Safety Regulations (N.S. Reg. 48/2003) (just regulations regs fsfiresf.htm)

N.S. Reg. 48/2003

Nova Scotia — Regulations

Safety Regulations (N.S. Reg. 48/2003) (just regulations regs fsfiresf.htm)

N.S. Reg. 48/2003

Nova Scotia — Regulations

This consolidation is unofficial and is for reference only.

For the official version of the regulations, consult the original documents on file with the Office of the Registrar of Regulations , or refer to the Royal Gazette

Part II .

Regulations are amended frequently.

Please check the list of Regulations by Act to see if there are any recent amendments to these regulations filed with our office that are not yet included in this consolidation.

Although every effort has been made to ensure the accuracy of this electronic version, the Office of the Registrar of Regulations assumes no responsibility for any discrepancies that may have resulted from reformatting.

This electronic version is copyright ©

, Province of Nova Scotia , all rights reserved. It is for your personal use and may not be copied for the purposes of resale in this or any other form.

Fire Safety Regulations

made under

Section 51 of the

Fire Safety Act

S.N.S. 2002, c. 6

O.I.C. 2003-83 (effective February 28, 2003), N.S. Reg. 48/2003

amended to O.I.C. 2025-77 (effective April 1, 2025), N.S. Reg. 60/2025

Table of Contents

Please note: this table of contents is provided for convenience of reference and does not form part of the regulations.

Click here to go to the text of the regulations .

Citation

Interpretation

Part 1 - Council and Committees

Fire Safety Advisory Council

Role of Council

Fire Services Advisory Committee

Role of Committee

Part 2—General Fire Safety Provisions

Building Plans

Plans to be provided to Fire Marshal

Review by Fire Marshal of other plans

Municipal Inspections

Responsibility of municipality to inspect

Failure of municipality to inspect

Prescribed expenditure amount for orders

Fire Hose Couplings

Interpretation

Standards for fire department equipment and standard hose

Fire protection for water system or supply

Portable Fire Extinguishers

Interpretation

Exemptions

Prohibitions

Issue of licence

Suspension or revocation of licence

Insurance Industry Fire Reports

Preliminary insurance report

Final insurance report

Part 3 - Fire Code

Adoption of Fire Code

Interpretation

Modifications to National Fire Code

Defined terms

Applicable editions

Sentences 2.1.2.2.(3) and 2.1.2.2.(4) repealed

Decorative materials

Occupant load

Posting of fire emergency procedures

Boarding and lodging houses

Farm buildings

Additional functional statements and objectives for Table 2.15.1.1.

Appointment of chief fire warden

Section 2.16 Chief Fire Wardens

2.16.1. Chief Fire Wardens

2.16.1.1. Appointment

2.16.1.2 Inspection

Clause 4.1.1.1.(3)(

c) modified

Sentence 4.1.1.1.(4) repealed

Section 4.12. repealed

Handling and discharge of fireworks

5.1.1.3. Handling and Discharge of Fireworks and Pyrotechnics

Repairs to fire protection system

6.1.1.4. Repairs

Lightning protection systems

Additional functional statements and objectives for Table 6.9.1.1.

Retrofits of boarding, lodging and rooming houses

Part 8

Retrofits of Boarding, Lodging and Rooming Houses

Section 8.1 General

8.1.1. General

8.1.1.1. Application

8.1.1.2. Containment

8.1.1.3. Floor Assemblies

8.1.1.4. Basement Fire Separations

8.1.1.5. Sleeping Areas and Bedroom Fire Separations

8.1.1.6. Furnace Room Fire Separations

8.1.1.7. Combustion Air

8.1.1.8. Means of Egress

8.1.1.8A. Handrails and Guards

8.1.1.9. Acceptable Exits

8.1.1.10. Approval of Fire Official

8.1.1.11. Fire Escapes

8.1.1.12. Protection of Exits

8.1.1.13. Interior Stairways

8.1.1.14. Protection of Openings in Fire Separations

8.1.1.15. Exit Signs

8.1.1.16. Interior Finishes

8.1.1.17. Illumination of Egress

8.1.1.18. Emergency Lighting

8.1.1.19. Fire and Smoke Alarm Requirements

8.1.1.19A. Emergency Planning

8.1.1.20. Fire Suppression

Section 8.2. Objectives and Functional Statements

8.2.1. Objectives and Functional Statements

8.2.1.1. Attribution to Acceptable Solutions

Form 1—Preliminary Insurance Report Form

Form 2—Final Insurance Report Form

Citation

1 These regulations may be cited as the Fire Safety Regulations .

Interpretation

(1) In these regulations,

“Act” means the Fire Safety Act ;

“Building Code” means the National Building Code of Canada, as adopted and

modified under the Building Code Act and the Nova Scotia Building Code

Regulations ;

“Committee” means the Fire Services Advisory Committee created by the Minister

under subsection 12(4) of the Act and referred to in

Section 5;

“Fire Code” means the fire code adopted pursuant to the Act, as set forth in

Section 27;

“National Fire Code” means the National Fire Code of Canada 2020 issued by the

National Research Council of Canada, as amended.

(2) Unless otherwise defined in the Act or these regulations, expressions that are

defined in the National Fire Code have the same meaning when used in these

regulations.

Part 1 - Council and Committees

Fire Safety Advisory Council

(1) The Council must be composed of the following members:

(

a) the Fire Marshal or the Fire Marshal’s representative;

(b) 1 representative from the Building Code Advisory Committee established

by the Building Code Act , as selected by that committee;

(c) 1 representative from the Nova Scotia Federation of Municipalities, as

selected by that association;

(d) 1 representative from the Fire Inspectors Association of Nova Scotia, as

selected by that organization;

(e) 1 representative from the Nova Scotia Building Officials Association, as

selected by that organization;

(f) 1 representative from the Insurers Advisory Organization, as selected by that

organization;

(g) 1 representative from the Insurance Bureau of Canada, as selected by that

organization;

(h) 1 representative from the Design and Construction Institute of Nova Scotia,

as selected by that organization;

(i) 1 representative from the Fire Service s Association of Nova Scotia, as

selected by that organization;

(j) 1 representative from the Nova Scotia Education Common Services Bureau,

as selected by that organization;

(

k) up to 3 additional members, as selected by the Minister;

(l) 1 representative from the Department responsible for the Building Code Act

who is knowledgeable about the Building Code, as selected by the Minister.

(2) If an organization specified in subsection (1) is unable to select a representative,

the Minister may appoint a member selected by a similar organization that the

Minister determines to be a replacement organization.

(3) A Council member’s term of appointment must not exceed 3 years.

(4) The Minister must designate 1 member of the Council as Chair and that member

must preside as Chair at meetings of the Council.

(5) Members of the Council must serve without remuneration.

Role of Council

4 It is the role of the Council to receive and hear petitions, briefs, and comments from

individuals or groups with respect to the Act.

Fire Services Advisory Committee

(1) The Committee must be composed of the following members:

(

a) the Fire Marshal or the Fire Marshal’s representative;

(b) 1 representative from the Department of Municipal Affairs, as selected by

the Deputy Minister of that Department;

(c) 1 representative from the Fire Inspectors Association of Nova Scotia, as

selected by that organization;

(d) 3 representatives from the Fire Service Association of Nova Scotia, as

selected by the membership of that organization;

(e) 1 representative of the firefighters in Nova Scotia who are unionized, as

selected by the Minister;

(f) 1 representative of Halifax Regional Fire and Emergency, as selected by the

Regional Council of the Halifax Regional Municipality;

(g) 1 representative of the Cape Breton Regional Fire Service, as selected by the

Regional Council of the Cape Breton Regional Municipality;

(h) 1 representative of the industrial fire brigades, as selected by the Industrial

Fire Brigades Committee;

(

i) up to 3 additional members, as selected by the Minister.

