British Columbia Gazette Part II — B.C. Reg. 103/2004

B.C. Reg. 103/2004

British Columbia — Gazette

British Columbia Gazette Part II — B.C. Reg. 103/2004

B.C. Reg. 103/2004

British Columbia — Gazette

Copyright © Queen's Printer,

Victoria, British Columbia, Canada

Licence

Disclaimer

Volume 47, No. 7

B.C. Reg. 103/2004

The British Columbia Gazette,

Part II

April 6, 2004

B.C. Reg. 103/2004, deposited March 23, 2004, pursuant

to the SAFETY STANDARDS ACT [Section 88]. Regulation of the Minister

of Community, Aboriginal and Women's Services M61/2004, dated March 22, 2004.

I, Murray Coell, Minister of Community, Aboriginal and Women's Services, order

that the attached Gas Safety Regulation is made, effective April 1, 2004.

— M. COELL, Minister of Community, Aboriginal and Women's Services.

GAS SAFETY REGULATION

Contents

Definitions for the Act

Definitions for this regulation

Application of this regulation

Part 1 — General Qualification Licensing Provisions

Division 1 — Individuals Who May Perform Regulated Work

Individuals who may perform regulated work

Division 2 — Certificates of Qualification

What all applicants for a certificate of qualification must do

Class A gas fitter certificate of qualification

Class B gas fitter certificate of qualification

Class A or B gas fitter may do limited electrical work

Duty of gas fitter to notify of need to repair

Gas fitter may make temporary repairs

Gas appliance service certificate of qualification

Gas piping certificate of qualification

Recreation vehicle installation and service certificate of qualification

Liquefied petroleum gas vehicle conversion certificate of qualification

Compressed natural gas vehicle conversion certificate of qualification

Compressed natural gas and liquefied petroleum gas vehicle conversion certificate of qualification

Gas venting certificate of qualification

Gas utility certificate of qualification

Special purpose gas certificate of qualification

Class A or class B certificates for individuals with qualifications from elsewhere in Canada

Division 3 — Contractor's Licence

Field safety representative not required for gas contractor's licence

Division 4 — Duties of Licensed Gas Contractor and Permit Holder

Duties of a licensed gas contractor and permit holder

Part 2 — Requirements for Permits

Permits that may be issued by a local government

Homeowner may perform work under a permit

Drawings to accompany installation permit application

Installation permit is also authorization

Field safety representative not required for installation permit

Requirements concerning operating permits

Duties of owners and licensed gas contractors in commercial and industrial buildings

Part 3 — Regulated Product Standards and Certification

Canadian gas standards adopted as B.C. Natural Gas and Propane Code

No installation of gas appliances unless certified or approved

Approved testing and certification agencies

Dealers to maintain records of gas appliances

Part 4 — Inspections

Duty to inform regulatory authority of completion of work for inspection

Part 5 — Safety Officers

Safety officer's certificate of qualification

Part 6 — Technical Requirements

Division 1 — Requirements and Procedures for Installation and Excavations

Connection for pressure gauge to be satisfactory

Procedures for a gas installation in vicinity of underground structures

Duties of persons intending to construct near gas installation

Procedures for excavations

No probing to locate gas installations

Requirements for blasting in vicinity of gas installation

Emergency excavation procedures

Procedure for backfilling an excavation when gas installation exposed

Procedure if gas escapes

Procedure if there is damage to gas installation

Procedure when gas installation exposed

Procedure if gas fittings exposed

Procedures in respect of cathodic protection devices

Procedure if damage to protective wrapping occurs

Test charts or reports to be provided on request

Provincial safety manager may require pressure tests

Duty of gas company to file construction standards with provincial safety manager

Division 2 — Installation and Repair Procedures for Appliances and Gas Systems

Turning gas supply on and off

Unrepairable appliance

Duties of owner of rental premises concerning gas appliances

Gas fitter's tag to be affixed on completion of work

Adjustments on connection to gas line

Testing after disconnection

Notice to gas company if input greater than 45 kW

Odorization

Part 7 — Information Requests for Existing Gas System

Information requests for an existing gas system

Schedule

Definitions for the Act

1 For the purposes of the Act:

"gas equipment" means anything used or designed to be used in connection with gas and includes any of the following:

(

a) piping;

(

b) appliances;

(

c) fuel containers;

(

d) vents;

"gas system" means a system of gas equipment that

(

a) is installed in premises and is downstream of an outlet of a service meter,

(

b) uses liquefied petroleum gas and is downstream of a second stage regulator,

(

c) is installed other than by or on behalf of a gas company and is upstream of the outlet of a meter or upstream of a second stage regulator,

(

d) is installed at a propane bulk plant,

(

e) is a vehicle fuel system or a vehicle gas system, or

(

f) is used for the production, handling and utilization of digester gas in a wastewater treatment plant or landfill gas at a landfill site.

Definitions for this regulation

2 In this regulation:

"Act" means the Safety Standards Act ;

"appliance" means a regulated product that converts

gas into energy and includes any valves, controls, fittings and components attached

to or connected to it or intended to be attached to or connected to it;

"B.C. Natural Gas and Propane Code" means the code

adopted under

section 30 (2);

"city gate" means the plant or premises where gas received from a pipeline is metered, reduced in pressure and prepared for distribution to individual users of the gas;

"conversion burner" means a burner designed to supply gaseous fuel to an appliance originally designed to use another fuel;

"digester gas" means a gas produced from the biological treatment of sewage and which is composed of methane, carbon dioxide and hydrogen sulphide or any combination of them;

"distribution main" means a pipe used for the transmission

and distribution of gas at a pressure of 700 kPa gauge or less for any

distance between a city gate and a service pipe;

"fan assisted appliance" means a Category 1 appliance

as defined in CSA B149.1;

