Building Construction Standards (2025)
Fla. Stat. ch. 553 (2025)
Florida Statutes
PART I MANUFACTURED BUILDINGS
PART II ACCESSIBILITY BY HANDICAPPED PERSONS
PART III TRENCH SAFETY ACT
PART IV FLORIDA BUILDING CODE
PART V THERMAL EFFICIENCY STANDARDS
PART VI ENERGY CONSERVATION STANDARDS
PART VII STANDARDS FOR RADON-RESISTANT BUILDINGS
PART VIII BUILDING ENERGY-EFFICIENCY RATING SYSTEM
CHAPTER 553
553.35
Short title.
History. — s. 1, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; ss. 2, 3, ch. 81-318; ss. 3, 4, ch. 84-32; s. 4, ch. 91-429.
553.355 Minimum construction requirements established.
History. — s. 54, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372.
553.36
Definitions.
(1) “Approved” means conforming to the requirements of the Florida Building Code.
(2) “Approved inspection agency” means an organization determined by the department to be especially qualified by reason of facilities, personnel, experience, and demonstrated reliability to investigate, test, and evaluate manufactured building units or systems or the component parts thereof, together with the plans, specifications, and quality control procedures to ensure that such units, systems, or component parts are in full compliance with the Florida Building Code and to label such units complying with those standards.
(3) “Closed construction” means that condition when any building, component, assembly, subassembly, or system is manufactured in such a manner that all portions cannot be readily inspected at the installation site without disassembly or destruction thereof.
(4) “Open construction” means any building, building component, assembly, or system manufactured in such a manner that all portions can be readily inspected at the building site without disassembly thereof, damage thereto, or destruction thereof.
(5) “Columbarium” means a permanent structure consisting of niches.
(6) “Component” means any assembly, subassembly, or combination of parts for use as a part of a building, which may include structural, electrical, mechanical, and fire protection systems and other systems affecting health and safety. Components that incorporate elements of a building subject to the product approval system adopted under s. 553.842 are subject to approval in accordance with the product approval system upon implementation thereof and are not subject to the rules adopted under this part. Components to which the rules adopted under this part apply are limited to three-dimensional systems for use as part of a building.
(7) “Department” means the Department of Business and Professional Regulation.
(8) “Factory-built school shelter” means any site-assembled or factory-built school building that is designed to be portable, relocatable, demountable, or reconstructible and that complies with the provisions for enhanced hurricane protection areas, as required by the applicable code.
(9) “Insignia” means an approved device or seal issued by the department to indicate compliance with the standards and rules established pursuant to this part.
(10) “Install” means the assembly of a manufactured building component or system on site and the process of affixing a manufactured building component or system to land, a foundation, or an existing building, and service connections which are a part thereof.
(11) “Local government” means any municipality, county, district, or combination thereof comprising a governmental unit.
(12) “Manufacture” means the process of making, fabricating, constructing, forming, or assembling a product from raw, unfinished, semifinished, or finished materials.
(13) “Manufactured building”, “modular building,” or “factory-built building” means a closed structure, building assembly, or system of subassemblies, which may include structural, electrical, plumbing, heating, ventilating, or other service systems manufactured in manufacturing facilities for installation or erection as a finished building or as part of a finished building, which shall include, but not be limited to, residential, commercial, institutional, storage, and industrial structures.
The term includes buildings not intended for human habitation such as lawn storage buildings and storage sheds manufactured and assembled offsite by a manufacturer certified in conformance with this part. This part does not apply to mobile homes.
(14) “Mobile home” means any residential unit constructed to standards promulgated by the United States Department of Housing and Urban Development.
(15) “Module” means a separately transported three-dimensional component of a manufactured building which contains all or a portion of structural systems, electrical systems, plumbing systems, mechanical systems, fire systems, and thermal systems.
(16) “Private mausoleum” means a structure intended for the private use of a family or group of family members.
(17) “Site” is the location on which a manufactured building is installed or is to be installed.
(18) “System” means structural, plumbing, mechanical, heating, electrical, or ventilating elements, materials, or components combined for use in a building.
History. — s. 2, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; s. 76, ch. 81-167; ss. 2, 3, ch. 81-318; s. 79, ch. 83-55; ss. 3, 4, ch. 84-32; s. 4, ch. 91-429; ss. 55, 56, ch. 2000-141; ss. 21, 34, ch. 2001-186; s. 3, ch. 2001-372; s. 12, ch. 2007-55; s. 5, ch. 2008-191; s. 410, ch. 2011-142.
553.37 Rules; inspections; and insignia.
(1) The Florida Building Commission shall adopt within the Florida Building Code requirements for construction or modification of manufactured buildings and building modules, to address:
(2) The department shall adopt rules to address:
(3) After the effective date of the Florida Building Code, no manufactured building, except as provided in subsection (12), may be installed in this state unless it is approved and bears the insignia of approval of the department and a manufacturer’s data plate. Approvals issued by the department under the provisions of the prior part shall be deemed to comply with the requirements of this part.
(4) All manufactured buildings issued and bearing insignia of approval pursuant to subsection (3) shall be deemed to comply with the Florida Building Code and are exempt from local amendments enacted by any local government.
(5) No manufactured building bearing department insignia of approval pursuant to subsection (3) shall be in any way modified prior to installation, except in conformance with the Florida Building Code.
(6) Manufactured buildings which have been issued and bear the insignia of approval pursuant to this part upon manufacture or first sale shall not require an additional approval or insignia by a local government in which they are subsequently sold or installed. Buildings or structures that meet the definition of “open construction” are subject to permitting by the local jurisdiction and are not required to bear insignia.
(7) If the department determines that the standards for construction and inspection of manufactured buildings prescribed by statute or rule of another state are at least equal to the Florida Building Code and that such standards are actually enforced by such other state, it may provide by rule that the manufactured building which has been inspected and approved by such other state shall be deemed to have been approved by the department and shall authorize the affixing of the appropriate insignia of approval.
(8) The department, by rule, shall establish a
schedule of fees to pay the cost of the administration and enforcement of this part. The rule may provide for manufacturers to pay fees to the administrator directly via the Building Code Information System.
(9) The department may delegate its enforcement authority to a state department having building construction responsibilities or a local government and may enter into contracts for the performance of its administrative duties under this part. The department may delegate its plan review and inspection authority to one or more of the following in any combination:
(10) The department shall develop an insignia to be affixed to all newly constructed buildings by the manufacturer or the inspection agency prior to the building leaving the plant. The department may charge a fee for issuing such insignias. Such insignias shall bear the department’s name, the state seal, an identification number unique to that insignia, and such other information as the department may require by rule.
(11) The department shall by rule develop minimum criteria for manufacturer’s data that must be affixed to all newly constructed buildings by the manufacturer prior to the building leaving the plant.
(12) Custom or one-of-a-kind prototype manufactured buildings are not required to have state approval, but must be in compliance with all local requirements of the governmental agency having jurisdiction at the installation site.
History. — s. 3, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; ss. 1, 4, ch. 80-86; ss. 2, 3, ch. 81-318; ss. 1, 3, 4, ch. 84-32; s. 4, ch. 91-429; s. 1, ch. 98-145; ss. 57, 58, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372; s. 6, ch. 2008-191; s. 28, ch. 2010-176; s. 16, ch. 2014-154.
553.375 Recertification of manufactured buildings.
History. — s. 59, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372; s. 29, ch. 2010-176.
553.38 Application and scope.
History. — s. 4, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; s. 3, ch. 78-323; ss. 1, 6, ch. 79-152; ss. 2, 4, ch. 80-86; ss. 2, 3, ch. 81-318; ss. 3, 4, ch. 84-32; s. 4, ch. 91-429; s. 60, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372.
553.381 Manufacturer certification.
(1) Before manufacturing buildings to be located within this state or selling manufactured buildings within this state, whichever occurs later, a manufacturer must be certified by the department. The department shall certify a manufacturer upon receipt from the manufacturer and approval and verification by the department of the following:
(2) The department may revoke any certification upon the failure of the manufacturer to comply with the Florida Building Code or other requirements of this part.
(3) Certification of manufacturers under this
section shall be for a period of 3 years, subject to renewal by the manufacturer. Upon application for renewal, the manufacturer must submit the information described in subsection (1) or a sworn statement that there has been no change in the status or content of that information since the manufacturer’s last submittal. Fees for renewal of manufacturers’ certification shall be established by the department by rule.
History. — ss. 2, 4, ch. 84-32; s. 4, ch. 91-429; s. 802, ch. 97-103; ss. 61, 62, ch. 2000-141; s. 30, ch. 2001-63; s. 34, ch. 2001-186; s. 3, ch. 2001-372; s. 7, ch. 2008-191.
553.382 Placement of certain housing.
History. — s. 7, ch. 2007-227; s. 411, ch. 2011-142.
553.39 Injunctive relief.
History. — s. 6, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; ss. 3, 4, ch. 80-86; ss. 2, 3, ch. 81-318; ss. 3, 4, ch. 84-32; s. 4, ch. 91-429; s. 63, ch. 2000-141.
553.41 Penalties.
History. — s. 5A, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; ss. 2, 3, ch. 81-318; ss. 3, 4, ch. 84-32; s. 146, ch. 91-224; s. 4, ch. 91-429.
553.415 Factory-built school buildings.
(1) It is the purpose of this
section to provide an alternative procedure for the construction and installation of factory-built school buildings designed or intended for use as school buildings. As used in this section, the term “factory-built school building” means any building designed or intended for use as a school building, which is in whole or in part, manufactured at an offsite facility in compliance with the State Uniform Code for Public Educational Facilities and Department of Education rule, effective on January 5, 2000.
After March 1, 2002, the Uniform Code for Public Educational Facilities shall be incorporated into the Florida Building Code, including specific requirements for Public Educational Facilities and the Department of Education rule, effective on January 5, 2000.
For the purpose of this section, factory-built school buildings include prefabricated educational facilities, factory-built educational facilities, and modular-built educational facilities, that are designed to be portable, relocatable, demountable, or reconstructible; are used primarily as classrooms or the components of an entire school; and do not fall under the provisions of ss. 320.822-320.862.
(2) A manufacturer of factory-built school buildings shall be subject to the certification and enforcement requirements in this part except as provided in this section.
(3) Within 90 days after the effective date of this section, the department shall adopt by emergency rule regulations to carry out the provisions of this section. Such rule shall ensure the safety of design, construction, accessibility, alterations, and inspections and shall also prescribe procedures for the plans, specifications, and methods of construction to be submitted to the department for approval.
(4) A manufacturer of factory-built school buildings designed or intended for use as school buildings shall submit to the department for approval the manufacturer’s plans, specifications, alterations, and methods of construction. The department is authorized to charge manufacturers a fee which reflects the actual expenses incurred for the review of such plans and specifications.
(5) The department, in accordance with the standards and procedures adopted pursuant to this
section and as such standards and procedures may thereafter be modified, shall approve or reject such plans, specifications, and methods of construction. Approval shall not be given unless such plans, specifications, and methods of construction are in compliance with the State Uniform Building Code for Public Educational Facilities and department rule. After March 1, 2002, the Uniform Code for Public Educational Facilities shall be incorporated into the Florida Building Code, including specific requirements for public educational facilities and department rule.
(6) The department may delegate its plans review authority to a state agency or public or private entity; however, the department shall ensure that any person conducting plans reviews is a certified plans examiner, pursuant to
part XII of
chapter 468.
(7) A standard plan approval may be obtained from the department for factory-built school buildings and such department-approved plans shall be accepted by the enforcement agency as approved for the purpose of obtaining a construction permit for the structure itself. The department, or its designated representative, shall determine if the plans qualify for purposes of a factory-built school shelter, as defined in s. 553.36.