(2) If an organization specified in subsection (1) is unable to select a representative,

the Minister may appoint a member selected by a similar organization that the

Minister determines to be a replacement organization.

(3) A Committee member’s term of appointment must not exceed 3 years.

(4) The Minister must designate 1 member of the Committee as Chair and that

member must preside as Chair at meetings of the Committee.

(5) Members of the Committee must serve without remuneration.

Role of Committee

6 It is the role of the Committee to

(

a) advise the Minister on Provincial legislation and policies with respect to the

delivery of fire services;

(

b) receive and hear petitions, briefs and comments from individuals or groups

with respect to Provincial fire services;

(

c) recommend legislation, policies, and practices to promote efficiency in the

administration and operation of emergency fire services; and

(

d) advise the Council on matters with respect to the delivery of fire services.

7 [repealed]

8 [repealed]

9 [repealed]

10 [repealed]

11 [repealed]

Part 2—General Fire Safety Provisions

Building Plans

Plans to be provided to Fire Marshal

(1) Prior to the start of construction, an owner of a building or facility containing one

of the following classes of occupancies must provide sealed building plans for the

construction or alteration of the building or facility to the Fire Marshal:

(

a) an assembly occupancy (Group

A) that

(

i) is more than 3 storeys high including the storeys below grade, or

(ii) has an area greater than 600 m 2 , or

(iii) is in a non-residential building that is used for a school, college or

university and that has an occupant load of more than 40 persons;

(

b) a care, treatment or detention occupancy (Group B);

(

c) a residential occupancy (Group

C) that is licensed or regulated under the

Homes for Special Care Act; and

(

e) a high hazard industrial occupancy (Group F, Division 1) that is more than 2

storeys high or has an area greater than 600 m 2 .

Review by Fire Marshal of other plans

(2) The Fire Marshal may, at the request of a professional engineer or architect, review

plans for changes to a building or facility not listed in subsection (1), and the fee

for the review of the sealed building plans is $96.50 per hour plus any expenditures

related to the performance of the plan review.

Municipal Inspections

13 [repealed]

Responsibility of municipality to inspect

(1) A municipality must inspect an assembly occupancy (Group

A) once every 3 years.

(2) A municipality must carry out a system of fire inspections on all buildings

containing the following occupancies:

(

a) a residential occupancy (Group

C) that has more than 3 units and is not

regulated under the Homes for Special Care Act ;

(aa) a residential occupancy (Group

C) that meets all of the following

conditions:

(

i) it has 3 or fewer units,

(ii) is not regulated under the Homes for Special Care Act ,

(iii) the municipal fire inspection office has received a complaint that a

fire or life safety issue exists in the building from a representative of

one of the following:

(

A) a Provincial government department or agency,

(

B) a fire department with jurisdiction over the property,

(

C) a police agency with jurisdiction over the property;

(

b) a business and personal services occupancy (Group D);

(

c) a mercantile occupancy (Group E); and

(

d) an industrial occupancy (Group F).

Failure of municipality to inspect

15 If a municipality fails to carry out an inspection required under

Section 14, the Fire

Marshal is required to carry out the inspection and the municipality must pay an

inspection fee of $96.50 per hour plus any expenditures related to the performance of the

inspection.

Prescribed expenditure amount for orders

15A For the purpose of clause 30(1)(

e) of the Act, $5000 is prescribed as the maximum

amount of an expenditure in respect of an order made under

Section 25 of the Act that

may be carried out or caused to be carried out by a fire official without further

authorization.

Fire Hose Couplings

Interpretation

16 For the purposes of Sections 17 and 18,

“adapter” means any means by which the coupling of one

section or portion of

standard hose that has one type of thread may be connected to a hydrant, nozzle,

other adapter or coupling of another

section or portion of standard hose that has a

different type of thread;

“fire department equipment” includes all fire hydrants, nozzles, hose, adapters,

couplings, attachments and appliances ordinarily used by a fire department; and

“standard hose” means fire hose with an inside diameter of 2.5 in., and includes

couplings, connections, fittings and attachments.

Standards for fire department equipment and standard hose

(1) Despite any bylaw, regulation or resolution passed by the council of a municipality,

all fire department equipment and standard hose used by a municipality must be

Nova Scotia Standard Thread, 5 threads to 1 in.

(2) All fire hose coupling screw threads for the standard hose referred to in subsection

(1) must meet the specifications for their size as set out in the following table:

Coupling Descriptions

Inside Diameter of Hose Coupling (in inches)

2 ½

4 ½

Number of threads per inch

Total length of threaded part

of coupling and hydrant nipple

external thread in inches

1 16/64

1 16/64

Distance from face nipple to

start of second turn in inches

16/64

24/64

28/64

Outside diameter of finished

male thread in inches

3 15/64

4 56/64

5 48/64

Clearance between external

and internal thread in inches

0.05

0.05

0.05

Flat at top and valley of thread

in inches

0.02

0.02

0.02

Distance from face of

coupling swivel to start of

second turn in inches

12/64

24/64

24/64

Depth of coupling swivel

thread from face of swivel in

inches

44/64

60/64

60/64

Depth of coupling swivel to

washer seat in inches

60/64

1 12/64

4 12/64

(3) Except as permitted by subsection (4), all fire hose coupling screws must meet the

following requirements:

(

a) nipple, male or external thread must be cylindrical to the base of the thread

at the beginning of the second turn;

(

b) coupling swivel, female or internal thread must be cylindrical to the base of

the thread at the beginning of the second turn;

(

c) the outer end of the external and internal thread must be terminated by the

Higbee Cut on the full thread to avoid crossing and mutilation of otherwise

finely drawn out thread; and

(

d) the form of the screw thread must be a V pattern with an included angle of

60° and truncated at the top and bottom in accordance with the specified

dimensions.

(4) A fire hose coupling may be a nonthreaded connection if all of the following

conditions are met:

(

a) the nonthreaded connection is listed for fire department use;

(

b) the coupling is a minimum of 100 mm in diameter;

(

c) the coupling is used for a high-volume supply;

(

d) the coupling is used to supply an apparatus or distribution device that is

listed for fire department use.

Fire protection for water system or supply

(1) A municipality must ensure that the fire department equipment of a public or

municipal water system or water supply used for fire protection purposes complies

with

Section 17.

(2) An owner who has a fire department connection for their water supply, including a

sprinkler system, standpipe or hydrant, must comply with

Section 17.

Portable Fire Extinguishers

Interpretation

19 For the purposes of this

Section and Sections 20 to 24,

“licence” means a licence issued under

Section 23 to engage in the business of

servicing portable fire extinguishers;

“portable fire extinguisher” means an appliance, apparatus, container or device that

is designed to be or is capable of being readily moved and that

(

i) contains or produces any liquid, powder or gas usable for the purpose

of extinguishing fire; or

(ii) appears by reason of its name, description or designation to be usable

for the purpose of extinguishing fire, and includes a recharge or refill

for any such appliance, apparatus, container or device;

“person” includes a partnership, corporation, firm or association; and

“servicing” includes testing, inspecting, maintaining, repairing, filling, charging,

refilling and recharging.