"fully detached dwelling" means any detached building containing only one dwelling unit if occupied or intended by the owner to be occupied as a permanent residence;

"gas" means any of the following:

(

a) natural gas, manufactured gas, liquefied petroleum

gas, digester gas, landfill gas or a mixture or dilution of any of them;

(

b) hydrogen;

"gas company" means a person engaged in the sale

or distribution of gas in British Columbia;

"gas fitter" means an individual who has obtained a certificate of qualification as a gas fitter under this regulation;

"gas installation" means a facility or system,

including fittings, that is owned or operated by a gas company and is used to

store, convey, measure or regulate gas;

"gas utility" means a gas company that owns or

operates a gas installation for conveying gas from a city gate or bulk storage

facility to the outlet of an individual user's meter set;

"homeowner" means the owner of a fully detached dwelling who lives in or intends to live in that dwelling as a permanent residence;

"industry training credential" has the meaning

in the Industry Training Authority Act ;

"landfill gas" means a gas composed of methane, carbon dioxide, water and hydrogen sulphide, or any combination of them, produced from the decomposition of organic waste material at a landfill site;

"licence" means a licence issued by a provincial safety manager in respect of gas systems and gas equipment;

"licensed gas contractor" means a person who holds a licence as a licensed contractor in respect of gas systems;

"liquefied petroleum gas" means a gas composed of a mixture of propane, propylene, butane and butylenes and other hydrocarbons that are gaseous under normal atmospheric conditions of pressure and temperature but can be liquefied under moderate pressure at ambient temperatures;

"manufactured gas" means a gas obtained by the

destructive distillation of carbon derived from coal, coke or oil;

"meter" means a device that measures the volume

of gas passing through it, and includes any components that are attached or

connected to it;

"natural draft appliance" means a Category 1 appliance

as defined in CSA B149.1 that has a draft hood or draft diverter and is

not equipped with a mechanical device for supplying combustion air;

"natural gas" means a naturally occurring mixture of hydrocarbon gases composed predominantly of methane but which may also contain ethane, nitrogen and propane;

"pipeline" has the meaning in the Pipeline Act ;

"propane bulk plant" means a facility that is used primarily for the storage of liquefied petroleum gas before distribution to persons or places outside the facility;

"regulatory authority" means the ministry or a

local government which provides for an inspection service and has authority

to require inspection of regulated work in respect of gas in an area of British Columbia;

"service meter" means a meter that is installed by or on behalf of a gas company;

"service pipe" means a pipe installed by or on behalf of a gas company for the transmission of gas from a distribution main to a meter on the land or premises of the purchaser of the gas;

"trainee" has the meaning in the Industry Training

Authority Act ;

"vehicle" has the meaning in the Motor Vehicle

Act ;

"vehicle fuel system" means gas equipment installed on a vehicle for the provision of motive power;

"vehicle gas system" means gas equipment used for

purposes other than motive power and which is

(

a) used or designed to be used in connection with or

for the purpose of the use, distribution or storage of gas, and

(

b) installed on any vehicle or used or designed to be used to supply or dispense gas for use in, on or by a vehicle;

"vehicle refuelling appliance" means a natural gas compressor package, not containing storage, that is designed for use for unattended refuelling of vehicle fuel systems;

"vent" means a conduit or passageway for conveying

the products of combustion from a gas appliance to the outside air.

Application of this regulation

3 This regulation does not apply to any of the

following:

(

a) a pressure vessel as defined in the Power Engineer, Boiler, Pressure Vessel and Refrigeration Safety Regulation;

(

b) any pipe in which anything is transmitted at a pressure

of greater than 700 kPa gauge, other than gas equipment installed in premises

downstream of an outlet of a gas company's service meter or gas equipment in

a vehicle gas system or vehicle fuel system;

(

c) a piping system used to refine or process gas in any way;

(

d) an internal combustion engine, turbine or any other prime mover;

(

e) a pipeline;

(

f) a vehicle fuel system approved under the Motor

Vehicle Safety Act (Canada).

Part

1 — General Qualification and Licensing Provisions

Division 1 — Individuals Who May

Perform Regulated Work

Individuals who may perform regulated

work

(1) An individual must not perform regulated

work in respect of a gas system or gas equipment unless the individual

(

a) holds a certificate of qualification issued under this Part,

(

b) is authorized to perform regulated work in respect of gas without holding a certificate of qualification,

(

c) has successfully completed a training program recognized by a provincial safety manager,

(

d) holds another certificate of qualification to perform limited work in respect of gas under the Act,

(

e) is a homeowner acting in accordance with

section 24,

(

f) is permitted to do so in accordance with

section 5

of the Safety Standards General Regulation.

(2) An authorized employee of a gas company or an individual who has permission from a gas company may work only with the equipment owned by the gas utility.

(3) An individual must not do welding on metallic gas

piping unless the individual holds a pressure welder's certificate of qualification

issued under the Act.

(4) An individual must not install or interconnect any non-metallic pipe unless the individual has successfully completed training recognized by the provincial safety manager.

(5) A provincial safety manager may, in a permit, require that the regulated work be done by an individual with special welding skills or other skills that are necessary to complete the regulated work safely.

Division 2 — Certificates of Qualification

What all applicants for a certificate

of qualification must do

(1) All applicants for a certificate of qualification,

except applicants for a special purpose certificate, must

(

a) pass an examination for that class of certificate, and

(

b) fulfill any other requirements for that class of certificate as detailed in this regulation.

Class A gas fitter certificate

of qualification

(1) An applicant for a class A gas fitter's

certificate of qualification must have held a class B gas fitter's certificate

of qualification for a minimum of 2 years.

(2) A class A gas fitter certificate of qualification entitles the holder to perform the installation or alteration of any gas system, except vehicle fuel systems, under an appropriate permit.