(8) Any amendment to the State Uniform Code for Public Educational Facilities, and after March 1, 2002, the Florida Building Code, shall become effective 180 days after the amendment is filed with the Secretary of State. Notwithstanding the 180-day delayed effective date, the manufacturer shall submit and obtain a revised approved plan within the 180 days. A revised plan submitted pursuant to this subsection shall be processed as a renewal or revision with appropriate fees. A plan submitted after the period of time provided shall be processed as a new application with appropriate fees.
(9) The school district or community college district for which any factory-built school building is constructed or altered after July 1, 2001, shall provide for periodic inspection of the proposed factory-built school building during each phase of construction or alteration. The inspector shall act under the direction of the governing board for employment purposes.
This subsection does not prevent a school district or community college district from purchasing or otherwise using a factory-built school building that has been inspected during all phases of construction or alteration conducted after July 1, 2001, by another school district or community college or by an approved inspection agency certified pursuant to s. 553.36(2).
If a factory-built school building is constructed or altered for an entity other than a school district or community college district, such entity may employ at its election a school district, community college district, or such approved inspection agency to conduct such inspections. A school district or community college district so employed may charge such entity for services at reasonable rates comparable to those charged for similar services by approved inspection agencies.
(10) The department shall, by rule, develop forms and reporting periods for the architect or structural engineer in charge of the supervision of the work of construction in the factory, the inspector on the work, and the manufacturer verifying that based upon personal knowledge, the work during the period covered by the report has been performed, and the materials used and installed, in every particular, in accordance with the approved plans and specifications, setting forth such detailed statements of facts as required by the department.
(11) The department shall require that an insignia bearing the department’s name and state seal and a manufacturer’s data plate be affixed to all newly constructed factory-built school buildings and existing factory-built school buildings which have been brought into compliance with the standards for existing “satisfactory” buildings pursuant to
chapter 5 of the Uniform Code for Public Educational Facilities, and after March 1, 2002, the Florida Building Code. The department may charge a fee for issuing such insignias. The manufacturer’s data plate shall, at a minimum, contain:
(12) Such insignia and data plate shall be permanently affixed by the manufacturer in the case of newly constructed factory-built school buildings, or by the department or its designee in the case of an existing factory-built building altered to comply with provisions of s. 1013.20.
(13) As of July 1, 2001, all newly constructed factory-built school buildings shall bear a label pursuant to subsection (12). As of July 1, 2002, existing factory-built school buildings and manufactured buildings used as classrooms and not bearing such label shall not be used as classrooms pursuant to s. 1013.20.
(14) Nothing in this
section shall affect any requirement for compliance with firesafety criteria.
History. — s. 64, ch. 2000-141; s. 22, ch. 2001-186; s. 1, ch. 2001-372; s. 1028, ch. 2002-387; s. 8, ch. 2008-191.
553.42 Legislative intent.
History. — s. 7, ch. 71-172; s. 1, ch. 74-208; s. 3, ch. 76-168; s. 1, ch. 77-457; ss. 1, 6, ch. 79-152; ss. 2, 3, ch. 81-318; ss. 3, 4, ch. 84-32; s. 4, ch. 91-429.
553.501
Short title.
History. — s. 1, ch. 93-183.
553.502 Intent.
History. — s. 1, ch. 93-183; s. 1, ch. 97-76; s. 21, ch. 2011-222.
553.503 Adoption of federal standards.
History. — s. 1, ch. 93-183; s. 2, ch. 97-76; s. 65, ch. 2000-141; s. 59, ch. 2000-154; s. 22, ch. 2011-222.
553.504 Exceptions to applicability of the federal standards.
(1) All new or altered public buildings and facilities, private buildings and facilities, places of public accommodation, and commercial facilities, as those terms are defined by the standards, subject to this part, must comply with this part.
(2) All new single-family houses, duplexes, triplexes, condominiums, and townhouses shall provide at least one bathroom, located with maximum possible privacy, where bathrooms are provided on habitable grade levels, with a door that has a 29-inch clear opening. However, if only a toilet room is provided at grade level, such toilet room must have a clear opening of at least 29 inches.
(3) Notwithstanding the requirements in s. 404.2.9 of the standards, exterior hinged doors must be designed so that such doors can be pushed or pulled open with a force not exceeding 8.5 foot pounds.
(4) In motels and hotels a number of rooms equaling at least 5 percent of the guest rooms minus the number of accessible rooms required by the standards must provide the following special accessibility features:
(5) Notwithstanding ss. 213 and 604 of the standards, required bathing rooms and toilet rooms in new construction shall be designed and constructed in accordance with the following:
(6) Barriers at common or emergency entrances and exits of business establishments conducting business with the general public that are existing, under construction, or under contract for construction which would prevent a person from using such entrances or exits must be removed.
History. — s. 1, ch. 93-183; s. 3, ch. 97-76; s. 23, ch. 2011-222.
553.5041 Parking spaces for persons who have disabilities.
(1) This
section is not intended to expand or diminish the defenses available to a place of public accommodation under the Americans with Disabilities Act and the federal Americans with Disabilities Act Standards for Accessible Design, including, but not limited to, the readily achievable standard, and the standards applicable to alterations to places of public accommodation and commercial facilities. Subject to the exceptions described in subsections (2), (4), (5), and (6), if the parking and loading zone requirements of the federal standards and related regulations provide increased accessibility, those requirements are adopted and incorporated by reference as the law of this state.
(2) State agencies and political subdivisions having jurisdiction over street parking or publicly owned or operated parking facilities are not required to provide a greater right-of-way width than would otherwise be planned under regulations, guidelines, or practices normally applied to new development.
(3) Designated accessible spaces shall be designed and marked for the exclusive use of individuals who have a severe physical disability and have permanent or temporary mobility problems that substantially impair their ability to ambulate and who have been issued a disabled parking permit under s. 316.1958 or s. 320.0848 or a license plate under s. 320.084, s. 320.0842, s. 320.0843, or s. 320.0845.
(4) The number of accessible parking spaces must comply with the parking requirements in s. 208 of the standards and the following:
(5) Accessible perpendicular and diagonal accessible parking spaces and loading zones must be designed and located to conform to ss. 502 and 503 of the standards.
(6) Each such parking space must be striped in a manner that is consistent with the standards of the controlling jurisdiction for other spaces and prominently outlined with blue paint, and must be repainted when necessary, to be clearly distinguishable as a parking space designated for persons who have disabilities.
The space must be posted with a permanent above-grade sign of a color and design approved by the Department of Transportation, which is placed on or at least 60 inches above the finished floor or ground surface measured to the bottom of the sign and which bears the international symbol of accessibility meeting the requirements of s. 703.7.2.1 of the standards and the caption “PARKING BY DISABLED PERMIT ONLY.” Such a sign erected after October 1, 1996, must indicate the penalty for illegal use of the space.
Notwithstanding any other provision of this section, in a theme park or an entertainment complex as defined in s. 509.013 in which accessible parking is located in designated lots or areas, the signage indicating the lot as reserved for accessible parking may be located at the entrances to the lot in lieu of a sign at each parking place. This subsection does not relieve the owner of the responsibility of complying with the signage requirements of s. 502.6 of the standards.
History. — s. 66, ch. 2000-141; s. 24, ch. 2011-222; s. 12, ch. 2012-13.
553.505 Exceptions to applicability of the Americans with Disabilities Act.
History. — s. 1, ch. 93-183; s. 14, ch. 96-200; s. 4, ch. 97-76; s. 23, ch. 2001-186; s. 25, ch. 2011-222.
553.506 Powers of the commission.
History. — s. 1, ch. 93-183; s. 67, ch. 2000-141; s. 60, ch. 2000-154; s. 26, ch. 2011-222.
553.507 Applicability.
(1) All areas of newly designed and newly constructed buildings and facilities as determined by the federal standards established and adopted pursuant to s. 553.503.
(2) Portions of altered buildings and facilities as determined by the federal standards established and adopted pursuant to s. 553.503.
(3) A building or facility that is being converted from residential to nonresidential or mixed use as defined by the Florida Building Code. Such building or facility must, at a minimum, comply with s. 553.508 and the requirements for alterations as determined by the federal standards established and adopted pursuant to s. 553.503.
(4) Buildings and facilities where the original construction or any former alteration or renovation was carried out in violation of applicable permitting law.
History. — s. 1, ch. 93-183; s. 5, ch. 97-76; s. 31, ch. 2001-63; s. 24, ch. 2001-186; s. 27, ch. 2011-222.
553.508 Architectural barrier removal.
History. — s. 1, ch. 93-183.
553.509 Vertical accessibility.
(1) This part and the Americans with Disabilities Act Standards for Accessible Design do not relieve the owner of any building, structure, or facility governed by this part from the duty to provide vertical accessibility to all levels above and below the occupiable grade level, regardless of whether the standards require an elevator to be installed in such building, structure, or facility, except for:
(2) However, buildings, structures, and facilities must, as a minimum, comply with the Americans with Disabilities Act Standards for Accessible Design.
History. — s. 1, ch. 93-183; s. 6, ch. 97-76; s. 12, ch. 2006-71; s. 28, ch. 2011-222.
553.511 Parking facilities; minimum height clearance requirement.
History. — s. 2, ch. 90-250; s. 2, ch. 93-183; s. 7, ch. 97-76.
553.512 Modifications and waivers; advisory council.
(1) The Florida Building Commission shall provide by regulation criteria for granting individual modifications of, or exceptions from, the literal requirements of this part upon a determination of unnecessary, unreasonable, or extreme hardship, provided such waivers shall not violate federal accessibility laws and regulations and shall be reviewed by the Accessibility Advisory Council. The commission shall establish by rule a fee to be paid upon submitting a request for a waiver as provided in this section.
Notwithstanding any other provision of this subsection, if an applicant for a waiver demonstrates economic hardship in accordance with 28 C.F.R. s. 36.403(f)(1), a waiver shall be granted. The commission may not consider waiving any of the requirements of s. 553.5041 unless the applicant first demonstrates that she or he has applied for and been denied waiver or variance from all local government zoning, subdivision regulations, or other ordinances that prevent compliance therewith. Further, the commission may not waive the requirement of s. 553.5041(5)(
a) and (c)1. governing the minimum width of accessible routes and minimum width of accessible parking spaces.
(2) The Accessibility Advisory Council shall consist of the following seven members, who shall be knowledgeable in the area of accessibility for persons with disabilities.
The Secretary of Business and Professional Regulation shall appoint the following: a representative from the Advocacy Center for Persons with Disabilities, Inc.; a representative from the Division of Blind Services; a representative from the Division of Vocational Rehabilitation; a representative from a statewide organization representing the physically handicapped; a representative from the hearing impaired; a representative from the Pensacola Pen Wheels Inc. Employ the Handicapped Council; and a representative of the Paralyzed Veterans of America.
The terms for the first three council members appointed subsequent to October 1, 1991, shall be for 4 years, the terms for the next two council members appointed shall be for 3 years, and the terms for the next two members shall be for 2 years. Thereafter, all council member appointments shall be for terms of 4 years. No council member shall serve more than two 4-year terms subsequent to October 1, 1991. Any member of the council may be replaced by the secretary upon three unexcused absences.
Upon application made in the form provided, an individual waiver or modification may be granted by the commission so long as such modification or waiver is not in conflict with more stringent standards provided in another chapter.
(3) Members of the council shall serve without compensation, but shall be entitled to reimbursement for per diem and travel expenses as provided by s. 112.061.
(4) Meetings of the advisory council shall be held in conjunction with the regular meetings of the commission.
History. — s. 3, ch. 78-333; s. 1, ch. 82-46; s. 2, ch. 83-265; s. 25, ch. 86-220; s. 5, ch. 89-97; ss. 1, 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 2, ch. 93-183; s. 10, ch. 97-76; s. 68, ch. 2000-141; s. 61, ch. 2000-154; s. 13, ch. 2002-293; s. 30, ch. 2010-176; s. 412, ch. 2011-142; s. 15, ch. 2016-129.