Exemptions

20 Sections 21 to 24 do not apply to

(

a) the filling or charging of a portable fire extinguisher by its manufacturer

prior to its sale; or

(

b) a fire department or person that services only their own portable fire

extinguishers for their own use by maintaining their own servicing facilities

and using their own personnel specially trained for servicing portable fire

extinguishers.

Prohibitions

21 No person may sell or distribute or have in their possession for the purpose of sale or

distribution a portable fire extinguisher unless it meets the requirements of the Fire Code.

22 No person may service or engage in the business of servicing a portable fire extinguisher

unless they hold a valid licence.

Issue of licence

(1) A person may apply to the Fire Marshal for a licence.

(2) The Fire Marshal may issue a licence with or without restrictions if

(

a) the Fire Marshal determines that the applicant is qualified to service

portable fire extinguishers in accordance with the Fire Code; and

(

b) the applicant pays a fee of $96.50.

(3) A licence is valid until the expiry date shown on the licence, for a term of up to 3

years from the date it is issued, unless suspended or cancelled sooner.

(4) A license that has expired or is about to expire may be renewed upon payment of

the fee prescribed in clause (2)(b).

Suspension or revocation of licence

(1) The Fire Marshal may suspend or revoke a licence if the licensee

(

a) is no longer qualified to service portable fire extinguishers; or

(

b) is selling or servicing portable fire extinguishers that have not been

approved by the Fire Marshal.

(2) A person whose licence is suspended or revoked under subsection (1) may appeal

in writing to the Board within 15 days after notice of the suspension or revocation

is served on the person.

Insurance Industry Fire Reports

Preliminary insurance report

25 A preliminary insurance report required by subsection 36(1) of the Act must contain all

of the information identified in Form 1.

Final insurance report

26 A final insurance report required by subsection 36(4) of the Act must contain all of the

information identified in Form 2.

Part 3 - Fire Code

Adoption of Fire Code

27 The National Fire Code as modified in this

Part is adopted in accordance with subsection

15(2) of the Act as the Fire Code.

Interpretation

28 In this Part,

“net floor space” means the total free space in a room that is available for exiting

purposes, and is determined by subtracting the space occupied by furnishings,

building features and equipment from the total available floor area;

“retrofit” means the renovation of an occupied building to install additional fire

safety features required by a fire safety official to provide a minimum level of fire

safety, but does not include renovations carried out by the owner that must meet

the intent of the Building Code; and

“fire separation continuity” means

(

i) the fire separation does not have unprotected openings,

(ii) the fire separation has no damage that would reduce its effectiveness,

whether it has a fire-resistance rating or not, and

(iii) the fire separation provides a tight fit to adjoining building elements

that enables it to maintain the fire resistance-rating, where required,

and smoke control.

Modifications to National Fire Code

Defined terms

28A

(1) Sentence 1.4.1.2.(1) (Part 1 of Division

A) of the National Fire Code is modified

by repealing all of the following defined terms:

“Agricultural occupancy (Group G)”

“Agricultural occupancy with no human occupants”

“Farm building”

“Greenhouse agricultural occupancy”

“High-hazard agricultural occupancy”

(2) The definition of “Major occupancy” in Sentence 1.4.1.2.(1) (Part 1 of Division

A) of the National Fire Code is modified by striking out “G1–High-hazard agricultural

occupancies, G2–Agricultural occupancies not elsewhere classified in Group G,

G3–Greenhouse agricultural occupancies, G4–Agricultural occupancies with no

human occupants”.

Applicable editions

28B

Article 1.3.1.2. (Part 1 of Division

B) of the National Fire Code, except Table 1.3.1.2., is

replaced by the following article:

1.3.1.2. Applicable Editions

1) Except as provided under Sentence (2), where documents are referenced in this

Code, they shall be the editions designated in Table 1.3.1.2. except those

documents identified in

Section 66 of the Nova Scotia Building Code Regulations

in the replacement Sentence 1.3.1.2.(1) (Part 1 of Division

B) of the National

Building Code as designated under

an Act or regulation of the Province of Nova

Scotia as listed, in which case the edition so referenced shall apply.

2) Where amendments to documents adopted by this Code apply, these amendments

shall apply to the particular provisions of those documents adopted by the above

Acts and regulations unless amended by the Nova Scotia Fire Safety Regulations .

Sentences 2.1.2.2.(3) and 2.1.2.2.(4) repealed

28C Sentences 2.1.2.2.(3) and 2.1.2.2.(4) (Part 2 of Division

B) of the National Fire Code are

repealed.

Decorative materials

Article 2.3.1.3. of the National Fire Code is modified by adding the following Sentences

immediately after Sentence (1):

2) Subject to

Article 2.3.2.3., in care, treatment or detention occupancies (Group

B) and in access to exits for assembly occupancies (Group A), combustible materials

used for festive decorations, including crepe paper decorations, other combustible

trimming or ornaments shall

a) be flame resistant, or

b) conform to CAN/ULC-S109-14 “Flame Test of Flame Resistant Fabrics

and Films”.

3) Combustible materials, such as student artwork and teaching aids attached to walls

or ceilings of a school classroom or access to exits shall not be greater than 20% of

the wall or ceiling surface unless

a) the combustible materials have been tested in accordance with CAN/ULC-S102-10 “Standard Method of Tests for Surface Burning Characteristics of

Building Materials and Assemblies”, and

b) the flame spread rating does not exceed the rating that is required for the

interior finish of the space in which they are located.

Occupant load

Article 2.7.1.3. of the National Fire Code is replaced by the following Article:

2.7.1.3. Occupant Load

1) The maximum permissible occupant load for any room shall be calculated on the

basis of the least of

a) 0.4 m 2 of net floor space per occupant,

b) the occupant load for which means of egress are provided, and

c) in a room used for dining, serving alcoholic beverages or as a cafeteria, 1.2

m 2 of gross floor space per occupant.

(See Note A-2.7.1.3.(1), NFC)

2) The number of occupants permitted to enter a room shall not exceed the maximum

occupant load calculated in conformance with Sentence (1).

Posting of fire emergency procedures

30A

Article 2.8.2.14. (Part 2 of Division

B) of the National Fire Code is modified by adding

the following sentence immediately after Sentence 2.8.2.14.(4):

5) The floor plan diagram required in Sentence 3.8.2.10.(5) of

Schedule “C” to the

Nova Scotia Building Code Regulations shall be maintained in conformance with

the requirements of Sentence 3.8.3.9.(4) of

Schedule “C” to the Nova Scotia

Building Code Regulations if that was required at the time of construction.

Boarding and lodging houses

30B

Article 2.11.1.1. (Part 2 of Division

B) of the National Fire Code is replaced by the

following article:

2.11.1.1. Boarding and Lodging Houses, Construction

1) Buildings altered or occupied for purposes of providing accommodation for

boarders, lodgers or roomers shall conform to either

a) the NBC, or

Part 8 of the Fire Safety Regulations .

Farm buildings

30C

Section 2.14. (Part 2 of Division

B) of the National Fire Code is replaced with the word

“RESERVED”.

Additional functional statements and objectives for Table 2.15.1.1.