Class B gas fitter certificate

of qualification

(1) An applicant for a class B certificate of

qualification must

(

a) be the holder of an industry training credential in plumbing, steamfitting, refrigeration or sprinkler fitting,

(

b) be a trainee in a gas fitting program recognized by a provincial safety manager,

(

c) have held a gas utility certificate of qualification

for at least 2 years, or

(

d) have an equivalent combination of experience and training acceptable to a provincial safety manager and have attained the standing acceptable to a provincial safety manager in a gas fitting course and examination that have been approved by a provincial safety manager.

(2) A class B gas fitter certificate of qualification entitles the holder to perform the installation or alteration of the following gas systems under an appropriate permit:

(

a) fan assisted appliances or natural draft appliances which bear the certification mark of an approved testing agency;

(

b) other appliances and vents up to and including 220 kW;

(

c) piping and atmospheric vents.

Class A or B gas fitter may do

limited electrical work

8 The holder of a class A or class B gas fitter's

certificate of qualification may, while employed by a licensed gas contractor

or working under an operating permit, perform electrical work that is restricted

to the installation, repair and maintenance of electrical wiring for solid,

liquid and gaseous-fuel-fired heating equipment for any of the following:

(

a) connecting branch circuit wiring to the heating equipment integral connection box from a junction box or disconnect mounted in close proximity to the heating equipment;

(

b) class 2 circuit wiring up to a rated output of 100 Volt

amps;

(

c) low voltage controls or 24 volt thermostats;

(d) 3 phase motors or controllers integral to the heating equipment.

Duty of gas fitter to notify of

need to repair

9 If it comes to the attention of a gas fitter

that there is a need to have regulated work done by a gas company to any part

of a supply system containing unmeasured gas, the gas fitter must immediately

notify the gas company of that need.

Gas fitter may make temporary

repairs

10 If it comes to the attention of a gas fitter

that gas is leaking from any part of a gas supply system containing unmeasured

gas, the gas fitter must notify the gas company that permanent repairs are necessary and

(

a) safely isolate the system until repairs can be made, or

(

b) make necessary temporary repairs.

Gas appliance service certificate

of qualification

(1) An applicant for an appliance service certificate

of qualification must have successfully completed a course in gas appliance

service training acceptable to a provincial safety manager.

(2) A gas appliance service certificate of qualification entitles the holder to perform the servicing of the following gas systems while employed by a licensed gas contractor or under an appropriate permit:

(

a) gas appliances installed for residential use;

(

b) light commercial appliances up to an input of 82 kW.

Gas piping certificate of qualification

(1) An applicant for a gas piping certificate

of qualification must

(

a) be the holder of a piping industry training credential

acceptable to a provincial safety manager, or

(

b) have had a minimum of 2 years' gas fitting experience

acceptable to a provincial safety manager.

(2) A gas piping certificate of qualification entitles the holder to install and test gas piping under an appropriate permit.

(3) The holder of a gas piping certificate of qualification must not install, service or commission gas appliances.

Recreation vehicle installation

and service certificate of qualification

(1) An applicant for a recreation vehicle installation

and service certificate of qualification must

(

a) provide documented evidence, acceptable to a provincial

safety manager, of a minimum of 2 years experience in the installation

or repair of recreation vehicle appliances and piping, and

(

b) have successfully completed a course in recreation vehicle appliance installation and servicing that is acceptable to a provincial safety manager.

(2) A recreation vehicle installation and service certificate of qualification entitles the holder to maintain, alter, repair and install vehicle gas systems in recreational vehicles under an appropriate permit.

Liquefied petroleum gas vehicle

conversion certificate of qualification

(1) An applicant for a liquefied petroleum

gas vehicle conversion certificate of qualification must have successfully completed

a course in the conversion of vehicles to liquefied petroleum gas that is acceptable

to a provincial safety manager and

(

a) be the holder of a 3 year automotive industry training

credential or an equivalent 3 year automotive trade certificate, or

(

b) provide documented evidence, acceptable to a provincial

safety manager, of a minimum of 3 years of automotive tune-up experience.

(2) A liquefied petroleum gas vehicle conversion certificate of qualification entitles the holder to maintain, alter, repair and install liquefied petroleum gas vehicle fuel systems under an appropriate permit.

Compressed natural gas vehicle

conversion certificate of qualification

(1) An applicant for a compressed natural gas

vehicle conversion certificate of qualification must

(

a) be the holder of a 3 year automotive industry training

credential or an equivalent 3 year automotive trade, or

(

b) have documented evidence, acceptable to a provincial

safety manager, of a minimum of 3 years of automotive tune-up experience, and

(

c) have successfully completed a course in the conversion of vehicles to compressed natural gas that is acceptable to a provincial safety manager.

(2) A compressed natural gas vehicle conversion certificate of qualification entitles the holder to maintain, alter, repair and install compressed natural gas vehicle fuel systems under an operating permit.

Compressed natural gas and liquefied

petroleum gas

vehicle conversion certificate of qualification

(1) An applicant for a compressed natural gas

and liquefied petroleum gas vehicle conversion certificate of qualification

must have successfully completed a course in the conversion of vehicles to compressed

natural gas and liquefied petroleum gas that is acceptable to a provincial safety

manager and

(

a) be the holder of a 3 year automotive industry training

credential or an equivalent 3 year automotive trade certificate, or

(

b) provide documented evidence of a minimum of 3 years of automotive tune-up experience.

(2) A compressed natural gas and liquefied petroleum gas vehicle conversion certificate of qualification entitles the holder to maintain, alter, repair and install compressed natural gas and liquefied petroleum gas vehicle fuel systems under an operating permit.