553.513 Enforcement.
History. — s. 6, ch. 89-97; s. 2, ch. 93-183.
553.514 Americans with Disabilities Act Standards for Accessible Design.
History. — s. 29, ch. 2011-222.
553.5141 Certifications of conformity and remediation plans.
(1) For purposes of this section:
(2)(
a) An owner of a place of public accommodation who requests that the owner’s facility be inspected by a qualified expert may submit a certification of conformity with the department that indicates that such place of public accommodation conforms to Title III of the Americans with Disabilities Act. Such certification of conformity is valid for 3 years after the date of issuance. Any certification of conformity filed with the department must include:
(3) An owner of a place of public accommodation may file a certificate of conformity or remediation plan with the department. Such filing serves as notice to the public that the place of public accommodation is in compliance with Title III of the Americans with Disabilities Act or that such place of public accommodation is making reasonable efforts to comply with such act.
(4) The department shall develop and maintain a website, accessible to the public, which provides an electronic registry of certifications of conformity and remediation plans.
(5) In any action brought in this state alleging a violation of Title III of the Americans with Disabilities Act, 42 U.S.C. s. 12182, a court must consider any remediation plan or certification of conformity filed in accordance with this
section by a place of public accommodation with the department before the filing of the plaintiff’s complaint, when the court considers and determines if the plaintiff’s complaint was filed in good faith and if the plaintiff is entitled to attorney fees and costs.
History. — s. 1, ch. 2017-139; s. 78, ch. 2020-160.
553.60
Short title.
History. — s. 1, ch. 90-96.
553.61 Intent.
History. — s. 2, ch. 90-96.
553.62 State standard.
History. — s. 3, ch. 90-96; s. 31, ch. 2011-213.
553.63 Trench excavations in excess of 5 feet deep; required information.
(1) The contract bid submitted by the contractor who will perform such excavation shall include:
(2) A contractor performing trench excavation shall:
History. — s. 4, ch. 90-96.
553.64 Certain requirements for contract bids.
History. — s. 5, ch. 90-96.
553.70
Short title.
History. — s. 1, ch. 74-167; s. 1, ch. 77-365.
553.71
Definitions.
(1) “Commission” means the Florida Building Commission created by this part.
(2) “Department” means the Department of Business and Professional Regulation.
(3) “Housing code” means any code or rule intending postconstruction regulation of structures which would include, but not be limited to: standards of maintenance, condition of facilities, condition of systems and components, living conditions, occupancy, use, and room sizes.
(4) “Load management control device” means any device installed by any electric utility or its contractors which temporarily interrupts electric service to major appliances, motors, or other electrical systems contained within the buildings or on the premises of consumers for the purpose of reducing the utility’s system demand as needed in order to prevent curtailment of electric service in whole or in part to consumers and thereby maintain the quality of service to consumers, provided the device is in compliance with a program approved by the Florida Public Service Commission.
(5) “Local enforcement agency” means an agency of local government, a local school board, a community college board of trustees, or a university board of trustees in the State University System with jurisdiction to make inspections of buildings and to enforce the codes which establish standards for design, construction, erection, alteration, repair, modification, or demolition of public or private buildings, structures, or facilities.
(6) “Local technical amendment” means an action by a local governing authority that results in a technical change to the Florida Building Code and its local enforcement.
(7) “Prototype building” means a building constructed in accordance with architectural or engineering plans intended for replication on various sites and which will be updated to comply with the Florida Building Code and applicable laws relating to firesafety, health and sanitation, casualty safety, and requirements for persons with disabilities which are in effect at the time a construction contract is to be awarded.
(8) “Secretary” means the Secretary of Business and Professional Regulation.
(9) “Special inspector” means a licensed architect or registered engineer who is certified under
chapter 471 or
chapter 481 to conduct inspections of threshold buildings.
(10) “State enforcement agency” means the agency of state government with authority to make inspections of buildings and to enforce the codes, as required by this part, which establish standards for design, construction, erection, alteration, repair, modification, or demolition of public or private buildings, structures, or facilities.
(11) “Temporary” includes, but is not limited to, buildings identified by, but not designated as permanent structures on, an approved development order.
(12) “Threshold building” means any building which is greater than three stories or 50 feet in height, or which has an assembly occupancy classification as defined in the Florida Building Code which exceeds 5,000 square feet in area and an occupant content of greater than 500 persons.
History. — s. 2, ch. 74-167; s. 1, ch. 75-111; s. 1, ch. 77-365; s. 4, ch. 78-323; ss. 3, 4, ch. 81-7; s. 77, ch. 81-167; ss. 1, 4, ch. 82-46; s. 80, ch. 83-55; s. 8, ch. 83-160; s. 2, ch. 83-265; s. 1, ch. 84-24; s. 1, ch. 84-365; ss. 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 3, ch. 93-249; s. 37, ch. 98-287; ss. 69, 70, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372; s. 3, ch. 2006-65; s. 58, ch. 2007-217; s. 9, ch. 2008-191; s. 413, ch. 2011-142; s. 13, ch. 2013-193.
553.72 Intent.
(1) The purpose and intent of this act is to provide a mechanism for the uniform adoption, updating, amendment,
interpretation, and enforcement of a single, unified state building code, to be called the Florida Building Code, which consists of a single set of documents that apply to the design, construction, erection, alteration, modification, repair, or demolition of public or private buildings, structures, or facilities in this state and to the enforcement of such requirements and which will allow effective and reasonable protection for public safety, health, and general welfare for all the people of Florida at the most reasonable cost to the consumer.
The Florida Building Code shall be organized to provide consistency and simplicity of use. The Florida Building Code shall be applied, administered, and enforced uniformly and consistently from jurisdiction to jurisdiction. The Florida Building Code shall provide for flexibility to be exercised in a manner that meets minimum requirements, is affordable, does not inhibit competition, and promotes innovation and new technology. The Florida Building Code shall establish minimum standards primarily for public health and lifesafety, and secondarily for protection of property as appropriate.
(2) It is the intent of the Legislature that local governments shall have the power to inspect all buildings, structures, and facilities within their jurisdictions in protection of the public health, safety, and welfare pursuant to chapters 125 and 166.
(3) It is the intent of the Legislature that the Florida Building Code be adopted, modified, updated, interpreted, and maintained by the Florida Building Commission in accordance with ss. 120.536(1) and 120.54 and enforced by authorized state and local government enforcement agencies.
(4) It is the intent of the Legislature that the Florida Fire Prevention Code and the Life Safety Code of this state be adopted, modified, updated, interpreted, and maintained by the Department of Financial Services in accordance with ss. 120.536(1) and 120.54 and included by reference as sections in the Florida Building Code.
(5) It is the intent of the Legislature that there be no conflicting requirements between the Florida Fire Prevention Code and the Life Safety Code of the state and other provisions of the Florida Building Code or conflicts in their enforcement and
interpretation. Potential conflicts shall be resolved through coordination and cooperation of the State Fire Marshal and the Florida Building Commission as provided by this part and
chapter 633.
(6) It is the intent of the Legislature that the nationally recognized private sector third-party testing and evaluation system shall provide product evaluation for the product-approval system and that effective government oversight be established to ensure accountability to the state.
History. — s. 3, ch. 74-167; s. 38, ch. 98-287; ss. 71, 72, ch. 2000-141; ss. 34, 35, ch. 2001-186; ss. 3, 4, ch. 2001-372; s. 662, ch. 2003-261.
553.721 Surcharge.
History. — s. 1, ch. 88-285; s. 4, ch. 91-429; s. 28, ch. 92-173; s. 19, ch. 93-120; s. 33, ch. 93-166; s. 2, ch. 94-284; s. 1, ch. 95-339; s. 2, ch. 98-145; s. 32, ch. 2008-153; s. 31, ch. 2010-176; s. 414, ch. 2011-142; s. 13, ch. 2012-13; s. 17, ch. 2014-154; s. 16, ch. 2016-129; s. 2, ch. 2017-29.
553.73 Florida Building Code.
(1)(
a) The commission shall adopt, by rule pursuant to ss. 120.536(1) and 120.54, the Florida Building Code which shall contain or incorporate by reference all laws and rules which pertain to and govern the design, construction, erection, alteration, modification, repair, and demolition of public and private buildings, structures, and facilities and enforcement of such laws and rules, except as otherwise provided in this section.
(2) The Florida Building Code shall contain provisions or requirements for public and private buildings, structures, and facilities relative to structural, mechanical, electrical, plumbing, energy, and gas systems, existing buildings, historical buildings, manufactured buildings, elevators, coastal construction, lodging facilities, food sales and food service facilities, health care facilities, including assisted living facilities, adult day care facilities, hospice residential and inpatient facilities and units, and facilities for the control of radiation hazards, public or private educational facilities, swimming pools, and correctional facilities and enforcement of and compliance with such provisions or requirements.
Further, the Florida Building Code must provide for uniform implementation of ss. 515.25, 515.27, and 515.29 by including standards and criteria for residential swimming pool barriers, pool covers, latching devices, door and window exit alarms, and other equipment required therein, which are consistent with the intent of s. 515.23. Technical provisions to be contained within the Florida Building Code are restricted to requirements related to the types of materials used and construction methods and standards employed in order to meet criteria specified in the Florida Building Code.
Provisions relating to the personnel, supervision or training of personnel, or any other professional qualification requirements relating to contractors or their workforce may not be included within the Florida Building Code, and subsections (4), (6), (7), (8), and (9) are not to be construed to allow the inclusion of such provisions within the Florida Building Code by amendment. This restriction applies to both initial development and amendment of the Florida Building Code.
(3) The commission shall use the International Codes published by the International Code Council, the National Electric Code (NFPA 70), or other nationally adopted model codes and standards for updates to the Florida Building Code. The commission may approve technical amendments to the code as provided in subsections (8) and (9), subject to all of the following conditions:
(4)(
a) All entities authorized to enforce the Florida Building Code under s. 553.80 shall comply with applicable standards for issuance of mandatory certificates of occupancy, minimum types of inspections, and procedures for plans review and inspections as established by the commission by rule. Local governments may adopt amendments to the administrative provisions of the Florida Building Code, subject to the limitations in this subsection. Local amendments must be more stringent than the minimum standards described in this
section and must be transmitted to the commission within 30 days after enactment. The local government shall make such amendments available to the general public in a usable format. The State Fire Marshal is responsible for establishing the standards and procedures required in this subsection for governmental entities with respect to applying the Florida Fire Prevention Code and the Life Safety Code.
(5) Notwithstanding subsection (4), counties and municipalities may adopt by ordinance an administrative or technical amendment to the Florida Building Code relating to flood resistance in order to implement the National Flood Insurance Program or incentives.
Specifically, an administrative amendment may assign the duty to enforce all or portions of flood-related code provisions to the appropriate agencies of the local government and adopt procedures for variances and exceptions from flood-related code provisions other than provisions for structures seaward of the coastal construction control line consistent with the requirements in 44 C.F.R. s. 60.6. A technical amendment is authorized to the extent it is more stringent than the code.
A technical amendment is not subject to the requirements of subsection (4) and may not be rendered void when the code is updated if the amendment is adopted for the purpose of participating in the Community Rating System promulgated pursuant to 42 U.S.C. s. 4022, the amendment had already been adopted by local ordinance prior to July 1, 2010, or the amendment requires a design flood elevation above the base flood elevation. Any amendment adopted under this subsection shall be transmitted to the commission within 30 days after being adopted.
A municipality, county, or special district may not use preliminary maps issued by the Federal Emergency Management Agency for any law, ordinance, rule, or other measure that has the effect of imposing land use changes or permits.