30D

Article 2.15.1.1. (Part 2 of Division

B) of the National Fire Code is modified by adding

the following rows containing functional statements and objectives to Table 2.15.1.1.

immediately after the rows containing functional statements and objectives for

Article

2.14.3.1.:

2.16.1.1. Appointment

(1) [F12-OP1.2]

[F12-OS1.2, OS1.5]

2.16.1.2. Inspection

(1) [F82-OS1.2, OS1.5]

(2) [F12-OP1.2]

[F12-OS1.5, OS1.2]

Appointment of chief fire warden

31 The National Fire Code is further modified by adding the following

Section immediately

after

Article 2.15.1.1.:

Section 2.16 Chief Fire Wardens

2.16.1. Chief Fire Wardens

2.16.1.1. Appointment

1) Every owner of a building shall appoint a chief fire warden if the building contains

a) an assembly occupancy (Group

A) with an occupant load greater than 200

persons, except for an assembly occupancy in a school, college or

university,

b) a detention occupancy (Group B, Division 1) facility with more than 50

occupants,

c) a care or treatment occupancy (Group B, Division 2 or 3) facility with more

than 10 occupants, or

d) a residential occupancy facility with more than 4 occupants that is licensed

or regulated under the Homes For Special Care Act .

2.16.1.2. Inspection

1) A chief fire warden appointed under Sentence 2.16.1.1.(1) shall, at least every 6

months,

a) inspect the building and any related buildings containing the occupancies

described in

Article 2.16.1.1. for fire hazards, and

b) provide a written report to the owner indicating

i) the condition of the means of egress,

ii) the condition of the fire protection system, and

iii) any other conditions respecting fire safety in the building or related

buildings.

2) The owner shall keep a copy of the report referred to in Clause (1)(

b) for 7 years

and shall make the report available to a fire official upon request.

Clause 4.1.1.1.(3)(

c) modified

31A Clause 4.1.1.1.(3)(c) (Part 4 of Division

B) of the National Fire Code is modified by

striking out “except as provided in Sentence (4),”.

Sentence 4.1.1.1.(4) repealed

31B Sentence 4.1.1.1.(4) (Part 4 of Division

B) of the National Fire Code is repealed.

Section 4.12. repealed

31C

Section 4.12. (Part 4 of Division

B) of the National Fire Code is replaced with the word

“RESERVED”.

Handling and discharge of fireworks

Article 5.1.1.3. of the National Fire Code is replaced by the following Article:

5.1.1.3. Handling and Discharge of Fireworks and Pyrotechnics

1) The handling and discharge of fireworks and pyrotechnics shall conform to the

“Display Fireworks Manual, 2010” and the “Special Effects Pyrotechnics Manual,

edition 3, 2014”, as published by the Explosives Regulatory Division, Natural

Resources Canada.

Repairs to fire protection system

Article 6.1.1.4. of the National Fire Code is replaced by the following Article:

6.1.1.4. Repairs

1) Except as provided in Sentence (2), where a fire protection system or any part of it

is shut down for repairs or is inoperative for more than 2 hours, the owner of the

building containing the fire system shall

a) notify the fire department, and

b) provide a sufficient number of trained people to patrol the building until the

fire protection system is restored to operating condition.

2) Sentence (1) does not apply to industrial or manufacturing facilities that maintain

their own industrial fire brigades.

3) Every owner of a building shall develop procedures to notify occupants of the

building if a fire or other emergency occurs when the fire alarm and detection

system are shut down or inoperative.

4) Every owner of a building shall develop procedures to provide protection to the

building if a sprinkler system or part of that system is shut down for more than 6

hours.

Lightning protection systems

Part 6 of Division B of the National Fire Code is amended by adding the following

Section immediately after

Section 6.8:

Section 6.8A. Lightning Protection Systems

6.8A.1. Lightning Protection Systems

6.8A.1.1. Inspection

1) The owner of a building with an installed lightning protection system shall have

the system inspected by a qualified person for signs of deterioration and

mechanical damage every 5 years and after changes have been made to the

structure or roof.

2) The owner of a building described in Sentence 6.8A.1.1.(1) shall keep inspection

records for at least 7 years from the inspection date and provide those records if

requested by the authority having jurisdiction.

Additional functional statements and objectives for Table 6.9.1.1.

34A

Article 6.9.1.1 of the National Fire Code is modified by adding the following rows

containing functional statements and objectives to Table 6.9.1.1. immediately after the

rows containing functional statements and objectives for Sentence 6.1.1.4.(1):

(2) [F02-OP1.2]

[F02-OP3.1]

[F02-OS1.2, OS1.5]

(3) [F02-OP1.2]

[F02-OP3.1]

[F02-OS1.2, OS1.5]

(4) [F02-OP1.2]

[F02-OP3.1]

[F02-OS1.2, OS1.5]

Retrofits of boarding, lodging and rooming houses

35 The National Fire Code is further modified by adding the following

Part immediately

after

Part 7:

Part 8

Retrofits of Boarding, Lodging and Rooming Houses

Section 8.1 General

8.1.1. General

8.1.1.1. Application

1) This Part applies to retrofits of boarding houses, lodging houses, rooming houses

and private rest homes in which residents do not require care or treatment because

of age or physical limitations, where

a) the building height does not exceed 3 storeys and the building area does not

exceed 600 m 2 ,

b) lodging is provided for more than 3 persons and is provided in return for

remuneration or the provision of services or both,

c) lodging rooms do not have both bathroom and kitchen facilities for the

exclusive use of individual occupants, and

d) the fire official is satisfied that, before April 1, 2025, the building was

occupied for the purpose of providing accommodations for boarders,

lodgers or roomers.

2) All fire separations accepted under this Part must maintain fire separation

continuity.

3) This Part does not apply to residential occupancies that are regulated by or under

the Homes For Special Care Act .

8.1.1.2. Containment

1) Fire separations required by this Part to have a fire-resistance rating shall comply

with Subsection 9.10.3. of the Building Code.

8.1.1.3. Floor Assemblies

1) Except as provided in Sentence (2),

a) floor assemblies shall be constructed as fire separations, and

b) floor assemblies and walls, columns and arches supporting floor assemblies

shall have a fire-resistance rating of not less than 30 minutes.

2) Existing floor assemblies with ceilings consisting of lath and plaster, gypsum board

or noncombustible materials shall be deemed to be in compliance with Sentence

(1).

8.1.1.4. Basement Fire Separations

1) Where a basement does not contain a bedroom, recreation room, meeting room or

hobby room, a fire separation having no fire-resistance rating between the

basement and first storey shall be deemed to be in compliance with Clause

8.1.1.3.(1)(b).

8.1.1.5. Sleeping Areas and Bedroom Fire Separations

1) Except as provided in Sentence (2), each sleeping area, bedroom or suite of rooms

shall have interior walls constructed as fire separations having a fire-resistance

rating of not less than 30 minutes.

2) Existing wall assemblies in sleeping areas, bedrooms or suites of rooms consisting

of membranes of lath and plaster or gypsum wallboard shall be deemed to be in

compliance with Sentence (1).

3) Except as provided in Sentence (4), a closure between sleeping area or bedrooms

and the corridor providing access to exit shall have a fire-protection rating of not

less than 20 minutes.

4) A solid core wood door that is 45 mm thick together with a solid door frame that is

42 mm thick with no approved listed fire-protection rating shall be deemed to be in

compliance with Sentence (3).

5) A door referred to in Sentences (3) and (4) shall be equipped with approved self-closing devices and positive latching devices.

8.1.1.6. Furnace Room Fire Separations

1) Except as provided in Sentence (2), in a building where the building height is

greater than 2 storeys or the building area is greater than 400 m 2 , a furnace room

that is located on a floor area that contains a bedroom, recreation room, meeting

room or hobby room shall be separated from the remainder of the building by a fire

separation having a fire-resistance rating of not less than 45 minutes.