Gas venting certificate of qualification

(1) An applicant for a gas venting certificate

of qualification must be the holder of a sheet metal industry training credential.

(2) A gas venting certificate of qualification entitles the holder to alter, repair and install venting under an appropriate permit.

Gas utility certificate of qualification

(1) An applicant for a gas utility certificate

of qualification must have successfully completed 2 years of training in

utility installations satisfactory to a provincial safety manager.

(2) A gas utility certificate of qualification entitles the holder, while employed by a gas utility and after gas service is interrupted, to do any of the following:

(

a) relight gas equipment with an input of 120 kW

or less;

(

b) replace thermocouples;

(

c) make other minor repairs;

(

d) do safety checks.

Special purpose gas certificate

of qualification

19 A special purpose certificate of qualification

entitles the holder to perform only the regulated work specified by the certificate

and only under the conditions specifically endorsed on the certificate.

Class A or class B certificates

for individuals

with qualifications from elsewhere in Canada

(1) An applicant for a class A certificate

of qualification who holds a gas fitter's certificate issued by another jurisdiction

in Canada must

(

a) have obtained a class B certificate of qualification,

(

b) have documented evidence, acceptable to a provincial

safety manager, of a minimum of 2 years of experience in the installation

and servicing of gas systems, and

(

c) pass the class A certificate of qualification exam.

(2) An applicant for a class B certificate of qualification who holds a gas fitter's certificate issued by another jurisdiction in Canada must pass the class B certificate of qualification exam and

(

a) have successfully completed a gas fitting apprenticeship,

(

b) have documented evidence, acceptable to a provincial

safety manager, of a minimum of 5 years of experience in the installation

and servicing of gas systems, or

(

c) have an equivalent combination of education and experience acceptable to a provincial safety manager.

Division 3 — Contractor's Licence

Field safety representative not

required for gas contractor's licence

Section 6 (

a) of the Safety Standards General

Regulation does not apply to an application for a gas contractor's licence under

this Division.

Division 4 — Duties of Licensed

Gas Contractor and Permit Holder

Duties of a licensed gas contractor

and permit holder

22 A licensed gas contractor or holder of a permit

must not allow an individual to do the regulated work coming within the scope

of the licence or permit unless the individual is authorized to do so in accordance

with this Part.

Part

2 — Requirements for Permits

Permits that may be issued by

a local government

23 If a local government administers a gas inspection

service under an agreement under

section 5 of the Act, a safety officer

appointed by the local government may issue an installation permit for only

the following kinds of regulated work in respect of gas equipment or gas systems:

(

a) regulated work in a fully detached dwelling serviced

by an individual service meter and supplied with gas at a pressure of 14.0 kPa

gauge or less;

(

b) regulated work in any premises other than a fully

detached dwelling, if the premises are supplied with gas at a pressure of 14.0 kPa

gauge or less and the total load for the building is 120 kW or less.

Homeowner may perform work under

a permit

(1) A homeowner may apply for an installation

permit to perform regulated work with respect to gas equipment in a fully detached

dwelling if

(

a) no person is being paid to do, or assist the owner

in doing, the work, and

(

b) no part of the dwelling is rented to any person.

(2) Section 26 does not apply to a homeowner who performs regulated work under this section.

Drawings to accompany installation

permit application

25 An applicant for an installation permit for

a gas system or proposed gas system must, if required by a provincial safety

manager, provide drawings in support of the application and pay any required

fees.

Installation permit is also authorization

(1) Unless otherwise provided in the installation

permit, if the holder of an installation permit complies with

section 34,

an installation permit issued for regulated work in respect of a gas system

is sufficient authorization for the use of the gas system.

(2) An installation permit for any of the following is authorization to begin the installation or reinstallation of the appliance but not to test or use the appliance until it has passed inspection or an inspection has been waived by the regulatory authority on conditions specified by the regulatory authority:

(

a) any direct-fired non-recirculating type make-up heater;

(

b) a conversion burner, except if it is to be installed

in a single family dwelling and has an input of 120 kW or less;

(

c) a commercial or industrial conversion burner;

(

d) any direct fired equipment;

(

e) a forced draft appliance over 409 600 BTU/hour.

(3) Despite subsection (2) a provincial safety manager may include in an installation permit permission to ignite or operate a regulated product before inspection under conditions specified in the permit.

Field safety representative not

required for installation permit

27 An installation permit issued under this regulation

is not required to name a field safety representative.

Requirements concerning operating

permits

(1) The owner of any of the following must

apply to a provincial safety manager for an operating permit:

(

a) an industrial or commercial establishment with appliances

used for processing or process water heating with a total input greater than

1 500 kW used for purposes other than space heating or domestic water

heating;

(

b) a propane bulk plant;

(

c) an establishment for filling cylinders or vehicle tanks with gas;

(

d) an establishment where regulated products are installed on vehicles as part of the vehicle fuel system;

(

e) an establishment where regulated products are installed on vehicles for purposes other than vehicle fuel systems;

(

f) an establishment that maintains portable heating

appliances of input equal to or less than 300 kW;

(

g) a portable appliance with an input greater than 300 kW

that can be transported from site to site;

(

h) a gas utility.

(2) All regulated work under an operating permit under

subsection (1) (a), (

b) or (

g) must be performed by a gas fitter

or under the direct supervision of a gas fitter and the gas fitter or field

safety representative must complete any records required by the permit.

(3) An individual who performs regulated work under an

operating permit issued under subsection (1) (

d) or (

e) must

hold the appropriate certificate of qualification and must complete and maintain

any records required by the permit.

(4) The operator of an establishment who applies for

a permit under subsection (1) (

d) or (

e) must provide, in the

required form, a bond, in an amount specified by a provincial safety manager,

before being issued an operating permit.