(6) The initial adoption of, and any subsequent update or amendment to, the Florida Building Code by the commission is deemed adopted for use statewide without adoptions by local government. For a building permit for which an application is submitted prior to the effective date of the Florida Building Code, the state minimum building code in effect in the permitting jurisdiction on the date of the application governs the permitted work for the life of the permit and any extension granted to the permit.
(7)(
a) The commission shall adopt an updated Florida Building Code every 3 years through review of the most current updates of the International Building Code, the International Fuel Gas Code, the International Existing Building Code, the International Mechanical Code, the International Plumbing Code, and the International Residential Code, all of which are copyrighted and published by the International Code Council, and the National Electrical Code, which is copyrighted and published by the National Fire Protection Association.
At a minimum, the commission shall adopt any updates to such codes or any other code necessary to maintain eligibility for federal funding and discounts from the National Flood Insurance Program, the Federal Emergency Management Agency, and the United States Department of Housing and Urban Development. The commission shall also review and adopt updates based on the International Energy Conservation Code (IECC); however, the commission shall maintain the efficiencies of the Florida Energy Efficiency Code for Building Construction adopted and amended pursuant to s. 553.901.
Every 3 years, the commission may approve updates to the Florida Building Code without a finding that the updates are needed in order to accommodate the specific needs of this state. The commission shall adopt updated codes by rule.
(8) Notwithstanding subsection (3) or subsection (7), the commission may address issues identified in this subsection by amending the code under the rule adoption procedures in
chapter 120. Updates to the Florida Building Code, including provisions contained in referenced standards and criteria which relate to wind resistance or the prevention of water intrusion, may not be amended under this subsection to diminish those standards; however, the commission may amend the Florida Building Code to enhance such standards. Following the approval of any amendments to the Florida Building Code by the commission and publication of the amendments on the commission’s website, authorities having jurisdiction to enforce the Florida Building Code may enforce the amendments.
(9)(
a) The commission may approve technical amendments to the Florida Building Code once each year for statewide or regional application upon a finding that the amendment:
(10) The following buildings, structures, and facilities are exempt from the Florida Building Code as provided by law, and any further exemptions shall be as determined by the Legislature and provided by law:
(11)(
a) In the event of a conflict between the Florida Building Code and the Florida Fire Prevention Code and the Life Safety Code as applied to a specific project, the conflict shall be resolved by agreement between the local building code enforcement official and the local fire code enforcement official in favor of the requirement of the code which offers the greatest degree of lifesafety or alternatives which would provide an equivalent degree of lifesafety and an equivalent method of construction.
Local boards created to address issues arising under the Florida Building Code or the Florida Fire Prevention Code may combine the appeals boards to create a single, local board having jurisdiction over matters arising under either code or both codes. The combined local appeals board may grant alternatives or modifications through procedures outlined in NFPA 1,
Section 1.4, but may not waive the requirements of the Florida Fire Prevention Code. To meet the quorum requirement for convening the combined local appeals board, at least one member of the board who is a fire protection contractor, a fire protection design professional, a fire department operations professional, or a fire code enforcement professional must be present.
(12) Except within coastal building zones as defined in s. 161.54, specification standards developed by nationally recognized code promulgation organizations to determine compliance with engineering criteria of the Florida Building Code for wind load design shall not apply to one or two family dwellings which are two stories or less in height unless approved by the commission for use or unless expressly made subject to said standards and criteria by local ordinance adopted in accordance with the provisions of subsection (4).
(13) The Florida Building Code does not apply to, and no code enforcement action shall be brought with respect to, zoning requirements, land use requirements, and owner specifications or programmatic requirements which do not pertain to and govern the design, construction, erection, alteration, modification, repair, or demolition of public or private buildings, structures, or facilities or to programmatic requirements that do not pertain to enforcement of the Florida Building Code.
Additionally, a local code enforcement agency may not administer or enforce the Florida Building Code to prevent the siting of any publicly owned facility, including, but not limited to, correctional facilities, juvenile justice facilities, or state universities, community colleges, or public education facilities, as provided by law.
(14) The general provisions of the Florida Building Code for buildings and other structures shall not apply to commercial wireless communication towers when such general provisions are inconsistent with the provisions of the code controlling radio and television towers. This subsection is intended to be remedial in nature and to clarify existing law.
(15) An agency or local government may not require that existing mechanical equipment located on or above the surface of a roof be installed in compliance with the requirements of the Florida Building Code except during reroofing when the equipment is being replaced or moved and is not in compliance with the provisions of the Florida Building Code relating to roof-mounted mechanical units.
(16) The Florida Building Code must require that the illumination in classroom units be designed to provide and maintain an average of 40 foot-candles of light at each desktop. Public educational facilities must consider using light-emitting diode lighting before considering other lighting sources.
(17) A provision of the International Residential Code relating to mandated fire sprinklers may not be incorporated into the Florida Building Code as adopted by the Florida Building Commission and may not be adopted as a local amendment to the Florida Building Code. This subsection does not prohibit the application of cost-saving incentives for residential fire sprinklers that are authorized in the International Residential Code upon a mutual agreement between the builder and the code official. This subsection does not apply to a local government that has a lawfully adopted ordinance relating to fire sprinklers which has been in effect since January 1, 2010.
(18) In a single-family dwelling, makeup air is not required for range hood exhaust systems capable of exhausting:
(19) The Florida Building Code shall require two fire service access elevators in all buildings with a height greater than 120 feet measured from the elevation of street-level access to the level of the highest occupiable floor. All remaining elevators, if any, shall be provided with Phase I and II emergency operations.
Where a fire service access elevator is required, a 1-hour fire-rated fire service access elevator lobby with direct access from the fire service access elevator is not required if the fire service access elevator opens into an exit access corridor that is no less than 6 feet wide for its entire length and is at least 150 square feet with the exception of door openings, and has a minimum 1-hour fire rating with three-quarter hour fire and smoke rated openings; and during a fire event the fire service access elevator is pressurized and floor-to-floor smoke control is provided.
However, where transient residential occupancies occur at floor levels more than 420 feet above the level of fire service access, a 1-hour fire-rated service access elevator lobby with direct access from the fire service access elevator is required. Standpipes in high-rise buildings of Florida Building Code —
(20) The Florida Building Commission may not:
History. — s. 4, ch. 74-167; s. 3, ch. 75-85; s. 1, ch. 77-365; s. 225, ch. 79-400; s. 1, ch. 80-106; s. 6, ch. 82-197; s. 2, ch. 84-273; s. 1, ch. 85-97; s. 33, ch. 86-191; s. 1, ch. 87-287; s. 1, ch. 88-142; s. 1, ch. 89-369; s. 2, ch. 91-172; s. 41, ch. 91-220; s. 49, ch. 95-144; s. 1, ch. 97-177; ss. 39, 40, 65, ch. 98-287; s. 61, ch. 98-419; ss. 73, 74, 75, ch. 2000-141; s. 62, ch. 2000-154; ss. 25, 34, 35, 36, ch. 2001-186; ss. 2, 3, 4, 5, ch. 2001-372; s. 86, ch. 2002-1; ss. 1, 14, ch. 2002-293; s. 66, ch. 2003-1; s. 663, ch. 2003-261; s. 7, ch. 2005-147; s. 1, ch. 2005-191; s. 4, ch. 2006-65; s. 7, ch. 2007-1; s. 4, ch. 2007-187; s. 140, ch. 2008-4; s. 10, ch. 2008-191; s. 108, ch. 2008-227; s. 1, ch. 2010-99; s. 32, ch. 2010-176; s. 14, ch. 2011-208; s. 30, ch. 2011-222; s. 14, ch. 2012-13; s. 148, ch. 2013-183; s. 14, ch. 2013-193; s. 18, ch. 2014-154; s. 17, ch. 2016-129; s. 11, ch. 2017-149; s. 6, ch. 2019-75; s. 2, ch. 2021-201; s. 2, ch. 2023-137; s. 8, ch. 2023-211; s. 2, ch. 2024-191; s. 3, ch. 2025-42; s. 6, ch. 2025-140.
553.74 Florida Building Commission.
(1) The Florida Building Commission is created and located within the Department of Business and Professional Regulation for administrative purposes. Members are appointed by the Governor subject to confirmation by the Senate. The commission is composed of 19 members, consisting of the following members:
(2) All appointments shall be for terms of 4 years. Each person who is a member of the Board of Building Codes and Standards on the effective date of this act shall serve the remainder of their term as a member of the Florida Building Commission. Any member who shall, during his or her term, cease to meet the qualifications for original appointment, through ceasing to be a practicing member of the profession indicated or otherwise, shall thereby forfeit membership on the commission.
(3) Members of the commission shall serve without compensation, but shall be entitled to reimbursement for per diem and travel expenses as provided by s. 112.061.
(4) Each appointed member is accountable to the Governor for the proper performance of the duties of the office. The Governor shall cause to be investigated any complaint or unfavorable report received concerning an action of the commission or any member and shall take appropriate action thereon. The Governor may remove from office any appointed member for malfeasance, misfeasance, neglect of duty, incompetence, permanent inability to perform official duties, or pleading guilty or nolo contendere to, or being found guilty of, a felony.
History. — s. 5, ch. 74-167; s. 2, ch. 77-365; s. 4, ch. 78-323; ss. 1, 2, ch. 80-231; ss. 1, 3, 4, ch. 81-7; ss. 1, 4, ch. 82-46; s. 2, ch. 83-265; ss. 3, 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 803, ch. 97-103; s. 41, ch. 98-287; s. 76, ch. 2000-141; s. 63, ch. 2000-154; s. 15, ch. 2002-293; ss. 664, 665, ch. 2003-261; s. 11, ch. 2008-191; s. 33, ch. 2010-176; s. 415, ch. 2011-142; s. 31, ch. 2011-222; s. 15, ch. 2013-193; s. 19, ch. 2014-154; s. 67, ch. 2016-10; s. 79, ch. 2020-160.
553.75 Organization of commission; rules and regulations; meetings; staff; fiscal affairs; public comment.
(1) The commission shall meet on call of the secretary. The commission shall annually elect from its appointive members such officers as it may choose.
(2) The commission shall meet at the call of its chair, at the request of a majority of its membership, at the request of the department, or at such times as may be prescribed by its rules. The members shall be notified in writing of the time and place of a regular or special meeting at least 7 days in advance of the meeting. A majority of members of the commission shall constitute a quorum.
(3) The department shall be responsible for the provision of administrative and staff support services relating to the functions of the commission. With respect to matters within the jurisdiction of the commission, the department shall be responsible for the implementation and faithful discharge of all decisions of the commission made pursuant to its authority under the provisions of this part. The department is specifically authorized to use communications media technology in conducting meetings of the commission or any meetings held in conjunction with meetings of the commission.
(4) Meetings of the commission shall be conducted so as to encourage participation by interested persons in attendance. At a minimum, the commission shall provide one opportunity for interested members of the public in attendance at a meeting to comment on each proposed action of the commission before a final vote is taken on any motion.
History. — s. 6, ch. 74-167; s. 4, ch. 78-323; ss. 2, 3, 4, ch. 81-7; ss. 1, 4, ch. 82-46; s. 2, ch. 83-265; ss. 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 804, ch. 97-103; s. 42, ch. 98-287; s. 12, ch. 2008-191.
553.76 General powers of the commission.
(1) Adopt rules pursuant to ss. 120.536(1) and 120.54 to implement the provisions of this part.
(2) Issue memoranda of procedure for its internal management and control. The commission may adopt rules related to its consensus-based decisionmaking process, including, but not limited to, super majority voting requirements. However, the commission must adopt the Florida Building Code, and amendments thereto, by at least a two-thirds vote of the members present at a meeting.
(3) Enter into contracts and do such things as may be necessary and incidental to the discharge of its responsibilities under this part.
(4) Adopt rules pursuant to ss. 120.536(1) and 120.54 to implement the provisions of the Florida Building Code and the provisions of this chapter.