2) Existing fire separations in a furnace room as described in Sentence (1) consisting

of lath and plaster or gypsum board shall be deemed to be in compliance with

Sentence (1).

3) Where the vertical fire separation in a furnace room complies with Sentence

(1) and it is not practical in the circumstances to construct the ceiling as a fire

separation having the fire-resistance rating required by Sentence (1), the furnace

room shall be sprinklered with a spacing that does not exceed 9.5 m 2 per sprinkler

head.

4) Except as provided in Sentence (5), a door or other opening in a fire separation for

a furnace room shall be protected with a closure having a fire-protection rating of

not less than 20 minutes.

5) A solid core wood door that is 45 mm thick together with a solid door frame that is

42 mm thick with no approved listed fire-protection rating shall be deemed to be in

compliance with Sentence (4).

6) Closures referred to in Sentences (4) and (5) shall be equipped with approved self-closing devices and positive latching devices.

7) Despite Sentence (1) fire dampers or fire stop flaps are not required in ducts at

penetrations of fire separations required to have a fire-resistance rating.

8.1.1.7. Combustion Air

1) Where a furnace room is separated to comply with the requirements of

Article

8.1.1.6., sufficient combustion air shall be brought directly from the exterior of the

building for the safe operation of the appliance.

8.1.1.8. Means of Egress

1) Except as otherwise provided in this Article, each floor area shall be served by at

least 2 exits.

2) A building with sleeping accommodations for 10 persons or less shall be deemed

to be in compliance with Sentence (1) if it has one exit from each of the first and

second floor areas.

3) A building with no sleeping areas or bedrooms in the basement or cellar shall be

deemed to be in compliance with Sentence (1) if it has one exit from the basement

or cellar.

4) A sleeping area or bedroom with a window that conforms to Subsection 9.9.10. of

the Building Code may serve as the second means of egress required by Sentence

(1) from a basement or cellar.

5) Except where the building is sprinklered, each bedroom, sleeping area or

combination bedroom shall have at least one outside window or exterior door

openable from the inside without the use of keys, tools or special knowledge and

without requiring the removal of sashes or hardware in conformance with the

bedroom window egress requirements in the Building Code.

8.1.1.8A. Handrails and Guards

1) Handrails and guards shall be installed on stairs and ramps in accordance with the

Building Code.

8.1.1.9. Acceptable Exits

1) Exits required by Sentences 8.1.1.8.(1), (2) and (3) shall comply with Articles

9.9.2.1. and 9.9.2.2 of the Building Code.

2) Despite the requirement in Sentence 8.1.1.12.(1) for fire separations for exits, one

of the exits required by

Article 8.1.1.8. from a basement or cellar may lead through

the first floor area.

3) In a building with sleeping accommodations for 10 persons or fewer, corridors that

are connected to an interior stairway may form part of the stairway enclosure, and

fire separations between floors shall be maintained with a minimum 30-minute

fire-resistance rating in conformance with

Article 8.1.1.3. and openings in fire

separations protected in conformance with Sentence 8.1.1.14.(1).

4) Only one interior stairway enclosure described in Sentence (3) shall be permitted

as an exit.

8.1.1.10. Approval of Fire Official

1) Despite Articles 8.1.1.8. and 8.1.1.9. alternative means of egress may be approved

where, in the opinion of a fire official, they will provide protection for fire safety

and life safety similar to the protection provided by compliance with Articles

8.1.1.8. and 8.1.1.9.

8.1.1.11. Fire Escapes

1) Except as provided in Sentence (2), each fire escape used as an exit shall be

constructed in compliance with Subsection 3.4.7. of the Building Code.

2) An existing fire escape may be approved by a fire official if the fire official is

satisfied that it provides protection for fire safety and life safety similar to the

protection provided by compliance with Sentence (1).

3) Access to a fire escape from a corridor shall be by means of an exterior exit door.

4) Where a fire escape is used as an exit, it shall be deemed to comply with the

requirements of

Article 9.9.2.1. of the Building Code.

8.1.1.12. Protection of Exits

1) Except as provided in Sentences (2) and (3), each exit, other than a doorway

opening directly onto a fire escape or to the outdoors at ground level, shall be

separated from each adjacent floor area or from another exit by a fire separation

having a fire-resistance rating of not less than 30 minutes.

2) An existing interior stairway exit, fire-separated from the remainder of the building

by walls consisting of lath and plaster or gypsum wallboard, shall be deemed to be

in compliance with Sentence (1).

3) An existing fire separation of noncombustible material may be approved by a fire

official if the fire official is satisfied that it provides protection for fire safety and

life safety similar to the protection provided by compliance with Sentence (2).

8.1.1.13. Interior Stairways

1) Floor fire separations shall be maintained at interior stairways that are not required

exits.

2) A floor fire separation shall be maintained at an exit permitted by Sentence

8.1.1.9.(2).

3) Floor fire separations required by Sentence (1) shall be rated in accordance with

Articles 8.1.1.3. and 8.1.1.12.

8.1.1.14. Protection of Openings in Fire Separations

1) Except as provided in Sentences (2) to (5), openings in fire separations required by

this Part shall be protected by closures in conformance with Subsection 9.10.13. of

the Building Code with a minimum 20-minute fire-protection rating.

2) Fire dampers or fire stop flaps are not required in ducts at penetrations of a fire

separation with a required fire-resistance rating.

3) A solid core wood door that is 45 mm thick shall be deemed to be in compliance

with Sentence (1).

4) Frames for doors described in Sentence (3) may be of wood or hollow metal

construction.

5) Existing wired glass closures shall be deemed to be in compliance with Sentence

(1).

8.1.1.15. Exit Signs

1) In buildings that are more than 2 storeys in building height or that have sleeping

accommodations for more than 10 persons, exit signs shall be installed in

accordance with Subsection 9.9.11. of the Building Code.

8.1.1.16. Interior Finishes

1) The flame-spread rating of interior finishes on walls and ceilings within a means of

egress shall not exceed 200.

8.1.1.17. Illumination of Egress

1) Corridors and stairways shall be lighted to the intensity of 50 lx measured at the

floor level, or 5 W/m 2 of floor area.

8.1.1.18. Emergency Lighting

1) In a building with sleeping accommodations for more than 10 persons, or where a

fire alarm is required by this Part, emergency lighting shall be provided to

corridors, exits and stairways in accordance to

Article 9.9.12.3. of the Building

Code.

8.1.1.19. Fire and Smoke Alarm Requirements

1) A fire alarm system complying with Subsection 9.10.18. of the Building Code

shall be installed in a building if it does not have both

a) floor assemblies having a minimum 45-minute fire-resistance rating, and

b) public corridors or corridors serving sleeping rooms that are separated from

the remainder of the building by a fire separation with a minimum

30-minute fire-resistance rating.

2) A fire alarm system complying with Subsection 9.10.18. of the Building Code

shall be installed in a building that has sleeping accommodations for more than 10

persons.

3) Where a fire alarm system is required in a building with sleeping accommodations

for less than 14 persons, an existing interconnected smoke alarm system installed

in accordance to Subsection 9.10.19. of the Building Code shall be deemed to be in

compliance with Sentence (1).

4) Despite Sentences (2) and (3), existing fire alarm systems may be approved where

system reliability and performance will not increase the risk to life or safety.