(5) The holder of an operating permit must keep an accurate

record of all regulated work authorized under the permit, including the location

and types of the appliances on which regulated work is performed, and must maintain

those records for a period of 7 years.

(6) If an operating permit has been issued under subsection (1) (

g) the appliance may be operated only by an individual who has been appropriately

trained by

(

a) the manufacturer of the appliance, or

(

b) the manufacturer's representative.

(7) The holder of an operating permit issued under subsection (1) (

a) or (

b) must notify a safety manager in writing of any addition to the gas

system.

(8) An individual must not transfer liquefied petroleum gas from one container to another unless the individual has successfully completed a training course that has been approved by a provincial safety manager and holds a certificate issued following that training course.

(9) The owner of portable equipment that is covered under

an operating permit issued under subsection (1) (

g) must, in writing,

notify a safety officer of the location and relocation of the portable equipment

each time that the portable equipment is moved to a new site.

Duties of owners and licensed

gas contractors

in commercial and industrial buildings

(1) In this section:

"commercial building" has the meaning in CSA B149.1;

"industrial building" has the meaning in CSA B149.1.

(2) Owners of commercial or industrial buildings that

contain appliances with total inputs of 1 500 kW or less but greater

than 220 kW must ensure that those appliances are properly serviced, repaired

and maintained by a licensed gas contractor.

(3) An owner of a commercial or industrial building must,

on the request of a safety manager or safety officer, supply accurate records

of any servicing or repairs done in respect to the appliances in subsection (2).

(4) A licensed gas contractor must, on an annual basis,

supply a provincial safety manager with documentation, in a form that is acceptable

to the safety manager, in respect of any regulated work referred to in subsection

(2) unless that work is exempted under the regulations from requiring inspection

requests or reporting procedures.

Part

3 — Regulated Product Standards and Certification

Canadian gas standards adopted

as B.C. Natural Gas and Propane Code

(1) In this section, "national code"

means the following codes or standards as amended from time to time and each

new edition of the code or standard as issued from time to time:

(

a) CSA-B149.1 Natural Gas and Propane Installation Code;

(

b) CSA-B149.2 Propane Storage and Handling Code;

(

c) the National Standard of Canada CAN/CGA-B149.3 Code for the Field Approval of Fuel-Related Components on Appliances and Equipment;

(

d) the National Standard of Canada CAN/CGA-B109 Natural

Gas for Vehicles Installation Code;

(

e) the National Standards of Canada CAN/CSA-Z662, Oil and Gas Pipeline Systems;

(

f) the National Standard of Canada CAN/CGA-B105 Code for Digester Gas and Landfill Gas Installations;

(

g) CSA B214 Installation Code for Hydronic Heating Systems.

(2) The national code is adopted by reference, with the

changes set out in the Schedule, as the B.C. Natural Gas and Propane Code.

No installation of gas appliances

unless certified or approved

(1) An appliance must not be installed unless

(

a) it has been tested and certified by an approved certification

agency, or

(

b) it has been approved for use under

section 10 of the Act.

(2) Subsection (1) does not apply to an appliance with

a maximum input below 120 kW which is being reinstalled, but no appliance

may be reinstalled unless it has been examined and repaired if necessary and

certified to be in safe working condition by a gas fitter.

(3) A person must not use a portable heater for temporary

heating unless the heater bears a current decal, valid for 2 years, applied

by a gas fitter certifying as to its safety and operation.

Approved testing and certification

agencies

32 The following are approved certification agencies

for the purposes of this regulation:

(

a) Canadian Standards Association;

(

b) Underwriter Laboratories of Canada Ltd.;

(

c) Underwriter Laboratories Inc.;

(

d) Intertek Testing Services NA Ltd.;

(

e) OMNI-Test Laboratories Inc.

Dealers to maintain records of

gas appliances

33 A dealer must keep, for a period of at least

7 years, a record respecting every gas appliance that the dealer sells, showing

the following:

(

a) the name and address of the purchaser;

(

b) the place of installation;

(

c) the type and model number of the appliance.

Part

4 — Inspections

Duty to inform regulatory authority

of completion of work for inspection

(1) On completion of each phase of the gas

system authorized by a permit, the holder of the permit, the gas fitter or the

field safety representative that represents the holder of the permit must immediately

inform the regulatory authority that the regulated work has been performed in

accordance with the Act and request an inspection.

(2) On final completion of the regulated work authorized by a permit, the holder of the permit must immediately complete a notification of completion, installation or alteration form and mail or deliver the completed form to the appropriate regulatory authority.

Part

5 — Safety Officers

Safety officer's certificate

of qualification

35 An application for a gas safety officer's certificate

of qualification must include proof, acceptable to a provincial safety manager,

that the applicant has been the holder of a class A or class B gas

fitter's certificate of qualification and employed as a gas fitter for a minimum

of 5 years.

Part

6 — Technical Requirements

Division 1 — Requirements and Procedures

for Installation and Excavations

Connection for pressure gauge

to be satisfactory

36 If a safety officer requests a connection for

a pressure gauge or a pressure recorder, a person who installs a gas installation

must supply the pressure gauge or connection.

Procedures for a gas installation

in vicinity of underground structures

(1) A person must not install a gas installation

or allow one to be installed so that the gas installation passes through or

interferes with any underground structure that is not solely for the use of

a gas installation without the written permission of the owner of the underground

structure.

(2) A person, unless allowed to do so as a condition of a permit to perform regulated work with respect to gas, must not begin to install or construct an underground structure that will interfere with a gas installation by passing over, passing under or enclosing the gas installation until an agreement has been entered into with the gas company for the removal or alteration of the gas installation.

Duties of persons intending to

construct near gas installation

38 A person who intends to construct an underground

structure within one metre of a gas installation must notify the gas company

operating in the area at least 3 business days before starting the excavation

for the structure.