(5) Adopt and promote, in consultation with state and local governments, other boards, advisory councils, and commissions, such recommendations as are deemed appropriate to determine and ensure consistent, effective, and efficient enforcement and compliance with the Florida Building Code, including, but not limited to, voluntary professional standards for the operation of building departments and for personnel development. Recommendations shall include, but not be limited to, provisions for coordination among and between local offices with review responsibilities and their coordination with state or regional offices with special expertise.
History. — s. 7, ch. 74-167; s. 4, ch. 78-323; ss. 3, 4, ch. 81-7; ss. 1, 4, ch. 82-46; s. 2, ch. 83-265; ss. 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 184, ch. 98-200; ss. 43, 44, ch. 98-287; s. 131, ch. 2000-141; s. 35, ch. 2001-186; s. 4, ch. 2001-372; s. 34, ch. 2010-176; s. 12, ch. 2017-149.
553.77 Specific powers of the commission.
(1) The commission shall:
(2) For educational and public information purposes, the commission shall develop and publish an informational and explanatory document which contains descriptions of the roles and responsibilities of the licensed design professional, residential designer, contractor, and local building and fire code officials. The State Fire Marshal shall be responsible for developing and specifying roles and responsibilities for fire code officials. Such document may also contain descriptions of roles and responsibilities of other participants involved in the building codes system.
(3) The commission may provide by rule for plans review and approval of prototype buildings owned by public and private entities to be replicated throughout the state. The rule must allow for review and approval of plans and changes to approved plans for prototype buildings to be performed by a public or private entity with oversight by the commission. The department may charge reasonable fees to cover the administrative costs of the program.
Such approved plans or prototype buildings shall be exempt from further review required by s. 553.79(2), except changes to the prototype design, site plans, and other site-related items. Changes to an approved plan may be approved by the local building department or by the public or private entity that approved the plan. As provided in s. 553.73, prototype buildings are exempt from any locally adopted amendment to any part of the Florida Building Code. Construction or erection of such prototype buildings is subject to local permitting and inspections pursuant to this part.
(4) The commission may produce and distribute a commentary document to accompany the Florida Building Code. The commentary must be limited in effect to providing technical assistance and must not have the effect of binding
interpretations of the code document itself.
(5) The commission may implement its recommendations delivered pursuant to s. 48(2),
chapter 2007-73, Laws of Florida, by amending the Florida Energy Efficiency Code for Building Construction as provided in s. 553.901.
(6) A member of the Florida Building Commission may abstain from voting in any matter before the commission which would inure to the commissioner’s special private gain or loss, which the commissioner knows would inure to the special private gain or loss of any principal by whom he or she is retained or to the parent organization or subsidiary of a corporate principal by which he or she is retained, or which he or she knows would inure to the special private gain or loss of a relative or business associate of the commissioner.
A commissioner shall abstain from voting under the foregoing circumstances if the matter is before the commission under ss. 120.569, 120.60, and 120.80. The commissioner shall, before the vote is taken, publicly state to the assembly the nature of the commissioner’s interest in the matter from which he or she is abstaining from voting and, within 15 days after the vote occurs, disclose the nature of his or her other interest as a public record in a memorandum filed with the person responsible for recording the minutes of the meeting, who shall incorporate the memorandum in the minutes.
(7) Building officials shall recognize and enforce variance orders issued by the Department of Health under s. 514.0115(9), including any conditions attached to the granting of the variance.
History. — s. 8, ch. 74-167; s. 4, ch. 75-85; s. 4, ch. 75-111; s. 3, ch. 77-365; s. 4, ch. 78-323; ss. 5, 8, ch. 79-152; ss. 3, 4, ch. 81-7; ss. 1, 4, ch. 82-46; s. 9, ch. 83-160; s. 2, ch. 83-265; s. 2, ch. 84-365; s. 1, ch. 86-135; s. 1, ch. 88-81; s. 9, ch. 89-139; s. 11, ch. 89-321; ss. 4, 5, 6, ch. 91-172; s. 5, ch. 91-429; s. 311, ch. 92-279; s. 55, ch. 92-326; s. 28, ch. 93-166; s. 51, ch. 95-196; ss. 45, 46, ch. 98-287; ss. 77, 78, 79, ch. 2000-141; ss. 26, 34, 35, ch. 2001-186; ss. 2, 3, 4, ch. 2001-372; s. 16, ch. 2002-293; s. 8, ch. 2005-147; s. 13, ch. 2008-191; s. 13, ch. 2010-143; s. 43, ch. 2011-4; s. 149, ch. 2013-183; s. 20, ch. 2014-154; s. 12, ch. 2016-129; s. 52, ch. 2020-133; s. 2, ch. 2021-68.
553.775
Interpretations.
(1) It is the intent of the Legislature that the Florida Building Code and the Florida Accessibility Code for Building Construction be interpreted by building officials, local enforcement agencies, and the commission in a manner that protects the public safety, health, and welfare at the most reasonable cost to the consumer by ensuring uniform
interpretations throughout the state and by providing processes for resolving disputes regarding
interpretations of the Florida Building Code and the Florida Accessibility Code for Building Construction which are just and expeditious.
(2) Local enforcement agencies, local building officials, state agencies, and the commission shall interpret provisions of the Florida Building Code and the Florida Accessibility Code for Building Construction in a manner that is consistent with declaratory statements and
interpretations entered by the commission, except that conflicts between the Florida Fire Prevention Code and the Florida Building Code shall be resolved in accordance with s. 553.73(11)(
c) and (d).
(3) The following procedures may be invoked regarding
interpretations of the Florida Building Code or the Florida Accessibility Code for Building Construction:
(4) In order to administer this section, the commission may adopt by rule and impose a fee for filing requests for declaratory statements and binding and nonbinding
interpretations to recoup the cost of the proceedings which may not exceed $125 for each request for a nonbinding
interpretation and $250 for each request for a binding review or
interpretation. For proceedings conducted by or in coordination with a third party, the rule may provide that payment be made directly to the third party, who shall remit to the department that portion of the fee necessary to cover the costs of the department.
History. — s. 9, ch. 2005-147; s. 5, ch. 2006-65; s. 8, ch. 2007-1; s. 5, ch. 2007-187; s. 14, ch. 2008-191; s. 35, ch. 2010-176; s. 49, ch. 2013-14; s. 21, ch. 2014-154; s. 18, ch. 2016-129.
553.781 Licensee accountability.
(1) The Legislature finds that accountability for work performed by design professionals and contractors is the key to strong and consistent compliance with the Florida Building Code and, therefore, protection of the public health, safety, and welfare. The purpose of this
section is to provide such accountability.
(2)(
a) Upon a determination by a local jurisdiction that a licensee, certificateholder, or registrant licensed under
chapter 455,
chapter 471,
chapter 481, or
chapter 489 has committed a material violation of the Florida Building Code and failed to correct the violation within a reasonable time, such local jurisdiction shall impose a fine of no less than $500 and no more than $5,000 per material violation.
(3) The Department of Business and Professional Regulation, as an integral part of the automated information system provided under s. 455.2286, shall establish, and local jurisdictions and state licensing boards shall participate in, a system of reporting violations and disciplinary actions taken against all licensees, certificateholders, and registrants under this
section that have been disciplined for a violation of the Florida Building Code. Such information shall be available electronically. Any fines collected by a local jurisdiction pursuant to subsection (2) shall be used initially to help set up the parts of the reporting system for which such local jurisdiction is responsible. Any remaining moneys shall be used solely for enforcing the Florida Building Code, licensing activities relating to the Florida Building Code, or education and training on the Florida Building Code.
(4) Local jurisdictions shall maintain records, readily accessible by the public, regarding material violations and shall report such violations to the Department of Business and Professional Regulation by means of the reporting system provided in s. 455.2286.
History. — s. 47, ch. 98-287; ss. 80, 81, ch. 2000-141; ss. 34, 35, ch. 2001-186; ss. 3, 4, ch. 2001-372.
553.79 Permits; applications; issuance; inspections.
(1)(
a) After the effective date of the Florida Building Code adopted as herein provided, it shall be unlawful for any person, firm, corporation, or governmental entity to construct, erect, alter, modify, repair, or demolish any building within this state without first obtaining a permit therefor from the appropriate enforcing agency or from such persons as may, by appropriate resolution or regulation of the authorized state or local enforcing agency, be delegated authority to issue such permits, upon the payment of such reasonable fees adopted by the enforcing agency.
The enforcing agency is empowered to revoke any such permit upon a determination by the agency that the construction, erection, alteration, modification, repair, or demolition of the building for which the permit was issued is in violation of, or not in conformity with, the provisions of the Florida Building Code. Whenever a permit required under this
section is denied or revoked because the plan, or the construction, erection, alteration, modification, repair, or demolition of a building, is found by the local enforcing agency to be not in compliance with the Florida Building Code, the local enforcing agency shall identify the specific plan or project features that do not comply with the applicable codes, identify the specific code chapters and sections upon which the finding is based, and provide this information to the permit applicant.
A plans reviewer or building code administrator who is responsible for issuing a denial, revocation, or modification request but fails to provide to the permit applicant a reason for denying, revoking, or requesting a modification, based on compliance with the Florida Building Code or local ordinance, is subject to disciplinary action against his or her license pursuant to s. 468.621(1)(i). Installation, replacement, removal, or metering of any load management control device is exempt from and shall not be subject to the permit process and fees otherwise required by this section.
(2)(a)1. Except as provided in subsection (8), an enforcing agency may not issue any permit for construction, erection, alteration, modification, repair, or demolition of any building or structure until the local building code administrator or inspector has reviewed the plans and specifications required by the Florida Building Code, or local amendment thereto, for such proposal and found the plans to be in compliance with the Florida Building Code.
If the local building code administrator or inspector finds that the plans are not in compliance with the Florida Building Code, the local building code administrator or inspector shall identify the specific plan features that do not comply with the applicable codes, identify the specific code chapters and sections upon which the finding is based, and provide this information to the local enforcing agency.
If the building code administrator, plans examiner, or inspector requests another local enforcing agency employee or a person contracted by the local enforcing agency to review the plans and that employee or person identifies specific plan features that do not comply with the applicable codes, the building code administrator, plans examiner, or inspector must provide this information to the local enforcing agency. The local enforcing agency shall provide this information to the permit applicant.
(3) Except as provided in this chapter, the Florida Building Code, after the effective date of adoption pursuant to the provisions of this part, shall supersede all other building construction codes or ordinances in the state, whether at the local or state level and whether adopted by administrative regulation or by legislative enactment. However, this subsection does not apply to the construction of manufactured homes as defined by federal law. Nothing contained in this subsection shall be construed as nullifying or divesting appropriate state or local agencies of authority to make inspections or to enforce the codes within their respective areas of jurisdiction.
(4) The Florida Building Code, after the effective date of adoption pursuant to the provisions of this part, may be modified by local governments to require more stringent standards than those specified in the Florida Building Code, provided the conditions of s. 553.73(4) are met.
(5)(
a) During new construction or during repair or restoration projects in which the structural system or structural loading of a building is being modified, the enforcing agency shall require a special inspector to perform structural inspections on a threshold building pursuant to a structural inspection plan prepared by the engineer or architect of record. The structural inspection plan must be submitted to and approved by the enforcing agency before the issuance of a building permit for the construction of a threshold building.
The purpose of the structural inspection plan is to provide specific inspection procedures and schedules so that the building can be adequately inspected for compliance with the permitted documents. The special inspector may not serve as a surrogate in carrying out the responsibilities of the building official, the architect, or the engineer of record. The contractor’s contractual or statutory obligations are not relieved by any action of the special inspector.
The special inspector shall determine that a professional engineer who specializes in shoring design has inspected the shoring and reshoring for conformance with the shoring and reshoring plans submitted to the enforcing agency. A fee simple title owner of a building, which does not meet the minimum size, height, occupancy, occupancy classification, or number-of-stories criteria which would result in classification as a threshold building under s. 553.71(12), may designate such building as a threshold building, subject to more than the minimum number of inspections required by the Florida Building Code.