5) Where a fire alarm is not required by this Part, smoke alarms shall be installed in

conformance with Subsection 9.10.19. and installed so there is at least one in all of

the following locations

a) on each storey, including basements,

b) in each sleeping room,

c) in each ancillary space s and common space s , and

d) in a location between the sleeping rooms or suite and the remainder of the

storey, and if the sleeping rooms are served by a corridor, the smoke alarm

shall be located in the corridor.

6) Except as permitted by Sentence (9), smoke alarms shall be interconnected so that

the activation of any one alarm causes all alarms within the building to sound.

7) Smoke alarms may be wirelessly interconnected or interconnected by hard-wiring

in conformance with

Article 9.10.19.4. (Part 9 of Division

B) of the Building Code

as modified by

Section 84 of the Nova Scotia Building Code Regulations .

8) Smoke alarms shall be installed in conformance with CAN/ULC S553, “Standard

for the Installation of Smoke Alarms”.

9) Smoke alarms installed in sleeping rooms may be battery-operated and are

permitted to sound localized alarms within individual suites, and need not sound

an alarm throughout the rest of the building.

8.1.1.19A. Emergency Planning

1) In every bedroom and sleeping area, the fire safety rules for occupants shall be

posted showing the locations of exits and the paths of travel to exits.

2) Fire emergency procedures shall be provided in accordance with

Section 2.8. of the

National Fire Code where a fire alarm is required by this Part.

8.1.1.20. Fire Suppression

1) At least one 2A rated portable fire extinguisher shall be provided in an easily

accessible and visible location on each floor.

2) At least one 2A10BC rated portable fire extinguisher shall be installed in each

kitchen that has shared cooking facilities.

Section 8.2. Objectives and Functional Statements

8.2.1. Objectives and Functional Statements

8.2.1.1. Attribution to Acceptable Solutions

1) For the purposes of compliance with this Code as required in Clause 1.2.1.1.(1)(

b) of Division A, the objectives and functional statements attributed to the acceptable

solutions in this Part shall be the objectives and functional statements listed in

Table 8.2.1.1. (See Note A-1.1.2.1.(1).)

Table 8.2.1.1.

Objectives and Functional Statements Attributed to the

Acceptable Solutions in

Part 8

Forming Part of Sentence 8.2.1.1.

(1) Functional Statements and Objectives

8.1.1.1. Application

(2) [F03-OS1.2]

[F03-OP1.2]

8.1.1.3. Floor Assemblies

(1) [F03-OS1.2]

[F03-OP1.2]

(2) [F03-OS1.2]

[F03-OP1.2]

8.1.1.4. Basement Fire Separations

(1) [F03-OS1.2]

[F03-OP1.2]

8.1.1.5. Wall Separating Bedrooms

(1) [F03-OS1.2]

[F03-OP1.2]

8.1.1.6. Furnace Room Fire Separations

(1) [F03-OS1.2]

[F03-OP1.2]

(2) [F03-OS1.2]

[F03-OP1.2]

(3) [F03-OS1.2]

[F03-OP1.2]

(4) [F03-OS1.2]

[F03-OP1.2]

(5) [F03-OS1.2]

[F03-OP1.2]

(6) [F03-OS1.2]

[F03-OP1.2]

8.1.1.7. Combustion Air

(1) [F01, F81, F82 - OP1.2, OP1.1]

[F81, F82 - OS3.4]

[F01, F81, F82 - OS1.1, OS1.2]

8.1.1.8. Means of Egress

(1) [F10 - OS3.7]

(2) [F10 - OS3.7]

(3) [F10 - OS3.7]

(4) [F10 - OS3.7]

8.1.1.9. Acceptable Exits

(1) [F10 - OS3.7]

(2) [F10 - OS3.7]

(3) [F10 - OS3.7]

(4) [F10 - OS3.7]

8.1.1.10. Approval of Fire Official

(1) [F10 - OS3.7]

8.1.1.11. Fire Escapes

(1) [F05-OS1.5]

[F06-OS1.2]

[F10, F12 - OS3.7]

[F20 - OS3.1]

[F20 - OS2.1]

[F30 - OS3.1]

(2) [F05 - OS1.5]

[F06 - OS1.2]

[F10, F12 - OS3.7]

[F20 - OS3.1]

[F20 - OS2.1]

[F30 - OS3.1]

(3) [F30 - OS3.1]

[F10 - OS3.7]

(4) [F05-OS1.5]

[F06-OS1.2]

[F10, F12 - OS3.7]

[F20 - OS3.1]

[F20 - OS2.1]

[F20 - OS3.1]

8.1.1.12 Protection of Exits

(1) [F05 - OS1.5]

[F03 - OS1.2]

[F03 - OP1.2]

(2) [F05 - OS1.5]

[F03 - OS1.2]

[F03 - OP1.2]

(3) [F05 - OS1.5]

[F03 - OS1.2]

[F03 - OP1.2]

8.1.1.13. Interior Stairways

(1) [F04 - OS1.2]

[F03 - OP1.2, OP1.3]

(2) [F10 - OS3.7]

(3) [F05 - OS1.5]

[F03 - OS1.2]

[F03 - OP1.2]

8.1.1.14. Protection of Openings in Fire Separations

(1) [F03 - OS1.2]

[F03 - OP1.2]

(2) [F03 - OS1.2]

[F03 - OP1.2]

(3) [F03 - OS1.2]

[F03 - OP1.2]

(4) [F03 - OS1.2]

[F03 - OP1.2]

(5) [F03 - OS1.2]

[F03 - OP1.2]

8.1.1.15. Exit Signs

(1) [F10, F81 - OS3.7]

8.1.1.16. Interior Finishes

(1) [F02 - OS1.2]

8.1.1.17. Illumination of Egress

(1) [F30 - OS3.1]

[F30 - OS3.7]

8.1.1.18. Emergency Lighting

(1) [F30 - OS3.1]

[F10 - OS3.7]

8.1.1.19 Fire Alarm Requirement

(1) [F-11 - OS1.5]

[F13 - OS1.2, OS1.5]

[F03 - OS1.2]

(2) [F11 - OS1.5]

[F13 - OS2.1, OS1.5]

[F03 - OS1.2]

(3) [F81, F11 - OS1.5]

(4) [F11 - OS1.5]

[F13 - OS1.2, OS1.5]

[F03 - OS1.2]

(5) [F81, F11 - OS1.5]

(6) [F81, F11 - OS1.5]

8.1.1.20. Fire Suppression

(1) [F81, F02, F12 - OS1.2]

[F81, F02, F12 - OP1.2]

(2) [F81, F02, F12 - OS1.2]

[F81, F02, F12 - OP1.2]

________________________________________________________________

Form 1—Preliminary Insurance Report Form

(subsection 36(1) of the Fire Safety Act )

Office of the Fire Marshal

Please complete this Preliminary Insurance Report Form as completely and accurately as possible.

This form may be filled in electronically using QuattroPro. The information obtained is used by

the Office of the Fire Marshal in its reporting process and for the development of training and

education programs. The data is also submitted for use in the Canadian Fire Statistics Database.

Also, please note the time fields are in 24hr format. i.e. 1:00 p.m. = 13:00

Section A: Fire Information

____________________________________________________________________________

Date of fire (mm/dd/yyyy) Time of fire (hr:min)

____________________________________________________________________________

Civic # Street name Unit/Suite/Apt #

City/Town/County Province Country

___________________

Postal code

Owner Information

Name Company

Civic # Street name Unit/Suite/Apt #

City/Town/County Province Country

Postal code Phone #

Insured: □ Yes □ No

Property classification

Occupant Information - For Real and Personal Property

Name Phone #

Insured: □ Yes □ No

Section B: Mobile Property (where fire starts on or within)

Please note “mobile property” is considered to be any vehicle, trailer, boat, farm equipment, etc.