Procedures for excavations

(1) A person must not excavate or cause any

excavating to be done in the vicinity of a gas installation that is or could

be in any way damaging or dangerous to a gas installation.

(2) A person who intends to excavate must, at least 3 business days before the person intends to excavate, request from the gas company serving that area, or its agent, information on the location of all underground gas installations in the vicinity of the proposed excavation.

(3) A person must not excavate until

(

a) the person ascertains that a request has been made

under subsection (2) and

(

i) the information was provided by the gas company under

subsection (5) and that information revealed that there is no gas installation

in the vicinity, or

(ii) the information was provided by the gas company

under subsection (5) and that information revealed that there is a gas

installation in the vicinity and that installation has been indicated in accordance

with subsection (5), and

(

b) the person ascertains that information provided by

the gas company in respect of the lack of indicators under paragraph (a) (

i) or the presence of indicators under paragraph (a) (ii) was supplied

by the gas company within 10 days before beginning of the excavation.

(4) If the excavator is not satisfied under subsection (3) (b),

the person must verify the information with the gas company before excavating.

(5) On receiving a request under subsection (2) a gas company must

(

a) provide the information requested within 3 business

days, and

(

b) indicate the location of gas installations owned or operated by it in the area where the excavation is intended to be made by one or more of the following methods as appropriate for conditions at the excavation site:

(

i) providing a plan or listing of facility locations by measurement from an ascertainable point on the surface;

(ii) surface staking;

(iii) surface marking.

(6) Prelocated or marked gas installations must be considered

to lie within a zone equal to the diameter of the gas installation plus one

metre on either side of the location indicated by the gas company under subsection (5).

(7) The indicated location of gas installations must be confirmed by the excavator by means of hand digging and the excavator must expose the gas installations at a sufficient number of locations to determine their exact positions and depths before using mechanized excavation equipment for any purpose other than breaking the surface cover.

(8) For existing gas installations of non-metallic material

not provided with tracer wires, the gas company must, on request, indicate the

location, including all changes in direction, of the installation by stakes

or paint or both, at intervals not exceeding 100 metres, and subsection (7)

applies.

(9) If an excavator finds that the gas installation is not within the limits described by the gas company,

(

a) the excavator must so advise the gas company,

(

b) the gas company must immediately assist in locating

and exposing the installation for the excavator, and

(

c) mechanized excavation must not be carried on in the vicinity until the installation has been located and exposed.

(10) As the excavation work progresses, the excavator must

(

a) maintain and keep visible all markings placed by

the gas company that identify the location of the gas installation, or

(

b) if it is impractical to maintain the markings, make other arrangements to ensure that the location of the gas installation is obvious to any observer.

No probing to locate gas installations

40 A person must not probe with pointed tools

to locate gas installations.

Requirements for blasting in

vicinity of gas installation

(1) A person who intends to blast in the vicinity

of a gas installation must

(

a) comply with sections 37 to 39, and

(

b) notify the relevant gas company at least 3 business days before blasting.

(2) If a person has already complied with sections 37

to 39 and discovers in the process of construction that blasting is required,

the person must notify the relevant gas company at least 24 hours, counted

only on business days, before blasting is to start.

Emergency excavation procedures

(1) Sections 37 to 40 do not apply to emergency

excavations if there may be an imminent danger to life, health or property.

(2) A person who excavates under subsection (1) must give notice of the excavation to the relevant gas company operating in that area as soon as practicable.

Procedure for backfilling an

excavation when gas installation exposed

43 A person who backfills an excavation that has

exposed a gas installation must do all of the following:

(

a) take care not to damage the installation, its protective wrapping or any cathodic protection devices;

(

b) thoroughly tamp the backfill under the gas installation;

(

c) adequately support the gas installation to the satisfaction of the gas company and ensure that it will remain in its original line and grade during settlement of the backfill;

(

d) ensure that the backfilling will not diminish lateral support for unexposed parts of the gas installation.

Procedure if gas escapes

44 A person who causes damage to a gas installation

which results in the escape of gas must immediately take the steps reasonable

in the circumstances to do all of the following:

(

a) notify the persons in any premises that may be affected;

(

b) notify the gas company;

(

c) warn all persons in any nearby building in which a gas odour is present to evacuate the building;

(

d) notify a member of the police force having jurisdiction in the place where the installation is located;

(

e) extinguish all flames and sources of ignition in the vicinity of the installation;

(

f) notify the nearest fire department;

(

g) warn traffic, vehicles and pedestrians not to enter the area rendered hazardous by the damage.

Procedure if there is damage

to gas installation

(1) A person who causes damage to a gas installation,

whether or not gas is escaping as a result, must immediately notify the relevant

gas company of the damage.

(2) Serious damage reported to a gas company under subsection

(1) must promptly be reported by the gas company to a provincial safety manager.

Procedure when gas installation

exposed

46 A person who exposes more than 3 metres of

a gas installation must immediately notify the relevant gas company and securely

support the gas installation, to the satisfaction of the gas company, on its

original line and grade at intervals of not more than 3 metres.

Procedure if gas fittings exposed

47 A person who exposes any bell and spigot joints,

mechanical couplings, valves or line insulators must immediately notify the

relevant gas company and adequately support the exposed fittings, to the satisfaction

of the gas company, such that no strain is placed on the gas installation.

Procedures in respect of cathodic

protection devices

(1) A person working in the vicinity of a gas

installation must take all necessary precautions to ensure that no damage is

done to insulators, test wires, sacrificial anodes, anode beds, rectifier wires

and other cathodic protection devices.

(2) If damage is done to any cathodic protection device the person who causes the damage must immediately report the damage to the relevant gas company.