(6) A state or local enforcement agency may perform virtual inspections at the discretion of the enforcement agency. However, a state or local enforcement agency may not perform virtual inspections for structural inspections on a threshold building. For purposes of this subsection, the term “virtual inspection” means a form of visual inspection which uses visual or electronic aids to allow a building code administrator or an inspector, or team of inspectors, to perform an inspection without having to be physically present at the job site during the inspection.
(7)(
a) A local enforcement agency must refund 10 percent of the permit and inspection fees to a permitholder if:
(8) A permit may not be issued for any building construction, erection, alteration, modification, repair, or addition unless the applicant for such permit complies with the requirements for plan review established by the Florida Building Commission within the Florida Building Code. However, the code shall set standards and criteria to authorize preliminary construction before completion of all building plans review, including, but not limited to, special permits for the foundation only, and such standards shall take effect concurrent with the first effective date of the Florida Building Code.
After submittal of the appropriate construction documents, the building official may issue a permit for the construction of foundations or any other part of a building or structure before the construction documents for the entire building or structure have been submitted. The holder of such permit for the foundation or other parts of a building or structure shall proceed at the holder’s own risk and without assurance that a permit for the entire structure will be granted. Corrections may be required to meet the requirements of the technical codes.
(9) Each enforcement agency shall require that, on every threshold building:
(10) No enforcing agency may issue a building permit for construction of any threshold building except to a licensed general contractor, as defined in s. 489.105(3)(a), or to a licensed building contractor, as defined in s. 489.105(3)(b), within the scope of her or his license. The named contractor to whom the building permit is issued shall have the responsibility for supervision, direction, management, and control of the construction activities on the project for which the building permit was issued.
(11) Any state agency whose enabling legislation authorizes it to enforce provisions of the Florida Building Code may enter into an agreement with any other unit of government to delegate its responsibility to enforce those provisions and may expend public funds for permit and inspection fees, which fees may be no greater than the fees charged others.
Inspection services that are not required to be performed by a state agency under a federal delegation of responsibility or by a state agency under the Florida Building Code must be performed under the alternative plans review and inspection process created in s. 553.791 or by a local governmental entity having authority to enforce the Florida Building Code.
(12) An enforcing authority may not issue a building permit for any building construction, erection, alteration, modification, repair, or addition unless the permit either includes on its face or there is attached to the permit the following statement: “NOTICE: In addition to the requirements of this permit, there may be additional restrictions applicable to this property that may be found in the public records of this county, and there may be additional permits required from other governmental entities such as water management districts, state agencies, or federal agencies.”
(13) The local enforcing agency may not issue a building permit to construct, develop, or modify a public swimming pool without proof of application, whether complete or incomplete, for an operating permit pursuant to s. 514.031. A certificate of completion or occupancy may not be issued until such operating permit is issued. The local enforcing agency shall conduct its review of the building permit application upon filing and in accordance with this chapter. The local enforcing agency may confer with the Department of Health, if necessary, but may not delay the building permit application review while awaiting comment from the Department of Health.
(14) Nothing in this
section shall be construed to alter or supplement the provisions of
part I of this
chapter relating to manufactured buildings.
(15) One-family and two-family detached residential dwelling units are not subject to plan review by the local fire official as described in this
section or inspection by the local fire official as described in s. 633.216, unless expressly made subject to the plan review or inspection by local ordinance.
(16)(
a) A property owner, regardless of whether the property owner is the one listed on the application for the building permit, may close a building permit by complying with the following requirements:
(17)(
a) A local enforcement agency may not deny issuance of a building permit to; issue a notice of violation to; or fine, penalize, sanction, or assess fees against an arms-length purchaser of a property for value solely because a building permit applied for by a previous owner of the property was not closed. The local enforcement agency shall maintain all rights and remedies against the property owner and contractor listed on the permit.
(18) Certifications by contractors authorized under the provisions of s. 489.115(4)(
b) shall be considered equivalent to sealed plans and specifications by a person licensed under
chapter 471 or
chapter 481 by local enforcement agencies for plans review for permitting purposes relating to compliance with the wind resistance provisions of the code or alternate methodologies approved by the commission for one and two family dwellings. Local enforcement agencies may rely upon such certification by contractors that the plans and specifications submitted conform to the requirements of the code for wind resistance. Upon good cause shown, local government code enforcement agencies may accept or reject plans sealed by persons licensed under
chapter 471,
chapter 481, or
chapter 489. A truss-placement plan is not required to be signed and sealed by an engineer or architect unless prepared by an engineer or architect or specifically required by the Florida Building Code.
(19)(
a) The Florida Building Commission shall establish, within the Florida Building Code adopted by rule, standards for permitting residential buildings or structures moved into or within a county or municipality when such structures do not or cannot comply with the code. However, such buildings or structures shall not be required to be brought into compliance with the building code in force at the time the building or structure is moved, provided:
(20) Notwithstanding any other provision of law, state agencies responsible for the construction, erection, alteration, modification, repair, or demolition of public buildings, or the regulation of public and private buildings, structures, and facilities, shall be subject to enforcement of the Florida Building Code by local jurisdictions. This subsection applies in addition to the jurisdiction and authority of the Department of Financial Services to inspect state-owned buildings.
This subsection does not apply to the jurisdiction and authority of the Department of Agriculture and Consumer Services to inspect amusement rides or the Department of Financial Services to inspect state-owned buildings and boilers.
(21)(
a) A local enforcing agency, and any local building code administrator, inspector, or other official or entity, may not require as a condition of issuance of a one- or two-family residential building permit the inspection of any portion of a building, structure, or real property that is not directly impacted by the construction, erection, alteration, modification, repair, or demolition of the building, structure, or real property for which the permit is sought.
(22) If an assessment of a new building’s interior radio coverage and signal strength under the Florida Fire Prevention Code determines that installation of a two-way radio communication enhancement system is required, a contractor having the appropriate license issued by the department must submit a design to the local authority having jurisdiction for a two-way radio communication enhancement system to correct noncompliant radio coverage.
The local authority having jurisdiction may not withhold issuance of a temporary certificate of occupancy for the building based solely on the need for a two-way radio communication enhancement system. Upon approval of the design by the local authority having jurisdiction, the jurisdiction must require the installation of the two-way radio communication enhancement system within 12 months after the issuance of a temporary certificate of occupancy. An extension for a temporary certificate of occupancy may not be unnecessarily withheld.
(23) For the purpose of inspection and record retention, site plans or building permits may be maintained in the original form or in the form of an electronic copy at the worksite. These plans and permits must be open to inspection by the building official or a duly authorized representative, as required by the Florida Building Code.
(24)(
a) A political subdivision of this state may not adopt or enforce any ordinance or impose any building permit or other development order requirement that:
(25)(
a) A local law, ordinance, or regulation may not prohibit or otherwise restrict the ability of a private property owner to obtain a building permit to demolish his or her single-family residential structure located in a coastal high-hazard area, moderate flood zone, or special flood hazard area according to a Flood Insurance Rate Map issued by the Federal Emergency Management Agency for the purpose of participating in the National Flood Insurance Program if the lowest finished floor elevation of such structure is at or below base flood elevation as established by the Florida Building Code or a higher base flood elevation as may be required by local ordinance, whichever is higher, provided that such permit otherwise complies with all applicable Florida Building Code, Florida Fire Prevention Code, and Life Safety Code requirements, or local amendments thereto.
History. — s. 10, ch. 74-167; s. 4, ch. 77-365; s. 10, ch. 83-160; s. 1, ch. 83-352; s. 2, ch. 84-24; s. 3, ch. 84-365; s. 2, ch. 85-97; s. 2, ch. 86-135; s. 2, ch. 87-287; s. 5, ch. 87-349; s. 2, ch. 88-142; s. 1, ch. 88-378; s. 1, ch. 91-7; s. 4, ch. 93-249; ss. 57, 260, ch. 94-119; s. 7, ch. 94-284; s. 461, ch. 94-356; s. 72, ch. 95-144; s. 2, ch. 95-379; s. 14, ch. 96-298; s. 73, ch. 96-388; s. 1175, ch. 97-103; ss. 48, 49, ch. 98-287; ss. 82, 83, 84, 135, ch. 2000-141; ss. 27, 34, 35, 37, ch. 2001-186; ss. 2, 3, 4, 6, ch. 2001-372; s. 666, ch. 2003-261; s. 10, ch. 2005-147; s. 36, ch. 2010-176; s. 1, ch. 2011-82; s. 73, ch. 2012-5; s. 15, ch. 2012-13; s. 150, ch. 2013-183; s. 16, ch. 2013-193; s. 126, ch. 2014-17; s. 22, ch. 2014-154; ss. 19, 39, ch. 2016-129; s. 36, ch. 2017-3; s. 3, ch. 2017-149; s. 5, ch. 2019-75; s. 11, ch. 2019-86; s. 131, ch. 2020-2; s. 15, ch. 2021-25; s. 3, ch. 2021-201; s. 2, ch. 2021-212; s. 4, ch. 2021-224; s. 3, ch. 2022-136; s. 1, ch. 2023-229; s. 1, ch. 2023-296; s. 227, ch. 2024-6; s. 3, ch. 2024-191; s. 7, ch. 2025-140.
553.791 Alternative plans review and inspection.
(1) As used in this section, the term:
(2)(
a) Notwithstanding any other law or local government ordinance or local policy, the fee owner of a building or structure, or the fee owner’s contractor upon written authorization from the fee owner, may choose to use a private provider to provide building code inspection services with regard to such building or structure and may make payment directly to the private provider for the provision of such services.
All such services shall be the subject of a written contract between the private provider, or the private provider’s firm, and the fee owner or the fee owner’s contractor, upon written authorization of the fee owner. The fee owner may elect to use a private provider to provide plans review or required building inspections, or both.
However, if the fee owner or the fee owner’s contractor uses a private provider to provide plans review, the local building official, in his or her discretion and pursuant to duly adopted policies of the local enforcement agency, may require the fee owner or the fee owner’s contractor to use a private provider to also provide required building inspections.
(3) A private provider and any duly authorized representative may only perform building code inspection services that are within the disciplines covered by that person’s licensure or certification under
chapter 468,
chapter 471, or
chapter 481, including single-trade inspections. A private provider may not provide building code inspection services pursuant to this
section upon any building designed or constructed by the private provider or the private provider’s firm.
(4) A fee owner or the fee owner’s contractor using a private provider to provide building code inspection services shall notify the local building official in writing at the time of permit application, or by 2 p.m. local time, 2 business days before the first scheduled inspection by the local building official or building code enforcement agency that a private provider has been contracted to perform the required inspections of construction under this section, including single-trade inspections, on a form to be adopted by the commission. This notice shall include the following information:
(5) After construction has commenced and if either the local building official is unable to provide inspection services in a timely manner or the work subject to inspection is related to a single-trade inspection for a single-family or two-family dwelling, the fee owner or the fee owner’s contractor may elect to use a private provider to provide inspection services by notifying the local building official of the owner’s or contractor’s intention to do so by 2 p.m. local time, 2 business days before the next scheduled inspection using the notice provided for in paragraphs (4)(a)-(c).
(6) A private provider performing plans review under this
section shall review the plans to determine compliance with the applicable codes. For single-trade plans reviews, a private provider may use an automated or software-based plans review system designed to determine compliance with one or more applicable codes, including, but not limited to, the National Electrical Code and the Florida Building Code. Upon determining that the plans reviewed comply with the applicable codes, the private provider shall prepare an affidavit or affidavits certifying, under oath, that the following is true and correct to the best of the private provider’s knowledge and belief:
(7)(
a) No more than 20 business days, or if the permit application is related to a single-trade plans review for a single-family or two-family dwelling, no more than 5 business days, after receipt of a permit application and the affidavit from the private provider required pursuant to subsection (6), the local building official shall issue the requested permit or provide a written notice to the permit applicant identifying the specific plan features that do not comply with the applicable codes, as well as the specific code chapters and sections.