Make Year Model Serial # Licence#

Make Year Model Serial # Licence#

Equipment, boat, etc. Brief description

Section C: Origin

Information not required until Final Report, Form 2, filed.

Section D: Fire Loss Details

The information related to the reserve will not be used in any way other than general statistics.

All specific information provided will be held in accordance with the Freedom of Information

and Protection of Privacy Act .

Insurance company/Broker: Insurance phone #

Adjuster’s name Adjusting company Adjuster’s phone #

Policy # Claim #

Reserve for estimated loss:

□ Under $50,000 □ $50,000-$500,000 □ Over $500,000

Casualty Information (Voluntary)

Male:

Female:

Firefighter:

Adult

Child

Adult

Child

Male

Female

Injuries

Fatalities

Hospital required: □ Yes □ No

Injury details

Section E: Additional Information

Responding fire department Report date (mm/dd/yyyy)

Additional comments (voluntary)

Signature Contact phone #

________________________________________________________________

Form 2—Final Insurance Report Form

(subsection 36(4) of the Fire Safety Act )

Office of the Fire Marshal

Please complete this Insurance Final Form as completely and accurately as possible. This form

may be filled in electronically using QuattroPro. The information obtained is used by the Office

of the Fire Marshal in its reporting process and for the development of training and education

programs. The data is also submitted for use in the Canadian Fire Statistics Database.

Also, please note the time fields are in 24hr format. i.e. 1:00 p.m. = 13:00

Section A: Fire Information

Date of fire (mm/dd/yyyy) Time of fire (hr:min)

Civic # Street name Unit/Suite/Apt #

City/Town/County Province Country

___________________

Postal code

Owner Information

Name Company

Civic # Street name Unit/Suite/Apt #

City/Town/County Province Country

Postal code Phone #

Insured: □ Yes □ No

Occupant Information - For Real and Personal Property

Name Phone #

Insured: □ Yes □ No

Section B: Mobile Property (where fire starts on or within)

Please note “mobile property” is considered to be any vehicle, trailer, boat, farm equipment, etc.

Make Year Model Serial # Licence#

Make Year Model Serial # Licence#

Equipment, boat, etc. Brief description

Section C: Origin

Property classification

Fire origin

Igniting object

Material first ignited

Fuel or energy

Possible cause (upon closing the file)

Equipment Involved - Where Equipment Has Been the Cause of the Fire:

Make Year Model Serial #

Make Year Model Serial #

Section D: Fire Loss Details

The information related to the building value, building loss and uninsured loss are estimates

only and will not be used in any way other than general statistics. All specific information

provided will be held in accordance with the Freedom of Information and Protection of Privacy

Act .

Insurance company/Broker: Insurance phone #

Adjuster’s name Adjusting company Adjuster’s phone #

Policy # Claim #

Building value Insured loss paid (building) Uninsured loss (building)

Contents value Insured loss paid (contents) Uninsured loss (contents)

Total value Total loss Total uninsured loss

Casualty Information (Voluntary)

Male:

Female:

Firefighter:

Adult

Child

Adult

Child

Male

Female

Injuries

Fatalities

Hospital required: □ Yes □ No

Injury details

Section E: Additional Information

Responding fire department Report date (mm/dd/yyyy)

Additional comments:

Signature Contact phone #

Legislative History

Reference Tables

Fire Safety Regulations

N.S. Reg.

48/2003

Fire Safety Act

Note: The information

in these tables does not form part of the regulations and is compiled by the

Office of the Registrar of Regulations for reference only.

Source Law

The current consolidation of the Fire Safety Regulations made under the Fire Safety Act includes all of the following regulations:

N.S.

Regulation

In force

date*

How in force

Royal Gazette

Part II Issue

48/2003

Feb 28, 2003

date specified

Mar 21, 2003

33/2004

Mar 18, 2004

date specified

Apr 2, 2004

67/2004

May 1, 2004

date specified

Apr 6, 2004

194/2006

Oct 31, 2006

date specified

Nov 10, 2006

103/2007

Apr 1, 2007

date specified

Mar 30, 2007

161/2008

Apr 1, 2008

date specified

Apr 18, 2008

103/2009

Apr 1, 2009

date specified

Apr 14, 2009

76/2011

Apr 1, 2011

date specified

Apr 15, 2011

215/2011

Jun 21, 2011

date specified

Jul 1, 2011

102/2013

Apr 1, 2013

date specified

Apr 12, 2013

101/2015

Apr 1, 2015

date specified

Apr 8, 2015

68/2017

May 1, 2017

date specified

Apr 28, 2017

3/2020

Jan 14, 2020

date specified

Jan 31, 2020

60/2025

Apr 1, 2025

date specified

Apr 4, 2025

The following regulations are not yet in force and are

not included in the current consolidation:

N.S.

Regulation

In force

date*

How in force

Royal Gazette

Part II Issue

*See subsection 3(6) of the Regulations Act for

rules about in force dates of regulations.

Amendments by Provision

ad. = added

am. = amended

fc. = fee change

ra. = reassigned

rep. = repealed

rs . = repealed and substituted

Provision affected

How affected

2(1) ...................................................

am. 3/2020 (clause lettering removed)

2(1), defn . of “Committee” ..............

am. 194/2006

2(1), defn . of “municipal

unit” .........

rep. 194/2006

2(1), defn . of “National Fire

Code” .

ra. from 2(1)(f) 194/2006 ; am. 215/2011, 68/2017,

3/2020, 60/2025

2(1)(

f) defn . of “National

Fire Code”

ra. as 2(1)(e) 194/2006

3 ........................................................

rs . 194/2006

3(1)(c) ..........................................

am. 60/2025

3(1)(j) ..........................................

am. 3/2020

3(1)(l) ..........................................

am. 215/2011, 68/2017

4 ........................................................

rs . 194/2006

5 ........................................................

rs . 194/2006

5(1)(b) .........................................

am. 68/2017, 60/2025

6 ........................................................

rs . 194/2006

7 ........................................................

rep. 33/2004

8 to 11 ...............................................

rep. 194/2006

12(1) .................................................

am. 60/2025

12(1)(a)(i) ....................................

am.

60/2025

12(1)(b) .......................................

am. 3/2020

12(1)(e) ........................................

am. 60/2025

12(2) .................................................

fc. 67/2004, 103/2007, 161/2008, 103/2009, 76/2011,

102/2013, 101/2015; rs . 60/2025

13 ......................................................

rep. 60/2025

14(1) .................................................

am.

60/2025

14( 2)( aa) ...........................................

ad. 60/2025

15 ......................................................

fc. 67/2004, 103/2007, 161/2008, 103/2009, 76/2011,

102/2013, 101/2015; am. 60/2025

15A ...................................................

ad.194/2006 ; am. 60/2025

16 ......................................................

am. 3/2020 (clause lettering removed)

17(3) .................................................

am.

60/2025

17(4) .................................................

ad. 60/2025

18(2) .................................................

am.

