6) Subject to the approval of the AHJ
, where a deficiency has been identified and a directive has been issued for the correction of the deficiency, the period for compliance to meet subsection (2) may be extended as follows:
(
a) fire protection features, 5 years;
(
b) structural requirements, 5 years;
(
c) means of egress requirements, 2 years; and
(
d) fire alarm and detection systems, 2 years.
(7) The owner may submit a life safety evaluation in accordance with
section 12 to comply with subsection (2).
(8) This
section
shall not apply to historic buildings
that are not undergoing rehabilitation
Back to Top
Rehabilitation work areas
(1)Where a rehabilitation
work area is in a building that is required to have a fire alarm and detection system in accordance with the NBCC, the fire alarm and detection system shall be installed throughout the entire building.
(2) Where a rehabilitation work area is in a building that is not equipped with a fire alarm and detection system, and the rehabilitation work when completed, changes the occupancy classification or the occupant loading, a fire alarm and detection system shall be installed throughout the entire building in accordance with the NBCC.
(3) Where a rehabilitation
work area is in a building that is required to have a sprinkler system in accordance with the NBCC, the sprinkler system shall be installed throughout the entire building.
(4) Where a rehabilitation work area is in a building that is not equipped with a sprinkler system, and the rehabilitation work when completed, changes the occupancy classification, building area or number of stories, a sprinkler system shall be installed throughout the entire building in accordance with NBCC.
(5) Where a rehabilitation work area is in a building that is not equipped with a sprinkler system and the rehabilitation work is less than 50% of the aggregate floor area a life safety evaluation may be provided in accordance with
section 12.
Back to Top
Historic buildings
(1) The
repair, renovation , modification , reconstruction , and change of use or occupancy of historic buildings shall comply with:
(
a) NFPA 101, LSC;
(
b) NFPA 914, Code for Fire Protection of Historic Structures; or
(
c) Fire Safety Alternatives for Heritage Buildings in St. Johns
, NL.
(2) For historic buildings
or structures located in whole or in
part in floodway or floodway fringe, work on the building or structure shall be permitted, provided that
both of the following are met:
(
a) the proposed work will not preclude continued designation as a historic building or structure; and
(
b) approval has been given by the Department of Municipal Affairs under the Newfoundland
and Labrador Provincial Land Use Policy, Flood Risk Areas.
Back to Top
Code conflicts
Where a conflict exists or appears to exist between 2 or more adopted code
requirements, sections 6 and 7 shall apply.
Back to Top
Code application where uncertainty
(1)Where the NBCC or the NFCC
does not, in the opinion of the fire commissioner, address an issue or does not provide detailed requirements, the applicable
Chapter for new construction
of NFPA 101, LSC
shall apply.
(2) Where the NFCC does not, in the opinion of the fire commissioner, address an issue or does not provide detailed requirements, the applicable
Chapter for existing buildings of NFPA 101, LSC shall apply.
(3) There shall be no use and occupancy requirement for existing buildings that exceeds the requirements of the NBCC or
section 2 of the applicable occupancy
chapter for existing buildings of the NFPA 101, LSC.
Back to Top
Life safety evaluation
Where the owner of an existing building
feels it is impractical to upgrade to meet code
compliance, the owner may submit a life safety evaluation to the AHJ for approval to meet fire and life safety equivalency in accordance with the adopted codes.