Procedure if damage to protective

wrapping occurs

49 If a person has in any way damaged protective

wrapping on a gas installation the person must do all of the following:

(

a) report the damage to the gas company before the damage is repaired;

(

b) rewrap the gas installation in accordance with the current standards of the gas company;

(

c) ensure that the rewrapped

section is not backfilled until the gas company authorizes the backfilling.

Test charts or reports to be

provided on request

(1) A gas company or gas equipment installer

must, on the request of a provincial safety manager, provide copies of test

pressure charts or test reports, or both, for any gas installation that the

gas company or gas installer is responsible for.

(2) A gas company must provide a report of the total length of distribution gas line extension installed by the gas company in any calendar year to a provincial safety manager.

Provincial safety manager may

require pressure tests

51 A provincial safety manager may, at any reasonable

time, require that a pressure test of a gas installation be conducted by a gas

company in the presence of a safety officer.

Duty of gas company to file construction

standards

with provincial safety manager

(1) A gas company must file with a provincial

safety manager its standards of construction and any amendments made to the

standards.

(2) On request of a safety officer, a gas company must

make any gas installation plan for which the gas company is responsible available

to the safety officer within 24 hours.

Division 2 — Installation and Repair

Procedures for Appliances and Gas Systems

Turning gas supply on and off

(1) A person must not turn off a gas supply

unless there is an imminent safety hazard and the person notifies all affected

consumers.

(2) If a gas supply has been turned off, a person must not turn the supply on again until the person

(

a) notifies all affected consumers, and

(

b) carefully checks all outlets and pilots to ascertain

that they are relighted or turned off.

Unrepairable appliance

(1) A person who finds any appliance or gas

equipment beyond repair or in an unsafe condition must

(

a) place the appliance or gas equipment out of service, and

(

b) promptly notify a safety officer of its condition and location.

(2) If the initial notification under subsection (1) (

b) is verbal, it must be promptly confirmed by a written statement setting out

the facts.

Duties of owner of rental premises

concerning gas appliances

55 The owner of rental premises must

(

a) post a notice, of a permanent nature, respecting the safe operation of an appliance, on the premises in a conspicuous location where it can be seen by any person using the appliance,

(

b) ensure that appliances on the rental premises are maintained in a safe condition, and

(

c) maintain accurate records of maintenance and servicing performed on the gas system on the rental premises.

Gas fitter's tag to be affixed

on completion of work

56 When a gas system installation has been completed,

a gas fitter must affix a tag, bearing the gas fitter's name, certificate of

qualification number, type of appliance and date of affixation,

(

a) if there is a building, to a pipe of that gas system

at the point of entry into the building or at the point where the gas pipe enters

the appliance, or

(

b) if there is no building, at the gas meter or at the point where the gas pipe enters the appliance.

Adjustments on connection to

gas line

57 A person who connects gas to an appliance must

do all of the following:

(

a) adjust and test each appliance the person connects so that it will operate in accordance with the manufacturer's specifications;

(

b) adjust the input rate to the required rate by

(

i) replacing a fixed orifice size,

(ii) changing the adjustment of an adjustable orifice, or

(iii) if a regulator is provided, by readjusting the gas pressure regulator outlet;

(

c) ensure that the appliance vents in a safe and proper manner.

Testing after disconnection

58 If a person disconnects the outlet of a service

meter from the house piping the person must

(

a) remake the joint at the service meter outlet, and

(

b) turn the service meter on again only after testing the house piping and ensuring that no other outlets are open.

Notice to gas company if input

greater than 45 kW

(1) A person must not install an appliance

or cause an appliance to be installed on a gas system without first giving notice

to the gas company that supplies that gas if

(

a) the installation of the appliance will increase the

total connected hourly input ratings of the appliances served by a service meter

to greater than 45 kW, or

(

b) the total connected hourly input rating of the appliances

served by a service meter is greater than 45 kW.

(2) A notice under subsection (1) must state the type and input rating of the appliance and the address of the premises in which the appliance is to be installed.

(3) This

section does not apply to

(

a) a vehicle gas system, or

(

b) gas equipment at a propane bulk plant.

Odorization

(1) All gas that does not naturally possess

a distinctive odour so that its presence in the atmosphere is readily detectable

at all gas concentrations equal to or higher than 1/5 of the lower explosive

limit must have an odorant added to make it so detectable.

(2) Subsection (1) does not apply to gas delivered for

further processing or for use if

(

a) the gas equipment is equipped with gas detection

devices that will detect any gas leakage at an atmospheric concentration equal

to or higher than 1/5 of the lower explosive limit, or

(

b) the odorant would serve no useful purpose as a warning agent.

Part

7 — Information Requests for Existing Gas System

Information requests for an existing

gas system

61 A person who requests information from a provincial

safety manager about an existing gas system must

(

a) provide the written consent of the owner of the premises

where the gas system is installed, and

(

b) pay any required fee.

Schedule

Variations for B.C. Natural

Gas and Propane Code to the National Code

1 Paragraph (

b) of Clause 3.14.6 of CAN/CGA-B149.1-00, the Natural Gas and Propane Installation Code, is repealed and the following substituted:

(

b) the clearance between the appliance and the edge

of the roof or other hazard shall be at least 6 feet (2 m), but this

clearance may be reduced to 3 feet (1

m) if a permanent guard rail

or equivalent protection is provided; and .