60/2025

19 ......................................................

am. 3/2020 (clause lettering removed)

19, defn . of “licence” ..................

am. 3/2020

23(2)(b) .............................................

fc. 67/2004, 103/2007, 161/2008, 103/2009, 76/2011,

102/2013, 101/2015

23(3) .................................................

rs . 194/2006

25 ......................................................

am. 3/2020

26 ......................................................

am. 3/2020

28 ......................................................

am. 3/2020 (clause lettering removed)

28A-28C ...........................................

ad. 60/2025

29, sentence 2.3.1.3 2) ......................

am. 215/2011, 3/2020

29, clause 2.3.1.3 2) b) .....................

am. 68/2017, 3/2020

29, clause 2.3.1.3 3) a) .....................

am. 194/2006, 68/2017

30 ......................................................

rs . 60/2025

30, sentences 2.7.1.3. 2)-4) .........

am. 68/2017

30A ...................................................

ad. 68/2017 ; rs . 60/2025

30B-30D ...........................................

ad. 60/2025

31 ......................................................

am. 194/2006, am. 60/2025

31,

Section 2.15 ...........................

ra. as 2.16 60/2025

31, subsection 2.15.1. ..................

ra. as 2.16.1. 60/2025

31,

article 2.15.1.1. ......................

ra. as 2.16.1.1. 60/2025

31, clause 2.15.1.1 1) b) ..............

am. 3/2020

31, clause 2.15.1.1 1) c) ..............

am. 3/2020

31,

article 2.15.1.2. ......................

ra. as 2.16.1.2. 60/2025

31,

Section 2.16 ...........................

ra. from 2.15 60/2025

31, subsection 2.16.1. ..................

ra. from 2.15.1. 60/2025

31,

article 2.16.1.1. ......................

ra. from 2.15.1.1. 60/2025

31,

article 2.16.1.2. ......................

ra. from 2.15.1.2. 60/2025

31, sentence 2.16.1.2(1) ..............

am.

60/2025

31, clause 2.16.1.2(1)(a) .............

am.

60/2025

31A-31C ...........................................

ad. 60/2025

32 ......................................................

rs . 194/2006

32,

sentence 5.1.1.3. 1) ...............

am. 3/2020

34 ......................................................

rs . 60/2025

34,

section 6.8A. .........................

ra. from 6.9. 68/2017

34, subsection 6.8A.1. .................

ra. from 6.9.1. 68/2017

34,

article 6.8A.1.1. .....................

ra. from 6.9.1.1. 68/2017

34, sentence 6.8A.1.1.1) ..............

am. 68/2017

34,

section 6.9. ............................

ra. as 6.8A. 68/2017

34, subsection 6.9.1. ....................

ra. as 6.8A.1. 68/2017

34,

article 6.9. 1.1.. .......................

ra. as 6.8A.1.1. 68/2017

34A ...................................................

ad. 68/2017 ; am. 60/2025

35, sentence 8.1.1.1.(1) ....................

am. 3/2020, 60/2025

35, clause 8.1.1.1.(1)(b)-(c) ........

am. 60/2025

35, clause 8.1.1.1.(1)(d) ..............

ad. 60/2025

35, clause 8.1.1.3.(1)(b) ....................

am. 60/2025

35,

article 8.1.1.5. .............................

am.

60/2025

35, sentence 8.1.1.5.(1)-(2) .........

am.

60/2025

35, sentence 8.1.1.5.(3)-(5) .........

ad. 60/2025

35, sentence 8.1.1.6.(4) ....................

rs . 60/2025

35, sentence 8.1.1.6.(5)-(7) ..............

am. 60/2025

35, sentence 8.1.1.8.(3) ....................

am.

60/2025

35, sentence 8.1.1.8.(4) ....................

am. 68/2017, 60/2025

35, sentence 8.1.1.8.(5) ....................

ad. 60/2025

35,

article 8.1.1.8A. ..........................

ad. 60/2025

35, sentence 8.1.1.9.(1) ....................

am. 68/2017, 60/2025

35, sentence 8.1.1.9.(3) ....................

rs . 60/2025

35, sentence 8.1.1.9.(4) ....................

am. 60/2025

35, sentence 8.1.1.11.(4) ..................

am. 68/2017

35, sentence 8.1.1.12.(1)-(3) ............

am. 60/2025

35,

article 8.1.1.13. ...........................

am. 60/2025

35, sentence 8.1.1.14.(1) ..................

rs . 60/2025

35, sentence 8.1.1.14.(2) ..................

am. 60/2025

35, sentence 8.1.1.15.(1) ..................

am. 215/2011

35, sentence 8.1.1.18.(1) ..................

am. 215/2011, 60/2025

35, sentence 8.1.1.18.(1) ..................

am. 215/2011

35,

article 8.1.1.19. ...........................

am. 60/2025

35, sentence 8.1.1.19.(1) .............

rs . 60/2025

35, sentence 8.1.1.19.(2) .............

am. 194/2006; rs . 60/2025

35, sentence 8.1.1.19.(3) .............

am. 194/2006

35, sentence 8.1.1.19.(5)-(6) .......

rs . 60/2025

35, sentence 8.1.1.19.(7)-(9) .......

ad. 60/2025

35,

article 8.1.1.19A. ........................

ad. 60/2025

35, sentence 8.1.1.20.(1)-(2) ............

am. 35/2004

35,

section 8.2. ..................................

ad. 68/2017

“ municipal unit” replaced throughout

with “municipality” ........................

am. 194/2006

Note that changes to headings are not

included in the above table.

Editorial Notes and Corrections

Note

Effective

date

The reference to Service Nova Scotia and Municipal

Relations in s. 5(1)(

b) should be read as a reference to the Department of

Municipal Affairs in accordance with O.I.C. 2014-71 under the Public Service Act , R.S.N.S. 1989, c.

(Corrected by N.S. Reg 68/2017)

Apr 1, 2014

The brackets surrounding the text in the right-hand

column of tables in s. 30A, 34A and 35 added by N.S. Reg 68/2017 are part of

the regulations and do not indicate editorial corrections made by the Office

of the Registrar of Regulations.

The reference to the Department of Municipal Affairs in

s. 5(1)(

b) should be read as a reference to the Department of Municipal

Affairs and Housing in accordance with O.I.C. 2019-50 under the Public Service Act , R.S.N.S. 1989, c.

Jun 3, 2019

The reference to the Department of Municipal Affairs in

s. 5(1)(

b) should be read as a reference to the Department of Municipal Affairs in accordance with O.I.C.

2021-58 under the Public Service Act ,

R.S.N.S. 1989, c. 376.

Feb 23, 2021

The reference to the Department of Municipal Affairs in

s. 5(1)(

b) should be read as a reference to the Department of Municipal Affairs and Housing in accordance with

O.I.C. 2021-209 under the Public

Service Act , R.S.N.S. 1989, c. 376.

Aug 31, 2021

The reference to the Department of Municipal Affairs in

s. 5(1)(

b) is to be read as a reference to the Department of Municipal

Affairs in accordance with O.I.C. 2024-425 under the Public Service Act , R.S.N.S. 1989, c. 376.

Dec 12, 2024

Repealed and Superseded

N.S.

Regulation

Title

In force

date

Repealed

date

160/1996

Automatic Sprinkler System Maintenance Regulations under the Fire Prevention Act

Oct 28, 1996

Feb 28, 2003

62/1972

Portable Fire Extinguished Control Regulations under the Fire Prevention Act

Oct 1, 1972

Feb 28, 2003

Note: Only

regulations that are specifically repealed and replaced appear in this

table. It may not reflect the entire

history of regulations on this subject matter.