If the local building official does not provide a written notice of the plan deficiencies within the prescribed time period, the permit application must be deemed approved as a matter of law, and the permit must be issued by the local building official on the next business day.
(8) A private provider performing required inspections under this
section shall inspect each phase of construction as required by the applicable codes. Such inspection, including a single-trade inspection, may be performed in person or virtually. The private provider may have a duly authorized representative perform the required inspections, provided all required reports are prepared by and bear the written or electronic signature of the private provider or the private provider’s duly authorized representative. The duly authorized representative must be an employee of the private provider entitled to receive reemployment assistance benefits under
chapter 443. The contractor’s contractual or legal obligations are not relieved by any action of the private provider.
(9) A private provider performing required inspections under this
section shall provide notice to the local building official of the approximate date and time of any such inspection. The local building official may not prohibit the private provider from performing any inspection outside the local building official’s normal operating hours, including after hours, weekends, or holidays. The local building official may visit the building site as often as necessary to verify that the private provider is performing all required inspections.
A deficiency notice must be posted by the private provider, the duly authorized representative of the private provider, or the building department whenever a noncomplying item related to the building code or the permitted documents is found. Such notice may be physically posted at the job site or electronically posted. After corrections are made, the item must be reinspected by the private provider or representative before being concealed.
Reinspection or reaudit fees shall not be charged by the local jurisdiction as a result of the local jurisdiction’s audit inspection occurring before the performance of the private provider’s inspection or for any other administrative matter not involving the detection of a violation of the building code or a permit requirement.
(10) If the private provider is a person licensed as an engineer under
chapter 471 or an architect under
chapter 481 and affixes his or her professional seal to the affidavit required under subsection (6), the local building official must issue the requested permit or provide a written notice to the permit applicant identifying the specific plan features that do not comply with the applicable codes, as well as the specific code chapters and sections, within 10 business days after receipt of the permit application and affidavit. In such written notice, the local building official must provide with specificity the plan’s deficiencies, the reasons the permit application failed, and the applicable codes being violated.
If the local building official does not provide specific written notice to the permit applicant within the prescribed 10-day period, the permit application is deemed approved as a matter of law, and the local building official must issue the permit on the next business day.
(11) If equipment replacements and repairs must be performed in an emergency situation, subject to the emergency permitting provisions of the Florida Building Code, a private provider may perform emergency inspection services without first notifying the local building official pursuant to subsection (9). A private provider must conduct the inspection within 3 business days after being contacted to conduct an emergency inspection and must submit the inspection report to the local building official within 1 day after the inspection is completed.
(12) Upon completing the required inspections at each applicable phase of construction, the private provider shall record such inspections on a form acceptable to the local building official. The form must bear the written or electronic signature of the provider or the provider’s duly authorized representative. These inspection records shall reflect those inspections required by the applicable codes of each phase of construction for which permitting by a local enforcement agency is required.
The private provider, upon completion of the required inspection, shall post each completed inspection record, indicating pass or fail, and provide the record to the local building official within 2 business days. Such inspection record may be electronically posted by the private provider, or the private provider may post such inspection record physically at the project site. The private provider may electronically transmit the record to the local building official.
The local building official may waive the requirement to provide a record of each inspection within 2 business days if the record is electronically posted or posted at the project site and all such inspection records are submitted with the certificate of compliance. Unless the records have been electronically posted, records of all required and completed inspections shall be maintained at the building site at all times and made available for review by the local building official.
The private provider shall report to the local enforcement agency any condition that poses an immediate threat to public safety and welfare.
(13) Upon completion of all required inspections, the private provider shall prepare a certificate of compliance, on a form acceptable to the local building official, summarizing the inspections performed and including a written representation, under oath, that the stated inspections have been performed and that, to the best of the private provider’s knowledge and belief, the building construction inspected complies with the approved plans and applicable codes.
The statement required of the private provider shall be substantially in the following form and shall be signed and sealed by a private provider as established in subsection (1) or may be electronically transmitted to the local building official:
(14)(
a) No more than 10 business days, or if the permit is related to single-family or two-family dwellings then no more than 2 business days, after receipt of a request for a certificate of occupancy or certificate of completion and the applicant’s presentation of a certificate of compliance and approval of all other government approvals required by law, including the payment of all outstanding fees, the local building official shall issue the certificate of occupancy or certificate of completion or provide a notice to the applicant identifying the specific deficiencies, as well as the specific code chapters and sections.
(15) If the local building official determines that the building construction or plans do not comply with the applicable codes, the official may deny the permit or request for a certificate of occupancy or certificate of completion, as appropriate, or may issue a stop-work order for the project or any portion thereof as provided by law, if the official determines that the noncompliance poses an immediate threat to public safety and welfare, subject to the following:
(16) For the purposes of this section, any notice to be provided by the local building official shall be deemed to be provided to the person or entity when successfully transmitted to the e-mail address listed for that person or entity in the permit application or revised permit application, or, if no e-mail address is stated, when actually received by that person or entity.
(17)(
a) A local enforcement agency, local building official, or local government may not adopt or enforce any laws, rules, procedures, policies, qualifications, or standards more stringent than those prescribed by this section.
(18) A private provider may perform building code inspection services on a building project under this
section only if the private provider maintains insurance for professional liability covering all services performed as a private provider. Such insurance shall have minimum policy limits of $1 million per occurrence and $2 million in the aggregate for any project with a construction cost of $5 million or less and $2 million per occurrence and $4 million in the aggregate for any project with a construction cost of over $5 million. Nothing in this
section limits the ability of a fee owner to require additional insurance or higher policy limits. For these purposes, the term “construction cost” means the total cost of building construction as stated in the building permit application. If the private provider chooses to secure claims-made coverage to fulfill this requirement, the private provider must also maintain coverage for a minimum of 5 years subsequent to the performance of building code inspection services. The insurance required under this subsection shall be written only by insurers authorized to do business in this state with a minimum A.M.
Best’s rating of A. Before providing building code inspection services within a local building official’s jurisdiction, a private provider must provide to the local building official a certificate of insurance evidencing that the coverages required under this subsection are in force.
(19) When performing building code inspection services, a private provider is subject to the disciplinary guidelines of the applicable professional board with jurisdiction over his or her license or certification under
chapter 468,
chapter 471, or
chapter 481. All private providers shall be subject to the disciplinary guidelines of s. 468.621(1)(c)-(h). Any complaint processing, investigation, and discipline that arise out of a private provider’s performance of building code inspection services shall be conducted by the applicable professional board.
(20) A local building code enforcement agency may not audit the performance of building code inspection services by private providers operating within the local jurisdiction until the agency has created standard operating private provider audit procedures for the agency’s internal inspection and review staff, which includes, at a minimum, the private provider audit purpose and scope, private provider audit criteria, an explanation of private provider audit processes and objections, and detailed findings of areas of noncompliance.
Such private provider audit procedures must be publicly available online, and a printed version must be readily accessible in agency buildings. The private provider audit results of staff for the prior two quarters also must be publicly available. The agency’s audit processes must adhere to the agency’s posted standard operating audit procedures.
The same private provider or private provider firm may not be audited more than four times in a year unless the local building official determines a condition of a building constitutes an immediate threat to public safety and welfare, which must be communicated in writing to the private provider or private provider firm. Work on a building or structure may proceed after inspection and approval by a private provider. The work may not be delayed for completion of an inspection audit by the local building code enforcement agency.
(21) The local government, the local building official, and their building code enforcement personnel shall be immune from liability to any person or party for any action or inaction by a fee owner of a building, or by a private provider or its duly authorized representative, in connection with building code inspection services as authorized in this act.
(22) Notwithstanding any other law, a county, a municipality, a school district, or an independent special district may use a private provider to provide building code inspection services for a public works project, an improvement, a building, or any other structure that is owned by the county, municipality, school district, or independent special district.
History. — s. 17, ch. 2002-293; s. 106, ch. 2005-2; s. 11, ch. 2005-147; s. 1, ch. 2005-216; s. 6, ch. 2006-65; s. 6, ch. 2007-187; s. 141, ch. 2008-4; s. 77, ch. 2012-30; s. 7, ch. 2017-149; s. 12, ch. 2019-86; s. 14, ch. 2019-165; s. 132, ch. 2020-2; s. 20, ch. 2020-27; s. 4, ch. 2021-201; s. 50, ch. 2022-4; s. 4, ch. 2022-136; s. 4, ch. 2024-191; s. 8, ch. 2025-140.
553.792 Building permit application to local government.
(1)(
a) A local government must approve, approve with conditions, or deny a building permit application after receipt of a completed and sufficient application within the following timeframes, unless the applicant waives such timeframes in writing:
(2) If any building permit fees are refunded under this section, the surcharges provided in s. 468.631 or s. 553.721 must be recalculated based on the amount of the building permit fees after the refund.
History. — s. 35, ch. 2005-147; s. 63, ch. 2006-1; s. 5, ch. 2021-224; s. 5, ch. 2022-136; s. 38, ch. 2023-17; s. 5, ch. 2024-191.
553.7921 Fire alarm permit application to local enforcement agency.
(1) A contractor must file a Uniform Fire Alarm Permit Application as provided in subsection (3) with the local enforcement agency and must receive the fire alarm permit before installing or replacing a fire alarm, if the local enforcement agency requires a plan review for the installation or replacement.
(2) If the local enforcement agency requires a fire alarm permit in order to repair an existing alarm system that was previously permitted by the local enforcement agency, a contractor must file a Uniform Fire Alarm Permit Application as provided in subsection (3) but may begin work after filing a Uniform Fire Alarm Permit Application as provided in subsection (3). A fire alarm repaired pursuant to this subsection may not be considered compliant with applicable codes and standards until the required permit is issued and the local enforcement agency approves the repair.
(3) A Uniform Fire Alarm Permit Application must be submitted with any drawing, plan, and supporting documentation required by a local enforcement agency for a project for which a plan review or fire alarm permit is required under subsection (1). The application may be submitted electronically or by facsimile and must be signed by the owner, or the owner’s authorized representative, and the contractor, or the contractor’s agent. The application must contain the following information, in a substantially similar form:
History. — s. 15, ch. 2019-140; s. 2, ch. 2021-110; s. 15, ch. 2021-113.
553.7922 Local government-expedited approval of certain permits.
History. — s. 12, ch. 2023-304.
553.793 Streamlined low-voltage alarm system installation permitting.
(1) As used in this section, the term:
(2) Notwithstanding any provision of law, this
section applies to all low-voltage alarm system projects for which a permit is required by a local enforcement agency. However, a permit is not required to install, maintain, inspect, replace, or service a wireless alarm system, including any ancillary components or equipment attached to the system.
(3) A low-voltage electric fence must meet all of the following requirements to be permitted as a low-voltage alarm system project, and no further permit shall be required for the low-voltage alarm system project other than as provided in this section:
(4) This
section does not apply to the installation or replacement of a fire alarm if a plan review is required.
(5) A local enforcement agency shall make uniform basic permit labels available for purchase by a contractor to be used for the installation or replacement of a new or existing alarm system at a cost of not more than $40 per label per project per unit. The local enforcement agency may not require the payment of any additional fees, charges, or expenses associated with the installation or replacement of a new or existing alarm system.
(6) A contractor shall post an unused uniform basic permit label in a conspicuous place on the premises of the low-voltage alarm system project site before commencing work on the project.