2 The following clause is added after Clause 3.14.7 of CSA-B149.1-00:

3.14.8 When it is considered necessary to install

an appliance within screening or within a roof well (a depressed area on a roof),

the following additional requirements apply:

(

a) screening shall have a free opening of not less than 50% of the area of each side;

(

b) there shall be no roof, cover or screens over the well enclosure;

(

c) each appliance shall be installed with not less than

(i) 36 inches (90 cm) clearance from any side of the appliance, or

(ii) the clearance required by the manufacturer of the appliance,

whichever is greater;

(

d) vent terminations with respect to the walls of a screen or roof well shall

(

i) be no higher than the height of the appliance when it is vented atmospherically, or

(ii) not exceed an angle of 45° from the vent outlet of a power or fan assisted venting system;

(

e) when an appliance is installed with screening consisting

of 2 solid walls or is installed in a roof well, fresh air shall not be taken

from within the enclosure unless a 20 foot (6

m) separation can be

maintained between the vent outlet and the fresh air inlet;

(

f) an appliance installed outdoors in an area which is subject to an ambient temperature lower than -40°F (-40°

C) shall be approved by a recognized testing agency for -60°F (-51.1°C), or be an appliance approved for operation to -40°F (- 40°

C) and equipped with a low ambient temperature switch.

3 The following clauses are added after Clause 5.15.14 of CSA-B149.1-00:

5.15.15 A metallic piping system laid underground

shall be cathodically protected regardless of pressure. The only exceptions

are construction camps (if the system is to be used for a limited time), nonmetallic

pipe and copper pipe or tube.

5.15.16 To ensure electrical continuity when a

mechanical fitting is used, each fitting shall be bonded over by No. 6TW

cable attached to the piping by either

(

a) cadwelding, or

(

b) brazing.

5.15.17 Cathodically protected underground piping

shall be buried not less than 12 inches (300 mm) horizontally from

all other underground pipes or conduits, except by special permission.

5.15.18 Where an underground gas pipe crosses

another underground pipe or conduit, a minimum clearance of 2 inches (50 mm)

shall be provided either above or below the gas line in accordance with the

requirements of

section 5.15.

5.15.19 All piping in the protected system shall

be electrically insulated from all other piping by means of suitable electrical

insulating fittings. Anodes shall be magnesium.

4 The following clauses are added after Clause 6.18.6 of CSA-B149.1-00:

(

c) The instructions to the lessee by the lessor shall include, but not be restricted to, the following:

(

i) replacement of tanks and cylinders;

(ii) operation of the construction heater;

(iii) specific tools to be used;

(iv) clearances required from combustible materials;

(

v) shutting off the construction heater;

(vi) checking for leaks;

(vii) moving the construction heater from location to location.

(

d) Maintenance of the construction heater must be performed by the lessor. This work shall include the regulator, hose and fittings.

5 The following clause is added after Clause 6.18.9 of CSA-B149.1-00:

6.18.10 A piping permit is required for the laying

of temporary gas piping to connect a construction heater. This work shall be

done by a qualified gas fitter.

6 Clause 6.23.4 of CSA-B149.1-00 is repealed.

7 The following clauses are added after Clause 6.23.5 of CSA-B149.1-00:

6.23A Gas Appliances Installed in Bedrooms and

Bathrooms

6.23A.1 A gas appliance installed in a bathroom

with a door shall be of the direct vent type only.

6.23A.2 A gas appliance installed in a closet

or a small room having access only through a bathroom, bedroom or bed-sitting

room shall be of the direct vent type or have combustion and ventilation air

supplied to the closet or small room. If any exhaust fan affects the operation

of a gas appliance, the gas appliance shall be isolated from the bathroom using

a sealed opening or door closer.

6.23A.3 A gas appliance installed in a bedroom

shall meet all of the following requirements:

(

a) the appliance must be of the automatic temperature controlled type;

(

b) the appliance must be equipped with a pressure regulator;

(

c) the appliance must have a 100% safety shut-off control valve;

(

d) the appliance must be vented and meet the requirements

for combustion air specified by

section 7.

6.23A.4 A gas appliance (fireplace) installed

as a divider between a bedroom and bathroom shall meet all the requirements

for an installation in a bedroom. In addition, the gas appliance shall be sealed

from the bathroom using material that is impact resistant and thermal shock

proof. Clearance to the tub must be maintained to prevent accidental injury

from the hot surface of the appliance.

8 Clause 7.3.6 of CSA-B149.1-00 is repealed and the following substituted:

7.3.6 An air supply inlet opening from the outdoors

shall

(

a) have a minimum vertical distance of 24 inches

(600 mm) between the bottom of the intake grill and the finished grade

at the point of intake in order to prevent obstruction of the combustion air

intake by snow or other material, and

(

b) not be taken from a car port.

9 The following clause is added after Clause 7.8.2 of CSA-B149.1-00:

7.8.3 When the air supply is provided by mechanical

means from the outdoors for natural draft, partial fan assisted, fan assisted

or power draft assisted burners, the air quantity supplied by the fan shall

be based on 30 cubic feet (0.85 cubic meters) of outside

air for each 1 000 BTU/hour of gas supplied to the burners.

10 The following sections are added after Clause 7.14.12 of CSA-B149.1-00:

7.14A Direct Vent Fireplace Vents

7.14A.1 A direct vent fireplace terminal location

shall not be installed in any area which is not allocated to the occupancy in

which the fireplace is installed.

7.14A.2 In a structure with 3 walls and a roof,

the terminal shall not be installed

(

a) more than 72 inches (183 cm) from the outside opening,

(

b) on any wall that has an opening between the terminal and the open side of the structure, or

(

c) below 84 inches (218 cm) from a deck, patio or balcony without a certified guard.

7.14A.3 A direct vent fireplace shall not be installed

(

a) less than 24 inches below a ceiling or soffit that

has perforations (openings) unless the ceiling or soffit is sealed for a distance

of 24 inches (61 cm) on either side of the centre line of the vent

termination,

(

b) less than 6 feet (183 cm) under a window that opens

on a horizontal plane, or

(

c) directly under a balcony or deck constructed such that there are openings in the deck surface.

Copyright

© 2004: Queen's Printer, Victoria, British Columbia, Canada