(7) A contractor is not required to notify the local enforcement agency before commencing work on a low-voltage alarm system project. However, a contractor must submit a Uniform Notice of a Low-Voltage Alarm System Project as provided under subsection (8) to the local enforcement agency within 14 days after completing the project. A local enforcement agency may take disciplinary action against a contractor who fails to timely submit a Uniform Notice of a Low-Voltage Alarm System Project.
(8) The Uniform Notice of a Low-Voltage Alarm System Project may be submitted electronically or by facsimile if all submissions are signed by the owner, tenant, contractor, or authorized representative of such persons. The Uniform Notice of a Low-Voltage Alarm System Project must contain the following information:
(9) A local enforcement agency may coordinate directly with the owner or customer to inspect a low-voltage alarm system project to ensure compliance with applicable codes and standards. If a low-voltage alarm system project fails an inspection, the contractor must take corrective action as necessary to pass inspection.
(10) A municipality, county, district, or other entity of local government may not adopt or maintain in effect any ordinance or rule regarding a low-voltage alarm system project that provides additional requirements beyond those set out in this
section for the installation or maintenance of a low-voltage alarm system project or that is otherwise inconsistent with this section.
(11) A uniform basic permit label shall not be required for the subsequent maintenance, inspection, or service of an alarm system that was permitted in accordance with this section.
History. — s. 2, ch. 2013-203; s. 1, ch. 2015-50; s. 1, ch. 2017-52; s. 2, ch. 2022-124; s. 1, ch. 2024-207.
553.7931 Alarm system registrations.
(1) As used in this section, the term “applicable local governmental entity” means the local enforcement agency or local law enforcement agency responsible for the administration of alarm system registration in a jurisdiction.
(2) A contractor or alarm system monitoring company is not liable for civil penalties and fines assessed or imposed by the applicable local governmental entity for failing to register an alarm system, for dispatch to an unregistered user, or for excessive false alarms not attributed to alarm system monitoring company error or improper installation by the contractor or alarm system monitoring company.
(3) A municipality, county, district, or other local governmental entity may not require that an alarm system registration form be notarized before an alarm system may be registered.
(4) A municipality, county, district, or other local governmental entity may not adopt or maintain in effect any ordinance or rule regarding alarm system registration that is inconsistent with this section.
History. — s. 20, ch. 2016-129.
553.7932 Simplified permitting processes.
(1) As used in this section, the term:
(2)(
a) A local enforcement agency may require a contractor, as a condition of obtaining a permit for a fire alarm system project or fire sprinkler system project, to submit a completed application and payment.
(3) A local enforcement agency must issue a permit for a fire alarm system project or fire sprinkler system project in person or electronically within 2 business days after submission of a completed application. A contractor may commence work authorized by the permit immediately after submission of a completed application.
(4) The local enforcement agency must provide an inspection within 3 business days after such inspection is requested, to ensure compliance with applicable codes and standards. If a fire alarm system project or fire sprinkler system project fails an inspection, the contractor must take corrective action as necessary to pass inspection.
(5)(
a) For a fire alarm system project, a contractor must keep a copy of the plans and specifications at the fire alarm system project worksite and make such plans and specifications available to the inspector for an onsite plans review at each inspection. If the local enforcement agency determines that it needs additional documents for recording purposes, the contractor must provide such documentation in paper or electronic form to the local enforcement agency within 4 business days after the inspection or 4 days after the documentation is requested, whichever is later.
The local enforcement agency may not require additional plans reviews or documentation of areas or devices outside the scope of permitted work, as needed on permit applications.
(6) A local government that fails to meet a deadline under subsection (3) or subsection (4) must refund the permit fee by 10 percent for each business day after such failure, unless the local government and contractor agree in writing to a reasonable extension of time, the delay is caused by the applicant, or the delay is attributable to a force majeure or other extraordinary circumstances. Each 10-percent refund shall be based on the original amount of the permit fee.
(7) By October 1, 2025, a local enforcement agency must establish a simplified permitting process that complies with this section.
History. — s. 3, ch. 2022-124; s. 1, ch. 2023-224; s. 1, ch. 2025-115.
553.794 Local government residential master building permit program.
(1) MASTER BUILDING PERMIT PROGRAM CREATION. —
(2) DEFINITIONS. —
(3) MASTER BUILDING PERMIT APPLICATION. —
(4) GENERAL CONSTRUCTION PLAN. —
(5) MASTER BUILDING PERMIT APPLICATION APPROVAL PROCESS. —
(6) REVISIONS TO MASTER BUILDING PERMIT. —
(7) SITE-SPECIFIC BUILDING PERMIT APPLICATIONS. —
(8) FEES. —
(9) PENALTIES. —
(10) PROGRAM GUIDELINES. —
History. — s. 1, ch. 2015-156; s. 6, ch. 2021-224.
553.80 Enforcement.
(1) Except as provided in paragraphs (a)-(g), each local government and each legally constituted enforcement district with statutory authority shall regulate building construction and, where authorized in the state agency’s enabling legislation, each state agency shall enforce the Florida Building Code required by this part on all public or private buildings, structures, and facilities, unless such responsibility has been delegated to another unit of government under s. 553.79(11).
(2)(
a) Any two or more counties or municipalities, or any combination thereof, may, in accordance with the provisions of
chapter 163, governing interlocal agreements, form an enforcement district for the purpose of enforcing and administering the provisions of the Florida Building Code. Each district so formed shall be registered with the department on forms to be provided for that purpose. Nothing in this subsection shall be construed to supersede provisions of county charters which preempt municipal authorities respective to building codes.
(3)(
a) Each enforcement district shall be governed by a board, the composition of which shall be determined by the affected localities.
(4) When an enforcement district has been formed as provided herein, upon its registration with the department, it shall have the same authority and responsibility with respect to building codes as provided by this part for local governing bodies.
(5) State and regional agencies with special expertise in building code standards and licensing of contractors and design professionals shall provide support to local governments upon request.
(6) Notwithstanding any other law, state universities, Florida College System institutions, and public school districts shall be subject to enforcement of the Florida Building Code under this part.
(7)(
a) The governing bodies of local governments may provide a
schedule of reasonable fees, as authorized by s. 125.56(2) or s. 166.222 and this section, for enforcing this part. These fees, and any fines or investment earnings related to the fees, may only be used for carrying out the local government’s responsibilities in enforcing the Florida Building Code, including, but not limited to, any process or enforcement related to obtaining or finalizing a building permit. When providing a
schedule of reasonable fees, the total estimated annual revenue derived from fees, and the fines and investment earnings related to the fees, may not exceed the total estimated annual costs of allowable activities. Any unexpended balances must be carried forward to future years for allowable activities or must be refunded at the discretion of the local government. A local government may not carry forward an amount exceeding the average of its operating budget for enforcing the Florida Building Code for the previous 4 fiscal years.
For purposes of this subsection, the term “operating budget” does not include reserve amounts. Any amount exceeding this limit must be used as authorized in subparagraph 2. However, a local government that established, as of January 1, 2019, a Building Inspections Fund Advisory Board consisting of five members from the construction stakeholder community and carries an unexpended balance in excess of the average of its operating budget for the previous 4 fiscal years may continue to carry such excess funds forward upon the recommendation of the advisory board.
The basis for a fee structure for allowable activities must relate to the level of service provided by the local government and must include consideration for refunding fees due to reduced services based on services provided as prescribed by s. 553.791, but not provided by the local government. Fees charged must be consistently applied.
(8) Effective January 1, 2023, local governments located in areas designated in the Federal Emergency Management Agency disaster declarations for Hurricane Ian or Hurricane Nicole may not raise building inspection fees, as authorized by s. 125.56(2) or s. 166.222 and this section, before October 1, 2024. This subsection expires June 30, 2025.
(9) The Department of Agriculture and Consumer Services is not subject to local government permitting requirements, plan review, or inspection fees for agricultural structures, such as equipment storage sheds and pole barns that are not used by the public.
(10) A single-family or two-family dwelling that is converted into a certified recovery residence, as defined in s. 397.311, or a recovery residence, as defined in s. 397.311, that has a charter from an entity recognized or sanctioned by Congress does not have a change of occupancy as defined in the Florida Building Code solely due to such conversion.
History. — s. 11, ch. 74-167; s. 3, ch. 75-111; s. 5, ch. 77-365; s. 3, ch. 85-97; s. 805, ch. 97-103; ss. 50, 51, ch. 98-287; ss. 85, 86, ch. 2000-141; ss. 34, 35, ch. 2001-186; ss. 3, 4, ch. 2001-372; s. 87, ch. 2002-1; s. 27, ch. 2002-20; s. 12, ch. 2005-147; s. 64, ch. 2006-1; s. 15, ch. 2008-191; s. 37, ch. 2010-176; s. 127, ch. 2014-17; s. 276, ch. 2014-19; s. 23, ch. 2014-154; s. 21, ch. 2016-129; s. 10, ch. 2017-149; s. 7, ch. 2019-75; s. 3, ch. 2019-121; s. 6, ch. 2021-128; s. 5, ch. 2021-201; s. 4, ch. 2021-212; s. 6, ch. 2022-136; s. 13, ch. 2023-304; s. 6, ch. 2024-191; s. 3, ch. 2025-177.
553.83 Injunctive relief.
History. — s. 14, ch. 74-167; s. 5, ch. 77-365; s. 87, ch. 2000-141; s. 34, ch. 2001-186; s. 3, ch. 2001-372.
553.835 Implied warranties.
(1) The Legislature finds that the courts have reached different conclusions concerning the scope and extent of the common law doctrine or theory of implied warranty of fitness and merchantability or habitability for improvements immediately supporting the structure of a new home, which creates uncertainty in the state’s fragile real estate and construction industry.
(2) It is the intent of the Legislature to affirm the limitations to the doctrine or theory of implied warranty of fitness and merchantability or habitability associated with the construction and sale of a new home.
(3) As used in this section, the term “offsite improvement” means:
(4) There is no cause of action in law or equity available to a purchaser of a home or to a homeowners’ association based upon the doctrine or theory of implied warranty of fitness and merchantability or habitability for damages to offsite improvements. However, this
section does not alter or limit the existing rights of purchasers of homes or homeowners’ associations to pursue any other cause of action arising from defects in offsite improvements based upon contract, tort, or statute, including, but not limited to, ss. 718.203 and 719.203.
History. — s. 1, ch. 2012-161.
553.837 Mandatory builder warranty.
(1) As used in this section, the term:
(2) A builder shall warrant a newly constructed home for all construction defects of equipment, material, or workmanship furnished by the builder or any subcontractor or supplier resulting in a material violation of the Florida Building Code pursuant to this part, for a period of 1 year after the date of original conveyance of title to the initial owner or after the date of initial occupancy of the dwelling, whichever occurs first. Defects with respect to appliances or equipment that are covered under a manufacturer warranty do not fall within the scope of the required warranty under this subsection.
(3) Notwithstanding any other provision in this section, the terms and conditions of an express written warranty that is provided by a builder to the initial owner of a newly constructed home supersede any provisions in this
section if the express written warranty contains provisions with respect to any of the following:
(4) Enforcement of this
section is limited to a private civil cause of action by a purchaser against any builder that fails to comply with this section. This
section may not be construed to extend the statute of repose beyond that provided by law.
History. — s. 1, ch. 2024-95.
553.84 Statutory civil action.
History. — s. 15, ch. 74-167; s. 88, ch. 2000-141; ss. 28, 34, ch. 2001-186; s. 3, ch. 2001-372; s. 2, ch. 2023-22.
553.841 Building code compliance and mitigation program.
(1) The Legislature finds that knowledge and understanding by persons licensed or employed in the design and construction industries of the importance and need for complying with the Florida Building Code and related laws is vital to the public health, safety, and welfare of this state, especially for protecting consumers and mitigating damage caused by hurricanes to residents and visitors to the state. The Legislature further finds that the Florida Building Code can be effective only if all participants in the design and construction industries maintain a thorough knowledge of the code, code com